Sec. 434.201 Definitions.
For the purposes of this part, the following terms, phrases, and
words shall be defined as provided:
Accessible (as applied to equipment): admitting close approach; not
guarded by locked doors, elevations, or other effective means. (See also
``readily accessible'')
Annual Fuel Utilization Efficiency (AFUE): the ratio of annual
output energy to annual input energy that includes any non-heating
season pilot input loss.
Area of the space (A): the horizontal lighted area of a given space
measured from the inside of the perimeter walls or partitions, at the
height of the working surface.
Automatic: self-acting, operating by its own mechanism when actuated
by some impersonal influence, such as a change in current strength,
pressure, temperature, or mechanical configuration. (See also``manual'')
Automatic flue damper device: an electrically operated device, in
the flue outlet or in the inlet of or upstream of the draft hood of an
individual automatically operated gas-fired appliance, which is designed
to automatically open the flue outlet during appliance operation and to
automatically close off the flue outlet when the appliance is in a
standby condition.
Automatic vent damper device: a device intended for installation in
the venting system, in the outlet of or downstream of the appliance
draft hood, of an individual automatically operated gas-fired appliance,
which is designed to automatically open the venting system when the
appliance is in operation and to automatically close off the venting
system when the appliance is in a standby or shutdown condition.
(1) Electrically operated: an automatic vent damper device that
employs electrical energy to control the device.
(2) Thermally actuated: an automatic vent damper device dependent
for operation exclusively upon the direct conversion of the thermal
energy of the vent gases into mechanical energy.
Boiler capacity: the rated heat output of the boiler, in Btu/h, at
the design inlet and outlet conditions and rated fuel or energy input.
Building: means any structure to be constructed which includes
provision for a heating or cooling system, or both, or for a hot water
system.
Building code: means a legal instrument which is in effect in a
State or unit of general purpose local government, the provisions of
which must be adhered to if a building is to be considered to be in
conformance with law and suitable for occupancy and use.
Building envelope: the elements of a building that enclose
conditioned spaces through which thermal energy may be transferred to or
from the exterior or to or from unconditioned spaces.
Check metering: measurement instrumentation for the supplementary
monitoring of energy consumption (electric, gas, oil, etc) to isolate
the various categories of energy use to permit conservation and control,
in addition to the revenue metering furnished by the utility.
Coefficient of performance (COP)--Cooling: the ratio of the rate of
heat removal to the rate of energy input, in consistent units, for a
complete cooling system or factory assembled equipment, as tested under
a nationally recognized standard or designated operating conditions.
Coefficient of performance (COP) heat pump--Heating: the ratio of
the rate of heat delivered to the rate of energy
[[Page 359]]
input, in consistent units, for a complete heat pump system under
designated operating conditions.
Commercial building: a building other than a residential building,
including any building developed for industrial or public purposes.
Including but not limited to occupancies for assembly, business,
education, institutions, food sales and service, merchants, and storage.
Conditioned floor area: the area of the conditioned space measured
at floor level from the interior surfaces of the walls.
Conditioned space: a cooled space, heated space, or indirectly
conditioned space.
Cooled space: an enclosed space within a building that is cooled by
a cooling system whose sensible capacity:
(1) Exceeds 5 Btu/(h[middot]ft\2\); or
(2) Is capable of maintaining a space dry bulb temperature of
90[deg]F or less at design cooling conditions.
Daylight sensing control (DS): a device that automatically regulates
the power input to electric lighting near the fenestration to maintain
the desired workplace illumination, thus taking advantage of direct or
indirect sunlight.
Daylighted space: the space bounded by vertical planes rising from
the boundaries of the daylighted area on the floor to the floor or roof
above.
Daylighted zone:
(1) Under skylights: the area under each skylight whose horizontal
dimension in each direction is equal to the skylight dimension in that
direction plus either the floor-to-ceiling height or the dimension to an
opaque partition, or one-half the distance to an adjacent skylight or
vertical glazing, whichever is least.
