                            TITLE 10--ENERGY
 
                    CHAPTER II--DEPARTMENT OF ENERGY
 
PART 434_ENERGY CODE FOR NEW FEDERAL COMMERCIAL AND MULTI-FAMILY HIGH 
RISE RESIDENTIAL BUILDINGS--Table of Contents
 
          Subpart E_Building Energy Cost Compliance Alternative
 
Sec. 434.517  HVAC systems and equipment.

    517.1 The specifications and requirements for the HVAC systems of 
the Prototype and Reference Buildings shall be those in Table 517.1.1, 
HVAC Systems for Prototype and Reference Buildings. For the calculation 
of the Design Energy Consumption, the HVAC systems and equipment of the 
Proposed Design shall be used.
    517.2 The systems and types of energy presented in Table 517.1.1 are 
assumptions for calculating the Energy Cost Budget. They are not 
requirements for either systems or the type of energy to be used in the 
Proposed Building or for the calculation of the Design Energy Cost.

  Table 517.1.1--HVAC Systems of Prototype and Reference Buildings 1,2
------------------------------------------------------------------------
                               System No.  (Table     Remarks  (Table
   Building/space occupancy         517.4.1)              517.4.1)
------------------------------------------------------------------------
Assembly:
    a. Churches (any size)...                  1
    b. <=50,000 ft \2\ or <=3             1 or 3   Note 1.
     floors.
    c. 50,000 ft                    3
     \2\ or 3
     floors.
Office:
    a. <=20,000 ft \2\.......                  1
    b. <=50,000 ft \2\ and                     4
     either <=3 floors or
     <=75,000 ft \2\.
    c. <75,000 ft \2\ or 3 floors.
Retail:
    a. <=50,000 ft \2\.......             1 or 3   Note 1.
    b. 50,000 ft               4 or 5   Note 1.
     \2\.
Warehouse....................                  1   Note 1.
School:
    a. <=75,000 ft \2\ or <=3                  1
     floors.
    b. 75,000 ft                    3
     \2\ or 3
     floors.
Hotel/Motel:
    a. <=3 stories...........             2 or 7   Note 5, 7.
    b. 3 stories..                  6   Note 6.
Restaurant...................             1 or 3   Note 1.
Health:
    a. Nursing Home (any                  2 or 7   Note 7.
     size).
    b. <=15,000 ft \2\.......                  1
    c. <15,000 ft \2\ or                       4   Note 2.
     <=50,000 ft \2\.
    d. 50,000 ft                    5   Note 2, 3.
     \2\.
Multi-family High Rise                        7
 Residential 3
 stories.
------------------------------------------------------------------------
\1\ Space and Service Water Heating budget calculations shall be made
  using both electricity and natural gas. The Energy Cost Budget shall
  be the lower of these two calculations. If natural gas is not
  available at the rate, electricity and 2 fuel oil shall be
  used for the budget calculations.
\2\ The system and energy types presented in this Table are not intended
  as requirements or recommendations for the proposed design. Floor
  areas below are the total conditioned floor areas for the listed
  occupancy type in the building. The number of floors indicated below
  is the total number of occupied floors for the listed occupancy type.

    517.3 HVAC Zones. HVAC zones for calculating the Energy Cost Budget 
of the Prototype or Reference Building shall consist of at least four 
perimeter and one interior zones per floor. Prototype Buildings shall 
have one perimeter zone facing each cardinal direction. The perimeter 
zones of Prototype and Reference Buildings shall be 15 ft in width, or 
one-third the narrow dimension of the building, when this dimension is 
between 30 ft and 45 ft inclusive, or one-half the narrow dimension of 
the building when this dimension is less than 30 ft. Zoning requirements 
shall be a default assumption for calculating the Energy Cost Budget. 
For multi-family high-rise residential

[[Page 405]]

buildings, the prototype building shall have one zone per dwelling unit. 
The proposed design shall have one zone per unit unless zonal 
thermostatic controls are provided within units; in this case, two zones 
per unit shall be modeled. Building types such as assembly or warehouse 
may be modeled as a single zone if there is only one space.
    517.4 For calculating the Design Energy Consumption, no fewer zones 
shall be used than were in the Prototype and Reference Buildings. The 
zones in the simulation shall correspond to the zones provided by the 
controls in the Proposed Design. Thermally similar zones, such as those 
facing one orientation on different floors, may be grouped together for 
the purposes of either the Design Energy Consumption or Energy Cost 
Budget simulation.

