    519.1 All occupied conditioned spaces in the Prototype, Reference 
and

[[Page 408]]

Proposed Design Buildings in all climates shall be simulated as being 
both heated and cooled. The assumptions in this subsection are 
prescribed assumptions. If the Proposed Design does not include 
equipment for cooling or heating, the Design Energy Consumption shall be 
determined by the specifications for calculating the Energy Cost Budget 
as described in Table 517.4.1 HVAC System Description for Prototype and 
Reference Buildings. Exceptions to 519.1 are as follows:
    519.1.1 If a building is to be provided with only heating or 
cooling, both the Prototype or Reference Building and the Proposed 
Design shall be simulated, using the same assumptions. Such an 
assumption cannot be made unless the building interior temperature meets 
the comfort criteria of RS-2 (incorporated by reference, see Sec. 
434.701) at least 98% of the occupied hours during the year.
    519.1.2 If warehouses are not intended to be mechanically cooled, 
both the Energy Cost Budget and Design Energy Consumption shall be 
modeled assuming no mechanical cooling; and
    519.1.3 In climates where winter design temperature (97.5% 
occurrence) is greater than 59[deg]F, space heating need not be modeled.
    519.2 Space temperature controls for the Prototype or Reference 
Building, except multi-family high-rise residential buildings, shall be 
set at 70[deg]F for space heating and 75[deg]F for space cooling with a 
deadband per subsection 403.2.6.3. The system shut off during off-hours 
shall be according to the schedule in Table 515.2, except that the 
heating system shall cycle on if any space should drop below the night 
setback setting of 55[deg]F. There shall be no similar setpoint during 
the cooling season. Lesser deadband ranges may be used in calculating 
the Design Energy Consumption. Exceptions to 519.2 are as follows:
    (a) Setback shall not be modeled in determining either the Energy 
Cost Budget or Design Energy Cost if setback is not realistic for the 
Proposed Design, such as 24-hour/day operations. Health facilities need 
not have night setback during the heating season; and
    (b) Hotel/motels and multi-family high-rise residential buildings 
shall have a night setback temperature of 60 [deg]F from 11:00 p.m. to 
6:00 a.m. during the heating season; and
    (c) If deadband controls are not to be installed, the Design Energy 
Cost shall be calculated with both heating and cooling thermostat 
setpoints set to the same value between 70 [deg]F and 75 [deg]F 
inclusive, assumed to be constant for the year.
    519.2.1 For multi-family buildings, the thermostat schedule for the 
dwelling units shall be as in Table 519.1.2, Thermostat Settings for 
Multi-Family High-rise Buildings. The Prototype Building shall use the 
single zone schedule. The Proposed Design shall use the two-zone 
schedule only if zonal thermostatic controls are provided. For Proposed 
Designs that use heat pumps employing supplementary heat, the controls 
used to switch on the auxiliary heat source during morning warm-up 
periods shall be simulated accurately. The thermostat assumptions for 
multi-family high-rise buildings are prescribed assumptions.
    519.3 When providing for outdoor air ventilation in calculating the 
Energy Cost Budget, controls shall be assumed to close the outside air 
intake to reduce the flow of outside air to 0 cfm during setback and 
unoccupied periods. Ventilation using inside air may still be required 
to maintain scheduled setback temperature. Outside air ventilation, 
during occupied periods, shall be as required by RS-41, (incorporated by 
reference, see Sec. 434.701) or the Proposed Design, whichever is 
greater.
    519.4 If humidification is to be used in the Proposed Design, the 
same level of humidification and system type shall be used in the 
Prototype or Reference Building. If dehumidification requires subcooling 
of supply air, then reheat for the Prototype or Reference Building shall 
be from recovered waste heat such as condenser waste heat.

[[Page 409]]



                                   Table 519.1.2--Thermostat Settings for Multi-Family High-Rise Residential Buildings
--------------------------------------------------------------------------------------------------------------------------------------------------------
                                                             Single zone dwelling unit                        Two zone dwelling unit
                                                         -----------------------------------------------------------------------------------------------
                       Time of day                                                              Bedrooms/bathrooms                  Other rooms
                                                               Heat            Cool      ---------------------------------------------------------------
                                                                                               Heat            Cool            Heat            Cool
--------------------------------------------------------------------------------------------------------------------------------------------------------
Midnight-6 a.m..........................................              60              78              60              78              60              85
6 a.m.-9 a.m............................................              70              78              70              78              70              78
9 a.m.-5 p.m............................................              70              78              60              85              70              78
5 p.m.-11 p.m...........................................              70              78              70              78              70              78
11 p.m.-Midnight........................................              60              78              60              78              60              78
--------------------------------------------------------------------------------------------------------------------------------------------------------