(2) At vertical glazing: the area adjacent to vertical glazing that
receives daylighting from the glazing. For purposes of this definition
and unless more detailed daylighting analysis is provided, the
daylighting zone depth is assumed to extend into the space a distance of
15 ft or to the nearest opaque partition, whichever is less. The
daylighting zone width is assumed to be the width of the window plus
either 2 ft on each side, the distance to an opaque partition, or one
half the distance to an adjacent skylight or vertical glazing, whichever
is least.
Dead band (dead zone): the range of values within which an input
variable that can be varied without initiating any noticeable change in
the output variable.
Degree-day, cooling: a unit, based upon temperature difference and
time, used in estimating cooling energy consumption. For any one day,
when the mean temperature is more than a reference temperature,
typically 65[deg]F, there are as many degree-days as degrees Fahrenheit
temperature difference between the mean temperature for the day and the
reference temperature. Annual cooling degree-days (CDD) are the sum of
the degree-days over a calendar year.
Degree-day, heating: a unit, based upon temperature difference and
time, used in estimating heating energy consumption. For any one day,
when the mean temperature is less than a reference temperature,
typically 65[deg]F, there are as many degree-days as degrees Fahrenheit
temperature difference between the mean temperature for the day and the
reference temperature. Annual heating degree days (HDD) are the sum of
the degree-days over a calendar year.
Dwelling unit: a single housekeeping unit comprised of one or more
rooms providing complete independent living facilities for one or more
persons, including permanent provisions for living, sleeping, eating,
cooking, and sanitation.
Economizer, air: a ducting arrangement and automatic control system
that allows a cooling supply fan system to supply outdoor (outside) air
to reduce or eliminate the need for mechanical refrigeration during mild
or cold weather.
Economizer, water: a system by which the supply air of a cooling
system is cooled directly or indirectly or both by evaporation of water
or by other appropriate fluid in order to reduce or eliminate the need
for mechanical refrigeration.
Efficiency, HVAC system: the ratio of the useful energy output, at
the point of use to the energy input in consistent units, for a
designated time period, expressed in percent.
[[Page 360]]
Emergency system (back-up system): a system that exists for the
purpose of operating in the event of failure of a primary system.
Emergency use: electrical and lighting systems required to supply
power automatically for illumination and equipment in the event of a
failure of the normal power supply.
Energy efficiency ratio (EER): the ratio of net equipment cooling
capacity in Btu/h to total rate of electric input in watts under
designated operating conditions. When consistent units are used, this
ratio becomes equal to COP. (See also ``coefficient of performance''.)
Fan system energy demand: the sum of the demand of all fans that are
required to operate at design conditions to supply air from the heating
or cooling source to the conditioned space(s) and return it back to the
source or exhaust it to the outdoors.
Federal Agency: means any department, agency, corporation, or other
entity or instrumentality of the executive branch of the Federal
Government, including the United States Postal Service, the Federal
National Mortgage Association, and the Federal Home Loan Mortgage
Corporation.
Federal Building: means any building to be constructed by, or for
the use of, any Federal Agency which is not legally subject to State or
local building codes or similar requirements.
Fenestration: any light-transmitting section in a building wall or
roof. The fenestration includes glazing material (which may be glass or
plastic), framing (mullions, muntins, and dividers), external shading
devices, internal shading devices, and integral (between glass) shading
devices.
Fenestration area: the total area of fenestration measured using the
rough opening and including the glass or plastic, sash, and frame. For
doors where the glazed vision area is less than 50% of the door area,
the fenestration area is glazed vision area. For all other doors, the
fenestration area is the door area.
Flue damper: a device, in the flue outlet or in the inlet of or
upstream of the draft hood of an individual automatically operated gas-
fired appliance, which is designed to automatically open the flue outlet
during appliance operation and to automatically close off the flue
outlet when the appliance is in a standby condition.
Gross floor area: the sum of the floor areas of the conditioned
spaces within the building, including basements, mezzanine and
intermediate-floor tiers, and penthouses of headroom height 7.5 ft or
greater. It is measured from the exterior faces of exterior walls or
from the centerline of walls separating buildings (excluding covered
walkways, open roofed-over areas, porches and similar spaces, pipe
trenches, exterior terraces or steps, chimneys, roof overhangs, and
similar features).
Gross lighted area (GLA): the sum of the total lighted areas of a
building measured from the inside of the perimeter walls for each floor
of the building.
