[Code of Federal Regulations]
[Title 10, Volume 3]
[Revised as of January 1, 2005]
From the U.S. Government Printing Office via GPO Access
[CITE: 10CFR434.402]

[Page 373-380]
 
                            TITLE 10--ENERGY
 
                    CHAPTER II--DEPARTMENT OF ENERGY
 
PART 434_ENERGY CODE FOR NEW FEDERAL COMMERCIAL AND MULTI-FAMILY HIGH 
RISE RESIDENTIAL BUILDINGS--Table of Contents
 
  Subpart D_Building Design Requirements_Electric Systems and Equipment
 
Sec. 434.402  Building envelope assemblies and materials.

    The building envelope and its associated assemblies and materials 
shall meet the provisions of this section.
    402.1 Calculations and Supporting Information.
    402.1.1 Material Properties. Information on thermal properties, 
building envelope system performance, and component heat transfer shall 
be obtained from RS-4. When the information is not available from RS-4, 
(incorporated by reference, see Sec. 434.701) the data shall be 
obtained from manufacturer's information or laboratory or field test 
measurements using RS-5, RS-6, RS-7, or RS-8 (incorporated by reference, 
see Sec. 434.701).
    402.1.1.1 The shading coefficient (SC) for fenestration shall be 
obtained from RS-4 (incorporated by reference, see Sec. 434.701) or 
from manufacturer's test data. The shading coefficient of the 
fenestration, including both internal and external shading devices, is 
SCX and excludes the effect of external shading projections, 
which are calculated separately. The shading coefficient used for 
louvered shade screens shall be determined using a profile angle of 30 
degrees as found in Table 41, Chapter 27 of RS-4 (incorporated by 
reference, see Sec. 434.701).
    402.1.2 Thermal Performance Calculations. The overall thermal 
transmittance of the building envelope shall be calculated in accordance 
with Equation 402.1.2:
[GRAPHIC] [TIFF OMITTED] TR06OC00.022

Where:

Uo = the area-weighted average thermal transmittance of the 
gross area of the building envelope; i.e., the exterior wall assembly 
including fenestration and doors, the roof and ceiling assembly, and the 
floor assembly, Btu/(h[middot]ft\2\[middot][deg]F)
Ao = the gross area of the building envelope, ft\2\
Ui = the thermal transmittance of each individual path of the 
building envelope, i.e., the opaque portion or the fenestration, Btu/
(h[middot]ft\2\[middot][deg]F)
Ui = 1/Ri (where Ri is the total 
resistance to heat flow of an individual path through the building 
envelope)
Ai = the area of each individual element of the building 
envelope, ft\2\

    The thermal transmittance of each component of the building envelope 
shall be determined with due consideration of all major series and 
parallel heat flow paths through the elements of the component and film 
coefficients and shall account for any compression of insulation. The 
thermal transmittance of opaque elements of assemblies

[[Page 374]]

shall be determined using a series path procedure with corrections for 
the presence of parallel paths within an element of the envelope 
assembly (such as wall cavities with parallel paths through insulation 
and studs). The thermal performance of adjacent ground in below-grade 
applications shall be excluded from all thermal calculations.
    402.1.2.1 Envelope Assemblies Containing Metal Framing. The thermal 
transmittance of the envelope assembly containing metal framing shall be 
determined from one of three methods:
    (a) Laboratory or field test measurements based on RS-5, RS-6, RS-7, 
or RS-8 (incorporated by reference, see Sec. 434.701).
    (b) The zone method described in Chapter 22 of RS-4 (incorporated by 
reference, see Sec. 434.701) and the formulas on page 22.10.
    (c) For metal roof trusses or metal studs covered by Tables 
402.1.2.1a and b, the total resistance of the series path shall be 
calculated in accordance with the following Equations:
[GRAPHIC] [TIFF OMITTED] TR06OC00.023

Where:

Rt = the total resistance of the envelope assembly
Ri = the resistance of the series elements (for i = 1 to n) 
excluding the parallel path element(s)
Re = the equivalent resistance of the element containing the 
parallel path (R-value of insulation x Fc). Values for 
Fc and equivalent resistances shall be taken from Tables 
402.1.2.1a or b.

