[Code of Federal Regulations]

[Title 40, Volume 22]

[Revised as of July 1, 2005]

From the U.S. Government Printing Office via GPO Access

[CITE: 40CFR141.21]



[Page 354-361]

 

                   TITLE 40--PROTECTION OF ENVIRONMENT

 

         CHAPTER I--ENVIRONMENTAL PROTECTION AGENCY (CONTINUED)

 

PART 141_NATIONAL PRIMARY DRINKING WATER REGULATIONS--Table of Contents

 

            Subpart C_Monitoring and Analytical Requirements

 

Sec. 141.21  Coliform sampling.





    (a) Routine monitoring. (1) Public water systems must collect total 

coliform samples at sites which are representative of water throughout 

the distribution system according to a written sample siting plan. These 

plans are subject to State review and revision.

    (2) The monitoring frequency for total coliforms for community water 

systems is based on the population served by the system, as follows:



     Total Coliform Monitoring Frequency for Community Water Systems

------------------------------------------------------------------------

                                                                Minimum

                                                               number of

                      Population served                         samples

                                                               per month

------------------------------------------------------------------------

25 to 1,000 \1\..............................................          1

1,001 to 2,500...............................................          2

2,501 to 3,300...............................................          3

3,301 to 4,100...............................................          4

4,101 to 4,900...............................................          5

4,901 to 5,800...............................................          6

5,801 to 6,700...............................................          7

6,701 to 7,600...............................................          8

7,601 to 8,500...............................................          9

8,501 to 12,900..............................................         10

12,901 to 17,200.............................................         15

17,201 to 21,500.............................................         20

21,501 to 25,000.............................................         25

25,001 to 33,000.............................................         30

33,001 to 41,000.............................................         40

41,001 to 50,000.............................................         50

50,001 to 59,000.............................................         60

59,001 to 70,000.............................................         70

70,001 to 83,000.............................................         80

83,001 to 96,000.............................................         90

96,001 to 130,000............................................        100

130,001 to 220,000...........................................        120

220,001 to 320,000...........................................        150

320,001 to 450,000...........................................        180

450,001 to 600,000...........................................        210

600,001 to 780,000...........................................        240

780,001 to 970,000...........................................        270

970,001 to 1,230,000.........................................        300

1,230,001 to 1,520,000.......................................        330

1,520,001 to 1,850,000.......................................        360

1,850,001 to 2,270,000.......................................        390

2,270,001 to 3,020,000.......................................        420

3,020,001 to 3,960,000.......................................        450

3,960,001 or more............................................        480

------------------------------------------------------------------------

\1\ Includes public water systems which have at least 15 service

  connections, but serve fewer than 25 persons.





If a community water system serving 25 to 1,000 persons has no history 

of total coliform contamination in its current configuration and a 

sanitary survey conducted in the past five years shows that the system 

is supplied solely by a protected groundwater source and is free of 

sanitary defects, the State may reduce the monitoring frequency 

specified above, except that in no case may the State reduce the 

monitoring frequency to less than one sample per quarter. The State must 

approve the reduced monitoring frequency in writing.

    (3) The monitoring frequency for total coliforms for non-community 

water systems is as follows:

    (i) A non-community water system using only ground water (except 

ground water under the direct influence of surface water, as defined in 

Sec. 141.2) and serving 1,000 persons or fewer must monitor each 

calendar



[[Page 355]]



quarter that the system provides water to the public, except that the 

State may reduce this monitoring frequency, in writing, if a sanitary 

survey shows that the system is free of sanitary defects. Beginning June 

29, 1994, the State cannot reduce the monitoring frequency for a non-

community water system using only ground water (except ground water 

under the direct influence of surface water, as defined in Sec. 141.2) 

and serving 1,000 persons or fewer to less than once/year.