Heat capacity (HC): the amount of heat necessary to raise the
temperature of a given mass 1[deg]F. Numerically, the mass expressed per
unit of wall surface multiplied by the specific heat Btu/
(ft\2\[middot][deg]F).
Heat trap: device or piping arrangement that effectively restricts
the natural tendency of hot water to rise in vertical pipes during
standby periods. Examples are the U-shaped arrangement of elbows or a
360-degree loop of tubing.
Heated space: an enclosed space within a building that is heated by
a heating system whose output capacity
(1) Exceeds 10 Btu/(h[middot]ft\2\), or
(2) Is capable of maintaining a space dry-bulb temperature of
50[deg]F or more at design heating conditions.
Heating seasonal performance factor (HSPF): the total heating output
of a heat pump during its normal annual usage period for heating, in
Btu, divided by the total electric energy input during the same period,
in watt-hours.
High rise residential building: hotels, motels, apartments,
condominiums, dormitories, barracks, and other residential-type
facilities that provide complete housekeeping or transient living
quarters and are over three stories in height above grade.
Humidistat: an automatic control device responsive to changes in
humidity.
HVAC system: the equipment, distribution network, and terminals that
[[Page 361]]
provide either collectively or individually the processes of heating,
ventilating, or air conditioning to a building.
Indirectly conditioned space: an enclosed space within the building
that is not a heated or cooled space, whose area-weighted heat transfer
coefficient to heated or cooled spaces exceeds that to the outdoors or
to unconditioned spaces; or through which air from heated or cooled
spaces is transferred at a rate exceeding three air changes per hour.
(See also ``heated space'', ``cooled space'', and ``unconditioned
space''.)
Infiltration: the uncontrolled inward air leakage through cracks and
crevices in any building element and around windows and doors of a
building.
Integrated part-load value (IPLV): a single-number figure of merit
based on part-load EER or COP expressing part-load efficiency for air-
conditioning and heat pump equipment on the basis of weighted operation
at various load capacities for the equipment.
Lumen maintenance control: a device that senses the illumination
level and causes an increase or decrease of illuminance to maintain a
preset illumination level.
Manual: action requiring personal intervention for its control. As
applied to an electric controller, manual control does not necessarily
imply a manual controller but only that personal intervention is
necessary. (See automatic.)
Marked rating: the design load operating conditions of a device as
shown by the manufacturer on the nameplate or otherwise marked on the
device.
Multi-family high rise residential: a residential building
containing three or more dwelling units and is designed to be 3 or more
stories above grade.
Occupancy sensor: a device that detects the presence or absence of
people within an area and causes any combination of lighting, equipment,
or appliances to be adjusted accordingly.
Opaque areas: all exposed areas of a building envelope that enclose
conditioned space except fenestration areas and building service
openings such as vents and grilles.
Orientation: the directional placement of a building on a building
site with reference to the building's longest horizontal axis or, if
there is no longest horizontal axis, then with reference to the
designated main entrance.
Outdoor air: air taken from the exterior of the building that has
not been previously circulated through the building. (See ``ventilation
air'')
Ozone depletion factor: a relative measure of the potency of
chemicals in depleting stratospheric ozone. The ozone depletion factor
potential depends upon the chlorine and the bromine content and
atmospheric lifetime of the chemical. The depletion factor potential is
normalized such that the factor for CFC-11 is set equal to unity and the
factors for the other chemicals indicate their potential relative to
CFC-11.
Packaged terminal air conditioner (PTAC): a factory-selected wall
sleeve and separate unencased combination of heating and cooling
components, assemblies, or sections (intended for mounting through the
wall to serve a single room or zone). It includes heating capability by
hot water, steam, or electricity.
Packaged terminal heat pump: a PTAC capable of using the
refrigeration system in a reverse cycle or heat pump mode to provide
heat.
Plenum: an enclosure that is part of the air-handling system and is
distinguished by having a very low air velocity. A plenum often is
formed in part or in total by portions of the building.
Private driveways, walkways, and parking lots: exterior transit
areas that are associated with a commercial or residential building and
intended for use solely by the employees or tenants and not by the
general public.