 Table 402.1.2.1a--Parallel Path Correction Factors--Metal Roof Trusses
       Spaced 4 ft. o.c. or Greater That Penetrate the Insulation
------------------------------------------------------------------------
                                                             Equivalent
      Effective framing cavity R-values        Correction    resistance
                                                factor Fc      Re \1\
------------------------------------------------------------------------
R-0.........................................          1.00           R-0
R-5.........................................          0.96         R-4.8
R-10........................................          0.92         R-9.2
R-15........................................          0.88        R-13.2
R-20........................................          0.85        R-17.0
R-25........................................          0.81        R-20.3
R-30........................................          0.79        R-23.7
R-35........................................          0.76        R-26.6
R-40........................................          0.73        R-29.2
R-45........................................          0.71        R-32.0
R-50........................................          0.69        R-34.5
R-55........................................          0.67       R-36.0
------------------------------------------------------------------------
1 Based on 0.66-inch-diameter cross members every one foot.


       Table 402.1.2.1b--Parallel Path Correction Factors--Metal Framed Walls With Studs 16 Ga. or Lighter
----------------------------------------------------------------------------------------------------------------
                                                                                                     Equivalent
           Size of members             Spacing of  framing,    Cavity  insulation R-   Correction    resistance
                                                in.                    Value            factor Fc        Re
----------------------------------------------------------------------------------------------------------------
2 x 4...............................  16 O.C.                 R-11                            0.50         R-5.5
                                                              R-13                            0.46         R-6.0
                                                              R-15                            0.43         R-6.4
2 x 4...............................  24 O.C.                 R-11                            0.60         R-6.6
                                                              R-13                            0.55         R-7.2
                                                              R-15                            0.52         R-7.8
2 x 6...............................  16 O.C.                 R-19                            0.37         R-7.1
                                                              R-21                            0.35         R-7.4
2 x 6...............................  24 O.C.                 R-19                            0.45         R-8.6
                                                              R-21                            0.43         R-9.0
2 x 8...............................  16 O.C.                 R-25                            0.31         R-7.8
2 x 8...............................  24 O.C.                 R-25                            0.38         R-9.6
----------------------------------------------------------------------------------------------------------------

    402.1.2.2 Envelope Assemblies Containing Nonmetal Framing. The 
thermal transmittance of the envelope assembly shall be determined from 
laboratory or field test measurements based on RS-5, RS-6, RS-7, or RS-8 
(incorporated by reference, see Sec. 434.701) or from the series-
parallel (isothermal planes) method provided in page 23.2 of Chapter 23 
of RS-4 (incorporated be reference, see Sec. 434.701).
    402.1.2.3 Metal Buildings. For elements with internal metallic 
structures bonded on one or both sides to a metal skin or covering, the 
calculation

[[Page 375]]

procedure specified in RS-9 (incorporated by reference, see Sec. 
434.701) shall be used.
    402.1.2.4 Fenestration Assemblies. Determine the overall thermal 
transmittance of fenestration assemblies in accordance with RS-18 and 
RS-19 (incorporated by reference, see Sec. 434.701) or by calculation. 
Calculation of the overall thermal transmittance of fenestration 
assemblies shall consider the center-of-glass, edge-of-glass, and frame 
components.
    (a) The following equation 402.1.2.4a shall be used.
    [GRAPHIC] [TIFF OMITTED] TR06OC00.024
    
Where:

Uof = the overall thermal transmittance of the fenestration 
assemblies, including the center-of-glass, edge-of-glass, and frame 
components, Btu/(h[middot]ft2[middot][deg]F)
i = numerical subscript (1, 2, . . .n) refers to each of the various 
fenestration types present in the wall
n = the number of fenestration assemblies in the wall assembly
Ucg = the thermal transmittance of the center-of-glass area, 
Btu/(h[middot]ft2[middot][deg]F)
Acg = the center of glass area, that is the overall visible 
glass area minus the edge-of-glass area, ft2
Ueg = the thermal transmittance of the edge of the visible 
glass area including the effects of spacers in multiple glazed units, 
Btu/(h[middot]ft2[middot][deg]F)
Aeg = the edge of the visible glass area, that is the 2.5 in. 
perimeter band adjacent to the frame, ft2
Uf = the thermal transmittance of the frame area, Btu/
(h[middot]ft2[middot][deg]F)
Af = the frame area that is the overall area of the entire 
glazing product minus the center-of-glass area and minus the edge-of-
glass area, ft\2\