    (ii) A non-community water system using only ground water (except 

ground water under the direct influence of surface water, as defined in 

Sec. 141.2) and serving more than 1,000 persons during any month must 

monitor at the same frequency as a like-sized community water system, as 

specified in paragraph (a)(2) of this section, except the State may 

reduce this monitoring frequency, in writing, for any month the system 

serves 1,000 persons or fewer. The State cannot reduce the monitoring 

frequency to less than once/year. For systems using ground water under 

the direct influence of surface water, paragraph (a)(3)(iv) of this 

section applies.

    (iii) A non-community water system using surface water, in total or 

in part, must monitor at the same frequency as a like-sized community 

water system, as specified in paragraph (a)(2) of this section, 

regardless of the number of persons it serves.

    (iv) A non-community water system using ground water under the 

direct influence of surface water, as defined in Sec. 141.2, must 

monitor at the same frequency as a like-sized community water system, as 

specified in paragraph (a)(2) of this section. The system must begin 

monitoring at this frequency beginning six months after the State 

determines that the ground water is under the direct influence of 

surface water.

    (4) The public water system must collect samples at regular time 

intervals throughout the month, except that a system which uses only 

ground water (except ground water under the direct influence of surface 

water, as defined in Sec. 141.2), and serves 4,900 persons or fewer, 

may collect all required samples on a single day if they are taken from 

different sites.

    (5) A public water system that uses surface water or ground water 

under the direct influence of surface water, as defined in Sec. 141.2, 

and does not practice filtration in compliance with Subpart H must 

collect at least one sample near the first service connection each day 

the turbidity level of the source water, measured as specified in Sec. 

141.74(b)(2), exceeds 1 NTU. This sample must be analyzed for the 

presence of total coliforms. When one or more turbidity measurements in 

any day exceed 1 NTU, the system must collect this coliform sample 

within 24 hours of the first exceedance, unless the State determines 

that the system, for logistical reasons outside the system's control, 

cannot have the sample analyzed within 30 hours of collection. Sample 

results from this coliform monitoring must be included in determining 

compliance with the MCL for total coliforms in Sec. 141.63.

    (6) Special purpose samples, such as those taken to determine 

whether disinfection practices are sufficient following pipe placement, 

replacement, or repair, shall not be used to determine compliance with 

the MCL for total coliforms in Sec. 141.63. Repeat samples taken 

pursuant to paragraph (b) of this section are not considered special 

purpose samples, and must be used to determine compliance with the MCL 

for total coliforms in Sec. 141.63.

    (b) Repeat monitoring. (1) If a routine sample is total coliform-

positive, the public water system must collect a set of repeat samples 

within 24 hours of being notified of the positive result. A system which 

collects more than one routine sample/month must collect no fewer than 

three repeat samples for each total coliform-positive sample found. A 

system which collects one routine sample/month or fewer must collect no 

fewer than four repeat samples for each total coliform-positive sample 

found. The State may extend the 24-hour limit on a case-by-case basis if 

the system has a logistical problem in collecting the repeat samples 

within 24 hours that is beyond its control. In the case of an extension, 

the State must specify how much time



[[Page 356]]



the system has to collect the repeat samples.

    (2) The system must collect at least one repeat sample from the 

sampling tap where the original total coliform-positive sample was 

taken, and at least one repeat sample at a tap within five service 

connections upstream and at least one repeat sample at a tap within five 

service connections downstream of the original sampling site. If a total 

coliform-positive sample is at the end of the distribution system, or 

one away from the end of the distribution system, the State may waive 

the requirement to collect at least one repeat sample upstream or 

downstream of the original sampling site.

    (3) The system must collect all repeat samples on the same day, 

except that the State may allow a system with a single service 

connection to collect the required set of repeat samples over a four-day 

period or to collect a larger volume repeat sample(s) in one or more 

sample containers of any size, as long as the total volume collected is 

at least 400 ml (300 ml for systems which collect more than one routine 

sample/month).

