[Code of Federal Regulations] [Title 46, Volume 4] [Revised as of October 1, 2005] From the U.S. Government Printing Office via GPO Access [CITE: 46CFR111.10-9] [Page 218] TITLE 46--SHIPPING CHAPTER I--COAST GUARD, DEPARTMENT OF HOMELAND SECURITY (CONTINUED) PART 111_ELECTRIC SYSTEMS_GENERAL REQUIREMENTS--Table of Contents Subpart 111.10_Power Supply Sec. 111.10-9 Ship's service supply transformers; two required. If transformers are used to supply the ship's service distribution system required by this subpart for ships and mobile offshore drilling units, there must be at least two installed, independent power transformers. With the largest transformer out of service, the capacity of the remaining units must be sufficient to supply the ship service loads. Note to Sec. 111.10-9: A ship's service supply system would consist of transformers, overcurrent protection devices, and cables, and would normally be located in the system between a medium voltage bus and a low voltage ship's service switchboard. [CGD 94-108, 61 FR 28277, June 4, 1996; 61 FR 33045, June 26, 1996]