                Table 517.4.1--HVAC System Description for Prototype and Reference Buildings 1, 2
----------------------------------------------------------------------------------------------------------------
         HVAC component            System 1   System 2   System 3   System 4
----------------------------------------------------------------------------------------------------------------
System Description..............  Packaged rooftop    Packaged terminal   Air handler per     Packaged rooftop
                                   single room, one    air conditioner     zone with central   VAV w/perimeter
                                   unit per zone.      with space heater   plant.              reheat.
                                                       or heat pump, one
                                                       heating/cooling
                                                       unit per zone.
Fan system--Design supply         Note 9............  Note 10...........  Note 9............  Note 9.
 circulation rate.
Supply fan total static pressure  1.3 in. W.C.......  N/A...............  2.0 in. W.C.......  3.0 in. W.C.
Combined supply fan, motor, and   40%...............  N/A...............  50%...............  45%.
 drive efficiency.
Supply fan control..............  Constant volume...  Fan Cycles with     Constant volume...  VAV w/forward
                                                       call for heating                        curved
                                                       or cooling.                             contrifugal fan
                                                                                               and variable
                                                                                               inlet vanes.
Return fan total static pressure  N/A...............  N/A...............  0.6 in. W.C.......  0.6 in. W.C.
Combined return fan, motor, and   N/A...............  N/A...............  25%...............  25%.
 drive efficiency.
Return fan control..............  N/A...............  N/A...............  Constant volume...  VAV w/forward
                                                                                               curved
                                                                                               centrifugal fan
                                                                                               and discharge
                                                                                               dampers.
Cooling System..................  Direct expansion    Direct expansion    Chilled water       Direct expansion
                                   air cooled.         air cooled.         (Note 1).           air cooled.
Heating System..................  Furnace, heat       Heat pump w/        Hot water (Note 8,  Hot water (Note
                                   pump, or electric   electric            12).                12) or electric
                                   resistance (Note    resistance                              resistance (Note
                                   8).                 auxiliary or air                        B).
                                                       conditioner w/
                                                       space heater
                                                       (Note 8).
Remarks.........................  Dry bulb            No economizer.....  Dry bulb            Dry bulb
                                   economizer per                          economizer per      economizer per
                                   Section 7.4.3                           Section 434.514.    Section 434.514.
                                   (barometric                                                 Minimum VAV
                                   relief).                                                    setting per
                                                                                               434.514 exception
                                                                                               1. Supply air
                                                                                               reset by zone of
                                                                                               greatest cooling
                                                                                               demand.
----------------------------------------------------------------------------------------------------------------
\1\ The systems and energy types presented in this Table are not intended as requirements or recommendations for
  the proposed design.
\2\ For numbered notes see end of Table 517.4.1.


                Table 517.4.1--HVAC System Description for Prototype and Reference Buildings \1\
----------------------------------------------------------------------------------------------------------------
            HVAC component                Systems 5       System 6        System 7
----------------------------------------------------------------------------------------------------------------
System Description...................  Built-up central VAV     Fourpipe fan coil per    Water source heat pump
                                        with perimeter reheat.   zone with central
                                                                 plant.
Fan system--Design supply circulation  Note 9.................  Note 9.................  Note 10.
 rate.
Supply fan total static pressure.....  4.0 in W.C.............  0.5 in W.C.............  0.5 in. W.C.
Combined supply fan, motor, and drive  55%....................  25A....................  25%.
 efficiency.

[[Page 406]]


Supply fan control...................  VAV w/air-foil           Fan Cycles with call     Fan cycles w/call for
                                        centrifugal fan and AC   for heating or cooling.  heating or cooling.
                                        frequency variable
                                        speed drive.
Return fan total static pressure.....  1.0 in W.C.............  N/A....................  N/A.
Combined return fan, motor, and drive  30%....................  N/A....................  N/A.
 efficiency.
Return fan control...................  VAV with air-foil        N/A....................  N/A.
                                        centrifugal fan and AC
                                        frequency variable
                                        speed drive.
Cooling System.......................  Chilled water (Note 11)  Chilled water (Note 11)  Closed circuit,
                                                                                          centrifugal blower
                                                                                          type cooling tower
                                                                                          sized per Note 11.
                                                                                          Circulating pump sized
                                                                                          for 2.7 GPM per ton.
Heating System.......................  Hot water (Note 12) or   Hot water (Note 12) or   Electric or natural
                                        electric resistance      electric resistance      draft fossil fuel
                                        (Note 8).                (Note 8).                boiler (Note 8).
Remarks..............................  Dry bulb economizer per  No economizer..........  Tower fans and boiler
                                        Section 7.4.3. Minimum                            cycled to maintain
                                        VAV setting per                                   circulating water
                                        Section 7.4.4.3.                                  temperature between 60
                                        Supply air reset by                               and design tower
                                        zone of greatest                                  leaving water
                                        cooling demand.                                   temperature.
----------------------------------------------------------------------------------------------------------------