    (b) Values of Uof shall be based on one of the following 
methods:
    (1) Results from laboratory test of center-of-glass, edge-of-glass, 
and frame assemblies tested as a unit at winter conditions. One of the 
procedures in Section 8.3.2 of RS-1 (incorporated by reference, see 
Sec. 434.701) shall be used.
    (2) Overall generic product C (commercial) in Table 13, Chapter 27, 
of the RS-4 (incorporated by reference, see Sec. 434.701). The generic 
product C in Table 13, Chapter 27, is based on a product of 24 ft\2\. 
Larger units will produce lower U-values and thus it is recommended to 
use the calculation procedure detailed in Equation 402.1.2.4a.
    (3) Calculations based on the actual area for center-of-glass, edge-
of-glass, and frame assemblies and on the thermal transmittance of 
components derived from 402.1.2.4a, 402.1.2.4b or a combination of the 
two.
    402.1.3 Gross Areas of Envelope Components.
    402.1.3.1 Roof Assembly. The gross area of a roof assembly shall 
consist of the total surface of the roof assembly exposed to outside air 
or unconditioned spaces and is measured from the exterior faces of 
exterior walls and centerline of walls separating buildings. The roof 
assembly includes all roof or ceiling components through which heat may 
flow between indoor and outdoor environments, including skylight 
surfaces but excluding service openings. For thermal transmittance 
purposes when return air ceiling plenums are employed, the roof or 
ceiling assembly

[[Page 376]]

shall not include the resistance of the ceiling or the plenum space as 
part of the total resistance of the assembly.
    402.1.3.2 Floor Assembly. The gross area of a floor assembly over 
outside or unconditioned spaces shall consist of the total surface of 
the floor assembly exposed to outside air or unconditioned space and is 
measured from the exterior face of exterior walls and centerline of 
walls separating buildings. The floor assembly shall include all floor 
components through which heat may flow between indoor and outdoor or 
unconditioned space environments.
    402.1.3.3 Wall Assembly. The gross area of exterior walls enclosing 
a heated or cooled space is measured on the exterior and consists of the 
opaque walls, including between-floor spandrels, peripheral edges of 
flooring, window areas (including sash), and door areas but excluding 
vents, grilles, and pipes.
    402.2 Air Leakage and Moisture Mitigation. The requirements of this 
section shall apply only to those building components that separate 
interior building conditioned space from the outdoors or from 
unconditioned space or crawl spaces. Compliance with the criteria for 
air leakage through building components shall be determined by tests 
conducted in accordance with RS-10 (incorporated by reference, see Sec. 
434.701).
    402.2.1 Air Barrier System. A barrier against leakage shall be 
installed to prevent the leakage of air through the building envelope 
according to the following requirements:
    (a) The air barrier shall be continuous at all plumbing and heating 
penetrations of the building opaque wall.
    (b) The air barrier shall be sealed at all penetrations of the 
opaque building wall for electrical and telecommunications equipment.

