Subpart F_Building Energy Compliance Alternative
Sec. 434.602 Determination of the annual energy budget.
602.1 The Energy Use Budget shall be calculated for the appropriate
Prototype or Reference Building in accordance with the procedures
prescribed in subsection 502 with the following exceptions: The Energy
Use Budget shall be stated in units of Btu/ft2/yr and the
simulation tool shall segregate the calculated energy consumption by
fuel type producing an Energy Use Budget for each fuel (the fuel
selections having been made by a life cycle cost analysis in determining
the proposed design).
602.2 The Energy Use Budget is calculated similarly for the
Reference or Prototype Building using equation 602.2.
[GRAPHIC] [TIFF OMITTED] TR06OC00.029
Where EUB1, EUB2, EUBi are the
calculated annual energy targets for each fuel used in the Reference or
Prototype building and f1, f2, . . . fi
are the energy conversion factors given in Table 602.2, Fuel Conversion
Factors for Computing Design Annual Energy Uses. In lieu of case by case
calculation of the Energy Use Budget, the designer may construct Energy
Use Budget tables for the combinations of energy source(s) that may be
considered in a set of project designs, such as electric heating,
electric service water, and gas cooling or oil heating, gas service
water and electric cooling. The values in such optional Energy Use
Budget tables shall be equal to or less than the corresponding Energy
Use Budgets calculated on a case by case basis according to this
section. Energy Use Budget tables shall be constructed to correspond to
the climatic regions and building types in accordance with provisions
for Prototype or Reference Building models in subpart E of this part.
Table 602.2--Fuel Conversion Factors, for Computing Design Annual Energy
Uses
------------------------------------------------------------------------
Fuels Conversion factor
------------------------------------------------------------------------
Electricity............................ 3412 Btu/kilowatt hour.
Fuel Oil............................... 138,700 Btu/gallon.
Natural Gas............................ 1,031,000 Btu/1000 ft\2\.
Liquified Petroleum (including Propane 95,5000 Btu/gallon.
and Butane).
Anthracite Coal........................ 28,300,000 Btu/short ton.
Bituminous Coal........................ 24,580,000 Btu/short ton.
Purchase Steam and Steam from Central 1,000 Btu/Pound.
Plants.
High Temperature or Medium Temperature Use the heat value based on the
Water from Central Plants. water actually delivered at
the building five foot line.
------------------------------------------------------------------------
Note: At specific locations where the energy source Btu content varies
significantly from the value presented above then the local fuel value
may be used provided there is supporting documentation from the fuel
source supplier stating this actual energy value and varifying that
this value will remain consistent for the foreseeable future. The fuel
content for fuels not given this table shall be determined from the
best available source.