                    Numbered Notes for Table 517.4.1

     HVAC System Descriptions for Prototype and Reference Buildings

    Notes:
    1. For occupancies such as restaurants, assembly and retail which 
are part of a mixed use building which, according to Table 517.4.1, 
includes a central chilled water plant (systems 3, 5, or 6), chilled 
water system type 3 or 5, as indicated in the Table, shall be used.
    2. Constant volume may be used in zones where pressurization 
relationships must be maintained by code. VAV shall be used in all other 
areas, in accordance with Sec. 517.4
    3. Provide run-around heat recovery systems for all fan systems with 
minimum outside air intake greater than 75%. Recovery effectiveness 
shall be 0.60.
    4. If a warehouse is not intended to be mechanically cooled, both 
the Energy Cost Budgets and Design Energy Costs, may be calculated 
assuming no mechanical cooling.
    5. The system listed is for guest rooms only. Areas such as public 
areas and back-of-house areas shall be served by system 4. Other areas 
such as offices and retail shall be served by the systems listed in 
Table 517.4.1 for those occupancy types.
    6. The system listed is for guest rooms only. Areas such as public 
areas and back-of-house areas shall be served by System 5. Other areas 
such as offices and retail shall be served by the systems listed in 
Table 517.4.1.1 for those occupancy types.
    7. System 2 shall be used for Energy Cost Budget calculation except 
in areas with design heating outside air temperatures less than 
10[deg]F.
    8. Prototype energy budget cost calculations shall be made using 
both electricity and natural gas. If natural gas is not available at the 
site, electricity and 2 fuel oil shall be used. The Energy Cost 
Budget shall be the lower of these results. Alternatively, the Energy 
Cost Budget may be based on the fuel source that minimizes total 
operating, maintenance, equipment, and installation costs for the 
prototype over the building lifetime. Equipment and installation cost 
estimates shall be prepared using professionally recognized cost 
estimating tools, guides, and techniques. The methods of analysis shall 
conform to those of Subpart A of 10 CFR part 436. Energy costs shall be 
based on actual costs to the building as defined in this Section.
    9. Design supply air circulation rate shall be based on a supply air 
to room air temperature differences of 20[deg]F. A higher supply air 
temperature may be used if required to maintain a minimum circulation 
rate of 4.5 air changes per hour or 15 cfm per person at design 
conditions to each zone served by the system. If return fans are 
specified, they shall be sized from the supply fan capacity less the 
required minimum ventilation with outside air, or 75% or the supply air 
capacity, whichever is larger. Except where noted, supply and return 
fans shall be operated continually during occupied hours.
    10. Fan System Energy when included in the efficiency rating of the 
unit as defined in Sec. 403.2.4.3 need not be modeled explicitly for 
this system. The fan shall cycle with calls for heating or cooling.
    11. Chilled water systems shall be modeled using a reciprocating 
chiller for systems with total cooling capacities less than 175 tons, 
and centrifugal chillers for systems

[[Page 407]]

with cooling capacities of 175 tons or greater. For systems with cooling 
or 600 ton or more, the Energy Cost Budget shall be calculated using two 
centrifugal chillers lead/lag controlled. Chilled water pumps shall be 
sized using a 12[deg]F temperature rise, from 44[deg]F to 56[deg]F 
operating at 65 feed of head and 65% combined impeller and motor 
efficiency. Condenser water pumps shall be sized using a 10[deg]F 
temperature rise, operating at 60 feet of head and 60% combined impeller 
and motor efficiency. The cooling tower shall be an open circuit, 
centrifugal blower type sized for the larger of 85[deg]F leaving water 
temperature or 10[deg]F approach to design wet bulb temperature. The 
tower shall be controlled to provide a 65[deg]F leaving water 
temperature whenever weather conditions permit, floating up to design 
leaving water temperature at design conditions. Chilled water supply 
temperature shall be reset in accordance with Sec. 434.518.
    12. Hot water system shall include a natural draft fossil fuel or 
electric boiler per Note 8. The hot water pump shall be sized based on a 
30[deg]F temperature drop, for 18[deg]F to 150[deg]F, operating at 60 
feet of head and a combined impeller and motor efficiency of 60%. Hot 
water supply temperature shall be reset in accordance with Sec. 
434.518.

    517.5 Equipment Sizing and Redundant Equipment. For calculating the 
Energy Cost Budget of Prototype or Reference Buildings, HVAC equipment 
shall be sized to meet the requirements of subsection 403.2.2, without 
using any of the exceptions. The size of equipment shall be that 
required for the building without process loads considered. Redundant or 
emergency equipment need not be simulated if it is controlled so that it 
will not be operated during normal operations of the building. The 
designer shall document the installation of process equipment and the 
size of process loads.
    517.6 For calculating the Design Energy Consumption, actual air flow 
rates and installed equipment size shall be used in the simulation, 
except that excess capacity provided to meet process loads need not be 
modeled unless the process load was not modeled in setting Energy Cost 
Budget. Equipment sizing in the simulation of the Proposed Design shall 
correspond to the equipment actually selected for the design and the 
designer shall not use equipment sized automatically by the simulation 
tool.
    517.6.1 Redundant or emergency equipment need not be simulated if it 
is controlled to not be operated during normal operations of the 
building.