Process energy: energy consumed in support of a manufacturing,
industrial, or commercial process other than the maintenance of comfort
and amenities for the occupants of a building.
Process load: the calculated or measured time-integrated load on a
building resulting from the consumption or release of process energy.
Programmable: capable of being preset to certain conditions and
having self-initiation to change to those conditions.
Projection factor: the exterior horizontal shading projection depth
divided
[[Page 362]]
by the sum of the height of the fenestration and the distance from the
top of the fenestration to the bottom of the external shading projection
in units consistent with the projection depth.
Prototype building: a generic building design of the same size and
occupancy type as the proposed design that complies with the
prescriptive requirements of subpart D of this part and has prescribed
assumptions used to generate the energy budget concerning shape,
orientation, and HVAC and other system designs.
Public driveways, walkways, and parking lots: exterior transit areas
that are intended for use by the general public.
Public facility restroom: a restroom used by the transient public.
Readily accessible: capable of being reached quickly for operation,
renewal, or inspections without requiring those to whom ready access is
requisite to climb over or remove obstacles or to resort to portable
ladders, chairs, etc. (See also accessible.)
Recooling: lowering the temperature of air that has been previously
heated by a heating system.
Reference building: a specific building design that has the same
form, orientation, and basic systems as the prospective design that is
to be evaluated for compliance and meets all the criteria listed in
subsection 501.2 or subsection 601.2.
Reheating: raising the temperature of air that has been previously
cooled either by refrigeration or an economizer system.
Reset: adjustment of the controller setpoint to a higher or lower
value automatically or manually.
Roof: those portions of the building envelope, including all opaque
surfaces, fenestration, doors, and hatches, that are above conditioned
space and are horizontal or tilted at less than 60[deg] from horizontal.
(See also''walls'')
Room air conditioner: an encased assembly designed as a unit to be
mounted in a window or through a wall or as a console. It is designed
primarily to provide free delivery of conditioned air to an enclosed
space, room, or zone. It includes a prime source of refrigeration for
cooling and dehumidification and means for circulating and cleaning air
and may also include means for ventilating and heating.
Seasonal energy efficiency ratio (SEER): the total cooling output of
an air conditioner during its normal annual usage period for cooling, in
Btu, divided by the total electric energy input during the same period,
in watt-hours.
Service systems: all energy-using or energy-distributing components
in a building that are operated to support the occupant or process
functions housed therein (including HVAC, service water heating,
illumination, transportation, cooking or food preparation, laundering,
or similar functions).
Service water heating: the supply of hot water for purposes other
than comfort heating and process requirements.
Shading coefficient (SC): the ratio of solar heat gain through
fenestration under a specific set of conditions, with or without
integral shading devices, to that occurring through unshaded \1/8\-in-
thick clear double-strength glass under the same conditions.
Shell Building: a building for which the envelope is designed,
constructed, or both prior to knowing the occupancy type. (See also
``speculative building'')
Single-Line Diagram: a simplified schematic drawing that shows the
connection between two or more items. Common multiple connections are
shown as one line.
Skylight: glazing that is horizontal or tilted less than 60[deg]
from horizontal.
Solar energy source: natural daylighting or thermal, chemical, or
electrical energy derived from direct conversion of incident solar
radiation at the building site.
Solar heat gain coefficient (SHGC): the ratio of the solar heat gain
entering the space through the fenestration area to the incident solar
radiation. Solar heat gain includes directly transmitted solar heat and
absorbed solar radiation, which is then reradiated, conducted, or
convected into the space. (See fenestration area)
Speculative building: a building for which the envelope is designed,
constructed, or both prior to the design of the lighting, HVAC systems,
or both. A speculative building differs from a
[[Page 363]]
shell building in that the intended occupancy is known for the
speculative building. (See also ``shell building'')
System: a combination of equipment and/or controls, accessories,
interconnecting means, and terminal elements by which energy is
transformed so as to perform a specific function, such as HVAC, service
water heating, or illumination.
Tandem wiring: pairs of luminaries operating with lamps in each
luminaire powered from a single ballast contained in one of the
luminaires.
Task lighting: lighting that provides illumination for specific
functions and is directed to a specific surface or area.
