[Code of Federal Regulations]
[Title 10, Volume 3]
[Revised as of January 1, 2005]
From the U.S. Government Printing Office via GPO Access
[CITE: 10CFR434.513]

[Page 396-402]
 
                            TITLE 10--ENERGY
 
                    CHAPTER II--DEPARTMENT OF ENERGY
 
PART 434_ENERGY CODE FOR NEW FEDERAL COMMERCIAL AND MULTI-FAMILY HIGH 
RISE RESIDENTIAL BUILDINGS--Table of Contents
 
          Subpart E_Building Energy Cost Compliance Alternative
 
Sec. 434.513  Occupancy.

    5131 Occupancy schedules are default assumptions. The same 
assumptions shall be made in computing Design Energy Consumption as were 
used in calculating the Energy Cost Budget.
    513.2 Table 513.2.a, Occupancy Density, establishes the density, in 
ft2 person of conditioned floor area, to be

[[Page 397]]

used for each building type. Table 513.2.b, Building Schedule Percentage 
Multipliers, establishes the percentage of total occupants in the 
building by hour of the day for each building type.

                    Table 513.2.a--Occupancy Density
------------------------------------------------------------------------
                                                             Conditioned
                                                              floor area
                       Building type                            Ft \2\
                                                                person
------------------------------------------------------------------------
Assembly...................................................           50
Office.....................................................          275
Retail.....................................................          300
Warehouse..................................................        15000
School.....................................................           75
Hotel/Motel................................................          250
Restaurant.................................................          100
Health/Institutional.......................................          200
Multi-family High-rise Residential.........................   2 per unit
                                                                   .\1\
------------------------------------------------------------------------
\1\ Heat generation: Btu/h per person: 230 Btu/h per person sensible,
  and 190 Btu/h per person latent. See Tables 512.2 a and b.


[[Page 398]]

[GRAPHIC] [TIFF OMITTED] TR06OC00.012


[[Page 399]]

[GRAPHIC] [TIFF OMITTED] TR06OC00.013


[[Page 400]]

[GRAPHIC] [TIFF OMITTED] TR06OC00.014


[[Page 401]]

[GRAPHIC] [TIFF OMITTED] TR06OC00.015


[[Page 402]]

[GRAPHIC] [TIFF OMITTED] TR06OC00.016