    (4) If one or more repeat samples in the set is total coliform-

positive, the public water system must collect an additional set of 

repeat samples in the manner specified in paragraphs (b) (1)-(3) of this 

section. The additional samples must be collected within 24 hours of 

being notified of the positive result, unless the State extends the 

limit as provided in paragraph (b)(1) of this section. The system must 

repeat this process until either total coliforms are not detected in one 

complete set of repeat samples or the system determines that the MCL for 

total coliforms in Sec. 141.63 has been exceeded and notifies the 

State.

    (5) If a system collecting fewer than five routine samples/month has 

one or more total coliform-positive samples and the State does not 

invalidate the sample(s) under paragraph (c) of this section, it must 

collect at least five routine samples during the next month the system 

provides water to the public, except that the State may waive this 

requirement if the conditions of paragraph (b)(5) (i) or (ii) of this 

section are met. The State cannot waive the requirement for a system to 

collect repeat samples in paragraphs (b) (1)-(4) of this section.

    (i) The State may waive the requirement to collect five routine 

samples the next month the system provides water to the public if the 

State, or an agent approved by the State, performs a site visit before 

the end of the next month the system provides water to the public. 

Although a sanitary survey need not be performed, the site visit must be 

sufficiently detailed to allow the State to determine whether additional 

monitoring and/or any corrective action is needed. The State cannot 

approve an employee of the system to perform this site visit, even if 

the employee is an agent approved by the State to perform sanitary 

surveys.

    (ii) The State may waive the requirement to collect five routine 

samples the next month the system provides water to the public if the 

State has determined why the sample was total coliform-positive and 

establishes that the system has corrected the problem or will correct 

the problem before the end of the next month the system serves water to 

the public. In this case, the State must document this decision to waive 

the following month's additional monitoring requirement in writing, have 

it approved and signed by the supervisor of the State official who 

recommends such a decision, and make this document available to the EPA 

and public. The written documentation must describe the specific cause 

of the total coliform-positive sample and what action the system has 

taken and/or will take to correct this problem. The State cannot waive 

the requirement to collect five routine samples the next month the 

system provides water to the public solely on the grounds that all 

repeat samples are total coliform-negative. Under this paragraph, a 

system must still take at least one routine sample before the end of the 

next month it serves water to the public and use it to determine 

compliance with the MCL for total coliforms in Sec. 141.63, unless the 

State has determined that the system has corrected the contamination 

problem before the system took the set of repeat samples required in 

paragraphs (b) (1)-



[[Page 357]]



(4) of this section, and all repeat samples were total coliform-

negative.

    (6) After a system collects a routine sample and before it learns 

the results of the analysis of that sample, if it collects another 

routine sample(s) from within five adjacent service connections of the 

initial sample, and the initial sample, after analysis, is found to 

contain total coliforms, then the system may count the subsequent 

sample(s) as a repeat sample instead of as a routine sample.

    (7) Results of all routine and repeat samples not invalidated by the 

State must be included in determining compliance with the MCL for total 

coliforms in Sec. 141.63.

    (c) Invalidation of total coliform samples. A total coliform-

positive sample invalidated under this paragraph (c) does not count 

towards meeting the minimum monitoring requirements of this section.

    (1) The State may invalidate a total coliform-positive sample only 

if the conditions of paragraph (c)(1) (i), (ii), or (iii) of this 

section are met.

    (i) The laboratory establishes that improper sample analysis caused 

the total coliform-positive result.

    (ii) The State, on the basis of the results of repeat samples 

collected as required by paragraphs (b) (1) through (4) of this section, 

determines that the total coliform-positive sample resulted from a 

domestic or other non-distribution system plumbing problem. The State 

cannot invalidate a sample on the basis of repeat sample results unless 

all repeat sample(s) collected at the same tap as the original total 

coliform-positive sample are also total coliform-positive, and all 

repeat samples collected within five service connections of the original 

tap are total coliform-negative (e.g., a State cannot invalidate a total 

coliform-positive sample on the basis of repeat samples if all the 

repeat samples are total coliform-negative, or if the public water 

system has only one service connection).