Task location: an area of the space where significant visual
functions are performed and where lighting is required above and beyond
that required for general ambient use.
Terminal element: a device by which the transformed energy from a
system is finally delivered. Examples include registers, diffusers,
lighting fixtures, and faucets.
Thermal conductance (C): the constant time rate of heat flow through
the unit area of a body induced by a unit temperature difference between
the surfaces, expressed in Btu/(h[middot]ft\2\[middot][deg]F). It is the
reciprocal of thermal resistance. (See ``thermal resistance'')
Thermal mass: materials with mass heat capacity and surface area
capable of affecting building loads by storing and releasing heat as the
interior or exterior temperature and radiant conditions fluctuate. (See
also ``heat capacity'' and ``wall heat capacity'')
Thermal mass wall insulation position:
(1) Exterior insulation position: a wall having all or nearly all of
its mass exposed to the room air with the insulation on the exterior of
that mass.
(2) Integral insulation position: a wall having mass exposed to both
room and outside (outside) air with substantially equal amounts of mass
on the inside and outside of the insulation layer.
(3) Interior insulation position: a wall not meeting either of the
above definitions, particularly a wall having most of its mass external
to an insulation layer.
Thermal resistance (R): the reciprocal of thermal conductance 1/C,
l/H, 1/U; expressed in (h[middot]ft2. [deg]F)/Btu.
Thermal transmittance (U): the overall coefficient of heat transfer
from air to air. It is the time rate of heat flow per unit area under
steady conditions from the fluid on the warm side of the barrier to the
fluid on the cold side, per unit temperature difference between the two
fluids, expressed in Btu/(h[middot]ft2. [deg]F).
Thermal transmittance, overall (Uo): the gross overall (area
weighted average) coefficient of heat transfer from air to air for a
gross area of the building envelope, Btu/(h[middot]ft2.
[deg]F). The Uo value applies to the combined effect of the
time rate of heat flows through the various parallel paths, such as
windows, doors, and opaque construction areas, composing the gross area
of one or more building envelope components, such as walls, floors, and
roof or ceiling.
Thermostat: an automatic control device responsive to temperature.
Unconditioned space: space within a building that is not a
conditioned space. (See ``conditioned space'')
Unitary cooling equipment: one or more factory-made assemblies that
normally include an evaporator or cooling coil, a compressor, and a
condenser combination (and may also include a heating function).
Unitary heat pump: one or more factory-made assemblies that normally
include an indoor conditioning coil, compressor(s), and outdoor coil or
refrigerant-to-water heater exchanger, including means to provide both
heating and cooling functions.
Variable-air-volume (VAV) HVAC system: HVAC systems that control the
dry-bulb temperature within a space by varying the volume of heated or
cooled supply air to the space.
Vent damper: a device intended for installation in the venting
system, in the outlet of or downstream of the appliance draft hood, of
an individual automatically operating gas-fired appliance, which is
designed to automatically open the venting system when the appliance is
in operation and to automatically close off the venting system when the
appliance is in a standby or shutdown condition.
[[Page 364]]
Ventilation: the process of supplying or removing air by natural or
mechanical means to or from any space. Such air may or may not have been
conditioned.
Ventilation air: that portion of supply air which comes from the
outside, plus any recirculated air, to maintain the desired quality of
air within a designated space. (See also ``outdoor air'')
Visible light transmittance: the fraction of solar radiation in the
visible light spectrum that passes through the fenestration (window,
clerestory, or skylight).
Walls: those portions of the building envelope enclosing conditioned
space, including all opaque surfaces, fenestration, and doors, which are
vertical or tilted at an angle of 60* from horizontal or greater. (See
also ``roof'')
Wall heat capacity: the sum of the products of the mass of each
individual material in the wall per unit area of wall surface times its
individual specific heat, expressed in Btu/(ft
2[middot][deg]F). (See'' thermal mass'')
Window to wall ratio (WWR): the ratio of the wall fenestration area
to the gross exterior wall area.
Zone: a space or group of spaces within a building with any
combination of heating, cooling, or lighting requirements sufficiently
similar so that desired conditions can be maintained throughout by a
single controlling device.