[Code of Federal Regulations]
[Title 10, Volume 3]
[Revised as of January 1, 2005]
From the U.S. Government Printing Office via GPO Access
[CITE: 10CFR434.515]

[Page 403]
 
                            TITLE 10--ENERGY
 
                    CHAPTER II--DEPARTMENT OF ENERGY
 
PART 434_ENERGY CODE FOR NEW FEDERAL COMMERCIAL AND MULTI-FAMILY HIGH 
RISE RESIDENTIAL BUILDINGS--Table of Contents
 
          Subpart E_Building Energy Cost Compliance Alternative
 
Sec. 434.515  Receptacles.

    515.1 Receptacle loads and profiles are default assumptions. The 
same assumptions shall be made in calculating Design Energy Consumption 
as were used in calculating the Energy Cost Budget.
    515.2 Receptacle loads include all general service loads that are 
typical in a building. These loads exclude any process electrical usage 
and HVAC primary or auxiliary electrical usage. Table 515.2, Receptacle 
Power Densities, establishes the density, in W/ft\2\, to be used for 
each building type. The receptacle energy profiles shall be the same as 
the lighting energy profiles in Table 513.2.b. This profile establishes 
the percentage of the receptacle load that is switched on by hour of the 
day and by building type.

                 Table 515.2--Receptacle Power Densities
------------------------------------------------------------------------
                                                            W/ft\2\ of
                      Building type                         conditioned
                                                            floor  area
------------------------------------------------------------------------
Assembly................................................            0.25
Office..................................................            0.75
Retail..................................................            0.25
Warehouse...............................................             0.1
School..................................................             0.5
Hotel/Motel.............................................            0.25
Restaurant..............................................             0.1
Health..................................................             1.0
Multi-family High Rise Residential......................  ..............
------------------------------------------------------------------------
Included in Lights and Equipment portions of Tables 512.2 a and b.