    (iii) The State has substantial grounds to believe that a total 

coliform-positive result is due to a circumstance or condition which 

does not reflect water quality in the distribution system. In this case, 

the system must still collect all repeat samples required under 

paragraphs (b) (1)-(4) of this section, and use them to determine 

compliance with the MCL for total coliforms in Sec. 141.63. To 

invalidate a total coliform-positive sample under this paragraph, the 

decision with the rationale for the decision must be documented in 

writing, and approved and signed by the supervisor of the State official 

who recommended the decision. The State must make this document 

available to EPA and the public. The written documentation must state 

the specific cause of the total coliform-positive sample, and what 

action the system has taken, or will take, to correct this problem. The 

State may not invalidate a total coliform-positive sample solely on the 

grounds that all repeat samples are total coliform-negative.

    (2) A laboratory must invalidate a total coliform sample (unless 

total coliforms are detected) if the sample produces a turbid culture in 

the absence of gas production using an analytical method where gas 

formation is examined (e.g., the Multiple-Tube Fermentation Technique), 

produces a turbid culture in the absence of an acid reaction in the 

Presence-Absence (P-A) Coliform Test, or exhibits confluent growth or 

produces colonies too numerous to count with an analytical method using 

a membrane filter (e.g., Membrane Filter Technique). If a laboratory 

invalidates a sample because of such interference, the system must 

collect another sample from the same location as the original sample 

within 24 hours of being notified of the interference problem, and have 

it analyzed for the presence of total coliforms. The system must 

continue to re-sample within 24 hours and have the samples analyzed 

until it obtains a valid result. The State may waive the 24-hour time 

limit on a case-by-case basis.

    (d) Sanitary surveys. (1)(i) Public water systems which do not 

collect five or more routine samples/month must undergo an initial 

sanitary survey by June 29, 1994, for community public water systems and 

June 29, 1999, for non-community water systems. Thereafter, systems must 

undergo another



[[Page 358]]



sanitary survey every five years, except that non-community water 

systems using only protected and disinfected ground water, as defined by 

the State, must undergo subsequent sanitary surveys at least every ten 

years after the initial sanitary survey. The State must review the 

results of each sanitary survey to determine whether the existing 

monitoring frequency is adequate and what additional measures, if any, 

the system needs to undertake to improve drinking water quality.

    (ii) In conducting a sanitary survey of a system using ground water 

in a State having an EPA-approved wellhead protection program under 

section 1428 of the Safe Drinking Water Act, information on sources of 

contamination within the delineated wellhead protection area that was 

collected in the course of developing and implementing the program 

should be considered instead of collecting new information, if the 

information was collected since the last time the system was subject to 

a sanitary survey.

    (2) Sanitary surveys must be performed by the State or an agent 

approved by the State. The system is responsible for ensuring the survey 

takes place.

    (e) Fecal coliforms/Escherichia coli (E. coli) testing. (1) If any 

routine or repeat sample is total coliform-positive, the system must 

analyze that total coliform-positive culture medium to determine if 

fecal coliforms are present, except that the system may test for E. coli 

in lieu of fecal coliforms. If fecal coliforms or E. coli are present, 

the system must notify the State by the end of the day when the system 

is notified of the test result, unless the system is notified of the 

result after the State office is closed, in which case the system must 

notify the State before the end of the next business day.

    (2) The State has the discretion to allow a public water system, on 

a case-by-case basis, to forgo fecal coliform or E. coli testing on a 

total coliform-positive sample if that system assumes that the total 

coliform-positive sample is fecal coliform-positive or E. coli-positive. 

Accordingly, the system must notify the State as specified in paragraph 

(e)(1) of this section and the provisions of Sec. 141.63(b) apply.

    (f) Analytical methodology. (1) The standard sample volume required 

for total coliform analysis, regardless of analytical method used, is 

100 ml.

    (2) Public water systems need only determine the presence or absence 

of total coliforms; a determination of total coliform density is not 

required.

    (3) Public water systems must conduct total coliform analyses in 

accordance with one of the analytical methods in the following table.