            Table 402.2.1--Air Leakage for Fenestration and Doors Maximum Allowable Infiltration Rate
----------------------------------------------------------------------------------------------------------------
                                                                                 cfm/lin ft Sash  crack or cfm/
                Component                          Reference  standard                    ft2  of area
----------------------------------------------------------------------------------------------------------------
               Fenestration
Aluminum:
    Operable.............................  RS-11*                              0.37 cfm/lin ft.
    Jalousie.............................  RS-11*                              1.50 cfm/ft2.
    Fixed................................  RS-11*                              0.15 cfm/ft2.
Poly Vinyl Chloride (PVC):
    Prime Windows........................  RS-12*                              0.37 cfm/ft2.
Wood:
    Residential..........................  RS-13*                              0.37 cfm/ft2.
    Light Commercial.....................  RS-13*                              0.25 cfm/ft2.
    Heavy Commercial.....................  RS-13*                              0.15 cfm/ft2.
Sliding Glass Doors:
    Aluminum.............................  RS-11*                              0.37 cfm/ft2.
    PVC..................................  RS-12*                              0.37 cfm/lin ft.
Doors--Wood:
    Residential..........................  RS-14*                              0.34 cfm/ft2.
    Light Commercial.....................  RS-14*                              0.25 cfm/ft2.
    Heavy Commercial.....................  RS-14*                              0.10 cfm/ft2.
Commercial Entrance Doors................  RS-10*                              1.25 cfm/ft2.
Residential Swinging Doors...............  RS-10*                              0.50 cfm/ft2.
Wall Sections Aluminum...................  RS-10*                              0.06 cfm/ft2.
----------------------------------------------------------------------------------------------------------------
Note:
 [The ``Maximum Allowable Infiltration Rates'' are from current standards to allow the use of available
  products.]
* Incorporated by reference, see Sec. 434.701.

    402.2.2 Building Envelope. The following areas of the building 
envelope shall be sealed, caulked, gasketed, or weatherstripped to limit 
air leakage:
    (a) Intersections of the fenestration and door frames with the 
opaque wall sections.
    (b) Openings between walls and foundations, between walls and roof 
and wall panels.
    (c) Openings at penetrations of utility service through, roofs, 
walls, and floors.
    (d) Site built fenestration and doors.

[[Page 377]]

    (e) All other openings in the building envelope.
    Exceptions are as follows: Outside air intakes, exhaust outlets, 
relief outlets, stair shaft, elevator shaft smoke relief openings, and 
other similar elements shall comply with subsection 403.
    402.2.2.1 Fenestration and Doors Fenestration and doors shall meet 
the requirements of Table 402.2.1.
    402.2.2.2 Building Assemblies Used as Ducts or Plenums. Building 
assemblies used as ducts or plenums shall be sealed, caulked, and 
gasketed to limit air leakage.
    402.2.2.3 Vestibules. A door that separates conditioned space from 
the exterior shall be equipped with an enclosed vestibule with all doors 
opening into and out of the vestibule equipped with self-closing 
devices. Vestibules shall be designed so that in passing through the 
vestibule, it is not necessary for the interior and exterior doors to 
open at the same time. Exceptions are as follows: Exterior doors need 
not be protected with a vestibule where:
    (a) The door is a revolving door.
    (b) The door is used primarily to facilitate vehicular movement or 
material handling.
    (c) The door is not intended to be used as a general entrance door.
    (d) The door opens directly from a dwelling unit.
    (e) The door opens directly from a retail space less than 2,000 
ft\2\ in area, or from a space less than 1,500 ft\2\ for other uses.
    (f) In buildings less than three stories in building height in 
regions that have less than 6,300 heating degree days base 65[deg]F.
    402.2.2.4 Compliance Testing. All buildings shall be tested after 
completion using the methodology in RS-11, (incorporated by reference, 
see Sec. 434.701) or an equivalent approved method to determine the 
envelope air leakage. A standard blower door test is an acceptable 
technique to pressurize the building if the building is 5,000 ft\2\ or 
less in area. The buildings's air handling system can be used to 
pressurize the building if the building is larger than 5,000 ft\2\. The 
following test conditions shall be:
    (a) The measured envelope air leakage shall not exceed 1.57 pounds 
per square foot of wall area at a pressure difference of 0.3 inches 
water.
    (b) At the time of testing, all windows and outside doors shall be 
installed and closed, all interior doors shall be open, and all air 
handlers and dampers shall be operable. The building shall be 
unoccupied.
    (c) During the testing period, the average wind speed during the 
test shall be less than 6.6 feet per second, the average outside 
temperature greater than 59[deg]F, and the average inside-outside 
temperature difference is less than 41[deg]F.
    402.2.2.5 Moisture Migration. The building envelope shall be 
designed to limit moisture migration that leads to deterioration in 
insulation or equipment performance as determined by the following 
construction practices:
    (a) A vapor retarder shall be installed to retard, or slow down the 
rate of water vapor diffusion through the building envelope. The 
position of the vapor retarder shall be determined taking into account 
local climate and indoor humidity levels. The methodologies presented in 
Chapter 20 of RS-4 (incorporated by reference, see Sec. 434.701) shall 
be used to determine temperature and water vapor profiles through the 
envelope systems to assess the potential for condensation within the 
envelope and to determine the position of the vapor retarder within the 
envelope system.
    (b) The vapor retarder shall be installed over the entire building 
envelope.
    (c) The perm rating requirements of the vapor retarder shall be 
determined using the methodologies contained in Chapter 20 of RS-4, 
(incorporated by reference, see Sec. 434.701) and shall take into 
account local climate and indoor humidity level. The vapor retarder 
shall have a performance rating of 1 perm or less.
    402.3 Thermal Performance Criteria.
    402.3.1 Roofs; Floors and Walls Adjacent to Unconditioned Spaces. 
The area weighted average thermal transmittance of roofs and also of 
floors and walls adjacent to unconditioned spaces shall not exceed the 
criteria in Table 402.3.1a. Exceptions are as follows: Skylights for 
which daylight credit is