----------------------------------------------------------------------------------------------------------------

               Organism                              Methodology\12\                        Citation\1\

----------------------------------------------------------------------------------------------------------------

Total Coliforms \2\...................  Total Coliform Fermentation Technique 3,  9221A, B.

                                         4, 5.

                                        Total Coliform Membrane Filter Technique  9222A, B, C.

                                         \6\.

                                        Presence-Absence (P-A) Coliform Test 5,   9221D.

                                         7.

                                        ONPG-MUG Test \8\.......................  9223.

                                        Colisure Test \9\.                        ..............................

                                        E*Colite [reg] Test \10\.                 ..............................

                                        m-ColiBlue24 [reg] Test \11\.             ..............................

                                        Readycult [reg] Coliforms 100 Presence/   ..............................

                                         Absence Test \13\.

                                        Membrane Filter Technique using           ..............................

                                         Chromocult [reg] Coliform Agar\14\.

                                        Colitag [reg] Test \15\.                  ..............................

----------------------------------------------------------------------------------------------------------------

The procedures shall be done in accordance with the documents listed below. The incorporation by reference of

  the following documents listed in footnotes 1, 6, 8, 9, 10 , 11, 13, 14 and 15 was approved by the Director of

  the Federal Register in accordance with 5 U.S.C. 552(a) and 1 CFR Part 51. Copies of the documents may be

  obtained from the sources listed below. Information regarding obtaining these documents can be obtained from

  the Safe Drinking Water Hotline at 800-426-4791. Documents may be inspected at EPA's Drinking Water Docket,

  EPA West, 1301 Constitution Avenue, NW., EPA West, Room B102, Washington DC 20460 (Telephone: 202-566-2426);

  or at the National Archives and Records Administration (NARA). For information on the availability of this

  material at NARA, call 202-741-6030, or go to: http://www.archives.gov/federal--register/code--of--federal--

  regulations/ibr--locations.html.

\1\ Standard Methods for the Examination of Water and Wastewater, 18th edition (1992), 19th edition (1995), or

  20th edition (1998). American Public Health Association, 1015 Fifteenth Street, NW., Washington, DC 20005. The

  cited methods published in any of these three editions may be used.

\2\ The time from sample collection to initiation of analysis may not exceed 30 hours. Systems are encouraged

  but not required to hold samples below 10 deg. C during transit.

\3\ Lactose broth, as commercially available, may be used in lieu of lauryl tryptose broth, if the system

  conducts at least 25 parallel tests between this medium and lauryl tryptose broth using the water normally

  tested, and this comparison demonstrates that the false-positive rate and false-negative rate for total

  coliform, using lactose broth, is less than 10 percent.

\4\ If inverted tubes are used to detect gas production, the media should cover these tubes at least one-half to

  two-thirds after the sample is added.

\5\ No requirement exists to run the completed phase on 10 percent of all total coliform-positive confirmed

  tubes.



[[Page 359]]





\6\ MI agar also may be used. Preparation and use of MI agar is set forth in the article, ``New medium for the

  simultaneous detection of total coliform and Escherichia coli in water'' by Brenner, K.P., et. al., 1993,

  Appl. Environ. Microbiol. 59:3534-3544. Also available from the Office of Water Resource Center (RC-4100T),

  1200 Pennsylvania Avenue, NW., Washington, DC 20460, EPA/600/J-99/225. Verification of colonies is not

  required.

\7\ Six-times formulation strength may be used if the medium is filter-sterilized rather than autoclaved.

\8\ The ONPG-MUG Test is also known as the Autoanalysis Collect System.

\9\ A description of the Colisure Test, Feb 28, 1994, may be obtained from IDEXX Laboratories, Inc., One IDEXX

  Drive, Westbrook, Maine 04092. The Colisure Test may be read after an incubation time of 24 hours.

\10\ A description of the E*Colite [reg] Test, ``Presence/Absence for Coliforms and E. Coli in Water,'' Dec 21,

  1997, is available from Charm Sciences, Inc., 36 Franklin Street, Malden, MA 02148-4120.