[[Page 378]]

taken may be excluded from the calculations of the roof assembly 
Uor if all of the following conditions are met:
    (a) The opaque roof thermal transmittance is less than the criteria 
in Table 402.3.1b.
    (b) Skylight areas, including framing, as a percentage of the roof 
area do not exceed the values specified in Table 402.3.1b. The maximum 
skylight area from Table 402.3.1b may be increased by 50% if a shading 
device is used that blocks over 50% of the solar gain during the peak 
cooling design condition. For shell buildings, the permitted skylight 
area shall be based on a light level of 30 foot candles and a lighting 
power density (LPD) of less than 1.0 w/ft \2\. For speculative 
buildings, the permitted skylight area shall be based on the unit 
lighting power allowance from Table 401.3.2a and an illuminance level as 
follows: for LPD < 1.0, use 30 footcandles; for 1.0 < LPD < 2.5, use 50 
footcandles; and for LPD = 2.5, use 70 footcandles.
    (c) All electric lighting fixtures within daylighted zones under 
skylights are controlled by automatic daylighting controls.
    (d) The Uo of the skylight assembly including framing 
does not exceed------------Btu/(h[middot]ft \2\[middot][deg]F) [Use 0.70 
for <= 8000 HDD65 and 0.45 for 8000 HDD65 or both if the 
jurisdiction includes cities that are both below and above 8000 HDD65.]
    (e) Skylight curb U-value does not exceed 0.21 Btu/(h[middot]ft 
\2\[middot][deg]F).
    (f) The infiltration coefficient of the skylights does not exceed 
0.05 cfm/ft \2\.
    402.3.2 Below-Grade Walls and Slabs-on-Grade. The thermal resistance 
(R-value) of insulation for slabs-on-grade, or the overall thermal 
resistance of walls in contact with the earth, shall be equal to or 
greater than the values in Table 402.3.2.
    402.4 Exterior Walls. Exterior walls shall comply with either 
402.4.1 or 402.4.2.
    402.4.1 Prescriptive Criteria. (a) The exterior wall shall be 
designed in accordance with subsections 402.4.1.1 and 402.4.1.2. When 
the internal load density range is not known, the 0-1.50 W/ft \2\ range 
shall be used for residential, hotel/motel guest rooms, or warehouse 
occupancies; the 3.01-3.50 w/ft \2\ range shall be used for retail 
stores smaller than 2,000 ft \2\ and technical and vocational schools 
smaller than 10,000 ft \2\; and the 1.51-3.00 W/ft \2\ range shall be 
used for all other occupancies and building sizes. When the building 
envelope is designed or constructed prior to knowing the building 
occupancy type, an internal load density of ------ W/ft \2\ shall be 
used. [Use 3.0 W/ft \2\ for HDD65 <3000, 2.25 W/ft \2\ for 3000 < HDD65 
< 6000, and 1.5 W/ft \2\ for HDD65  6000.]
    (b) When more than one condition exists, area weighted averages 
shall be used. This requirement shall apply to all thermal 
transmittances, shading coefficients, projection factors, and internal 
load densities rounded to the same number of decimal places as shown in 
the respective table.
    402.4.1.1 Opaque Walls. The weighted average thermal transmittance 
(U-value) of opaque wall elements shall be less than the values in Table 
402.4.1.1. For mass walls (HC = 5), criteria are presented 
for low and high window/wall ratios and the criteria shall be determined 
by interpolating between these values for the window/wall ratio of the 
building.
    402.4.1.2 Fenestration. The design of the fenestration shall meet 
the criteria of Table 402.4.1.2. When the fenestration columns labeled 
``Perimeter Daylighting'' are used, automatic daylighting controls shall 
be installed in the perimeter daylighted zones of the building. These 
daylighting controls shall be capable of reducing electric lighting 
power to at least 50% of full power. Only those shading or lighting 
controls for perimeter daylighting that are shown on the plans shall be 
considered. The column labeled ``VLT  = SC'' shall be used 
only when the shading coefficient of the glass is less than its visible 
light transmittance.