\11\ A description of the m-ColiBlue24 [reg] Test, Aug 17, 1999, is available from the Hach Company, 100 Dayton

  Avenue, Ames, IA 50010.

\12\ EPA strongly recommends that laboratories evaluate the false-positive and negative rates for the method(s)

  they use for monitoring total coliforms. EPA also encourages laboratories to establish false-positive and

  false-negative rates within their own laboratory and sample matrix (drinking water or source water) with the

  intent that if the method they choose has an unacceptable false-positive or negative rate, another method can

  be used. The Agency suggests that laboratories perform these studies on a minimum of 5% of all total coliform-

  positive samples, except for those methods where verification/confirmation is already required, e.g., the M-

  Endo and LES Endo Membrane Filter Tests, Standard Total Coliform Fermentation Technique, and Presence-Absence

  Coliform Test. Methods for establishing false-positive and negative-rates may be based on lactose

  fermentation, the rapid test for [beta]-galactosidase and cytochrome oxidase, multi-test identification

  systems, or equivalent confirmation tests. False-positive and false-negative information is often available in

  published studies and/or from the manufacturer(s).

\13\ The Readycult [reg] Coliforms 100 Presence/Absence Test is described in the document, ``Readycult [reg]

  Coliforms 100 Presence/Absence Test for Detection and Identification of Coliform Bacteria and Escherichla coli

  in Finished Waters'', November 2000, Version 1.0, available from EM Science (an affiliate of Merck KGgA,

  Darmstadt Germany), 480 S. Democrat Road, Gibbstown, NJ 08027-1297. Telephone number is (800) 222-0342, e-mail

  address is: adellenbusch@emscience.com.

\14\ Membrane Filter Technique using Chromocult [reg] Coliform Agar is described in the document, ``Chromocult

  [reg] Coliform Agar Presence/Absence Membrane Filter Test Method for Detection and Identification of Coliform

  Bacteria and Escherichla coli in Finished Waters'', November 2000, Version 1.0, available from EM Science (an

  affiliate of Merck KGgA, Darmstadt Germany), 480 S. Democrat Road, Gibbstown, NJ 08027-1297. Telephone number

  is (800) 222-0342, e-mail address is: adellenbusch@emscience.com.

\15\ Colitag [reg] product for the determination of the presence/absence of total coliforms and E. coli is

  described in ``Colitag [reg] Product as a Test for Detection and Identification of Coliforms and E. coli

  Bacteria in Drinking Water and Source Water as Required in National Primary Drinking Water Regulations,''

  August 2001, available from CPI International, Inc., 5580 Skylane Blvd., Santa Rosa, CA, 95403, telephone

  (800) 878-7654, Fax (707) 545-7901, Internet address http://www.cpiinternational.com.



    (4) [Reserved]

    (5) Public water systems must conduct fecal coliform analysis in 

accordance with the following procedure. When the MTF Technique or 

Presence-Absence (PA) Coliform Test is used to test for total coliforms, 

shake the lactose-positive presumptive tube or P-A vigorously and 

transfer the growth with a sterile 3-mm loop or sterile applicator stick 

into brilliant green lactose bile broth and EC medium to determine the 

presence of total and fecal coliforms, respectively. For EPA-approved 

analytical methods which use a membrane filter, transfer the total 

coliform-positive culture by one of the following methods: remove the 

membrane containing the total coliform colonies from the substrate with 

a sterile forceps and carefully curl and insert the membrane into a tube 

of EC medium (the laboratory may first remove a small portion of 

selected colonies for verification), swab the entire membrane filter 

surface with a sterile cotton swab and transfer the inoculum to EC 

medium (do not leave the cotton swab in the EC medium), or inoculate 

individual total coliform-positive colonies into EC Medium. Gently shake 

the inoculated tubes of EC medium to insure adequate mixing and incubate 

in a waterbath at 44.5  0.2 [deg]C for 24  2 hours. Gas production of any amount in the inner 

fermentation tube of the EC medium indicates a positive fecal coliform 

test. The preparation of EC medium is described in Method 9221E 

(paragraph 1a) in Standard Methods for the Examination of Water and 

Wastewater, 18th edition (1992), 19th edition (1995), and 20th edition 

(1998); the cited method in any one of these three editions may be used. 