                               Appendix A

    The example Alternate Component Package tables illustrate the 
requirements of subsections 434.301.1, 434.402.3.1, 434.402.3.2, 
434.402.4.1.1 and 434.402.4.1.2. Copies of specific tables contained in 
this Appendix A can be obtained from the Energy Code for Federal 
Commercial Buildings, Docket No. EE-RM-79-112-C, EE-43, Office of 
Building Research and Standards, U.S. Department of Energy, Room 1J-018, 
1000 Independence Avenue, SW., Washington, DC 20585, (202) 586-9127.

[[Page 379]]

[GRAPHIC] [TIFF OMITTED] TR06OC00.011

    402.4.2 System Performance Criteria. The cumulative annual energy 
flux attributable to thermal transmittance and solar gains shall be less 
than the criteria determined using the ENVSTD24 computer program in 
Standard 90.1-1989, or the equations in RS-1, (incorporated by 
reference, see Sec. 434.701) Attachment 8-B. The cumulative annual 
energy flux shall be calculated using the ENVSTD24 computer program or 
the equations in RS-1, (incorporated by reference, see Sec. 434.701) 
Attachment 8-B.

[[Page 380]]



                                Table 402.4.2--EQUIP Default Values for ENVSTD24
----------------------------------------------------------------------------------------------------------------
                                                                      Default                         Default
                                                                     equipment        Default        adjusted
                            Occupancy                              power density   occupant load     equipment
                                                                         1         adjustment 1    power density
----------------------------------------------------------------------------------------------------------------
Assembly........................................................            0.25            0.75            1.00
Health/Institutional............................................            1.00           -0.26            0.74
Hotel/Motel.....................................................            0.25           -0.33            0.00
Warehouse/Storage...............................................            0.10           -0.60            0.00
Multi-Family High Rise..........................................            0.75             N/A            0.00
Office..........................................................            0.75           -0.35            0.40
Restaurant......................................................            0.10            0.07            0.17
Retail..........................................................            0.25           -0.38            0.00
School..........................................................            0.50            0.30           0.80
----------------------------------------------------------------------------------------------------------------
1 Defaults as defined in Section 8.6.10.5, Table 8-4, and Sections 8.6.10.6 and 13.7.2.1, Table 13-2 from RS-1
  (incorporated by reference, see Sec. 434.701).

    402.4.2.1 Equipment Power Density (EQUIP). The equipment power 
density used in the ENVSTD24 computer program shall use the actual 
equipment power density from the building plans and specifications or be 
taken from Table 402.4.2 using the column titled ``Default Adjusted 
Equipment Power Density'' or calculated for the building using the 
procedures of RS-1. (incorporated by reference, see Sec. 434.701). The 
program limits consideration of the equipment power density to a maximum 
of 1 W/ft 2.
    402.4.2.2 Lighting Power Density (LIGHTS). The lighting power 
density used in the ENVSTD24 computer program shall use the actual 
lighting power density from the building plans and specifications or the 
appropriate value from Tables 401.3.2a, b, c, or d.
    402.4.2.3 Daylighting Control Credit Fraction (DLCF). When the 
daylighting control credit fraction is other than zero, automatic 
daylighting controls shall be installed in the appropriate perimeter 
zones(s) of the building to justify the credit.