Public water systems need only determine the presence or absence of 

fecal coliforms; a determination of fecal coliform density is not 

required.

    (6) Public water systems must conduct analysis of Escherichia coli 

in accordance with one of the following analytical methods:

    (i) EC medium supplemented with 50 [micro]g/mL of 4-

methylumbelliferyl-beta-D-glucuronide (MUG) (final concentration), as 

described in Method 9222G in Standard Methods for the Examination of 

Water and Wastewater, 19th edition (1995) and 20th edition (1998). 

Either edition may be used. Alternatively, the 18th edition (1992) may 

be used if at least 10 mL of EC medium, as described in paragraph (f)(5) 

of this section, is supplemented with 50 [micro]g/mL of MUG before 

autoclaving. The inner inverted fermentation tube may be omitted. If



[[Page 360]]



the 18th edition is used, apply the procedure in paragraph (f)(5) of 

this section for transferring a total coliform-positive culture to EC 

medium supplemented with MUG, incubate the tube at 44.5  0.2 [deg]C for 24  2 hours, and 

then observe fluorescence with an ultraviolet light (366 nm) in the 

dark. If fluorescence is visible, E. coli are present.

    (ii) Nutrient agar supplemented with 100 [micro]g/mL of 4-

methylumbelliferyl-beta-D-glucuronide (MUG) (final concentration), as 

described in Method 9222G in Standard Methods for the Examination of 

Water and Wastewater, 19th edition (1995) and 20th edition (1998). 

Either edition may be used for determining if a total coliform-positive 

sample, as determined by a membrane filter technique, contains E. coli. 

Alternatively, the 18th edition (1992) may be used if the membrane 

filter containing a total coliform-positive colony(ies) is transferred 

to nutrient agar, as described in Method 9221B (paragraph 3) of Standard 

Methods (18th edition), supplemented with 100 [micro]g/mL of MUG. If the 

18th edition is used, incubate the agar plate at 35 [deg]C for 4 hours 

and then observe the colony(ies) under ultraviolet light (366 nm) in the 

dark for fluorescence. If fluorescence is visible, E. coli are present.

    (iii) Minimal Medium ONPG-MUG (MMO-MUG) Test, as set forth in the 

article ``National Field Evaluation of a Defined Substrate Method for 

the Simultaneous Detection of Total Coliforms and Escherichia coli from 

Drinking Water: Comparison with Presence-Absence Techniques'' (Edberg et 

al.), Applied and Environmental Microbiology, Volume 55, pp. 1003-1008, 

April 1989. (Note: The Autoanalysis Colilert System is an MMO-MUG test). 

If the MMO-MUG test is total coliform-positive after a 24-hour 

incubation, test the medium for fluorescence with a 366-nm ultraviolet 

light (preferably with a 6-watt lamp) in the dark. If fluorescence is 

observed, the sample is E. coli-positive. If fluorescence is 

questionable (cannot be definitively read) after 24 hours incubation, 

incubate the culture for an additional four hours (but not to exceed 28 

hours total), and again test the medium for fluorescence. The MMO-MUG 

Test with hepes buffer in lieu of phosphate buffer is the only approved 

formulation for the detection of E. coli.

    (iv) The Colisure Test. A description of the Colisure Test may be 

obtained from the Millipore Corporation, Technical Services Department, 

80 Ashby Road, Bedford, MA 01730.

    (v) The membrane filter method with MI agar, a description of which 

is cited in footnote 6 to the table in paragraph (f)(3) of this section.

    (vi) E*Colite [reg] Test, a description of which is cited 

in footnote 10 to the table at paragraph (f)(3) of this section.

    (vii) m-ColiBlue24 [reg] Test, a description of which is 

cited in footnote 11 to the table in paragraph (f)(3) of this section.

    (viii) Readycult [reg] Coliforms 100 Presence/Absence 

Test, a description of which is cited in footnote 13 to the table at 

paragraph (f)(3) of this section.

    (ix) Membrane Filter Technique using Chromocult [reg] 

Coliform Agar, a description of which is cited in footnote 14 to the 

table at paragraph (f)(3) of this section.

    (x) Colitag [reg], a description of which is cited in 

footnote 15 to the table at paragraph (f)(3) of this section.

    (7) As an option to paragraph (f)(6)(iii) of this section, a system 

with a total coliform-pos i tive, MUG-negative, MMO-MUG test may further 

analyze the culture for the presence of E. coli by transferring a 0.1 

ml, 28-hour MMO-MUG culture to EC Medium + MUG with a pipet. The 

formulation and incubation conditions of EC Medium + MUG, and 

observation of the results are described in paragraph (f)(6)(i) of this 

section.

    (8) The following materials are incorporated by reference in this 

section with the approval of the Director of the Federal Register in 

accordance with 5 U.S.C. 552(a) and 1 CFR part 51. Copies of the 

analytical methods cited in Standard Methods for the Examination of 

Water and Wastewater (18th, 19th, and 20th editions) may be obtained 

from the American Public Health Association et al.; 1015 Fifteenth 

Street, NW., Washington, DC 20005-2605. Copies of the MMO-MUG Test, as 

set forth in the article ``National Field Evaluation of a Defined 

Substrate Method for the Simultaneous Enumeration of Total Coliforms and 

Escherichia coli from



[[Page 361]]



Drinking Water: Comparison with the Standard Multiple Tube Fermentation 

Method'' (Edberg et al.) may be obtained from the American Water Works 

Association Research Foundation, 6666 West Quincy Avenue, Denver, CO 

80235. Copies of the MMO-MUG Test as set forth in the article ``National 

Field Evaluation of a Defined Substrate Method for the Simultaneous 

Enumeration of Total Coliforms and Escherichia coli from Drinking Water: 

Comparison with the Standard Multiple Tube Fermentation Method'' (Edberg 

et al.) may be obtained from the American Water Works Association 

Research Foundation, 6666 West Quincy Avenue, Denver, CO 80235. A 

description of the Colisure Test may be obtained from the Millipore 

Corp., Technical Services Department, 80 Ashby Road, Bedford, MA 01730. 

Copies may be inspected at EPA's Drinking Water Docket; 401 M St., SW.; 

Washington, DC 20460, or at the National Archives and Records 

Administration (NARA). For information on the availability of this 

material at NARA, call 202-741-6030, or go to: http://www.archives.gov/

federal--register/code--of--federal--regulations/ibr--locations.html.

    (g) Response to violation. (1) A pub lic water system which has 

exceeded the MCL for total coliforms in Sec. 141.63 must report the 

violation to the State no later than the end of the next busi ness day 

after it learns of the violation, and notify the public in accordance 

with subpart Q.

    (2) A public water system which has failed to comply with a coliform 

monitoring requirement, including the sanitary survey requirement, must 

report the monitoring violation to the State within ten days after the 

system discovers the violation, and notify the public in accordance with 

subpart Q.



[54 FR 27562, June 29, 1989, as amended at 54 FR 30001, July 17, 1989; 

55 FR 25064, June 19, 1990; 56 FR 642, Jan. 8, 1991; 57 FR 1852, Jan. 

15, 1992; 57 FR 24747, June 10, 1992; 59 FR 62466, Dec. 5, 1994; 60 FR 

34085, June 29, 1995; 64 FR 67461, Dec. 1, 1999; 65 FR 26022, May 4, 

2000; 67 FR 65246, Oct. 23, 2002; 67 FR 65896, Oct. 29, 2002; 69 FR 

7160, Feb. 13, 2004]