Sec. 180.209  Requirements for requalification of specification cylinders.



    (a) Periodic qualification of cylinders. (1) Each specification 

cylinder that becomes due for periodic requalification, as specified in 

the following table, must be requalified and marked in conformance with 

the requirements of this subpart. Requalification records must be 

maintained in accordance with Sec. 180.215. Table 1 follows:



                Table 1--Requalification of Cylinders \1\

------------------------------------------------------------------------

  Specification under which       Minimum test         Requalification

      cylinder was made       pressure  (psig) \2\     period  (years)

------------------------------------------------------------------------

DOT 3.......................  3000 psig...........  5

DOT 3A, 3AA.................  5/3 times service     5, 10, or 12 (see

                               pressure, except      Sec.  180.209(b),

                               noncorrosive          (f), (h), and (j)

                               service (see Sec.

                               180.209(g)).

DOT 3AL.....................  5/3 times service     5 or 12 (see Sec.

                               pressure.             180.209(j))

DOT 3AX, 3AAX...............  5/3 times service     5

                               pressure.

3B, 3BN.....................  2 times service       5 or 10 (see Sec.

                               pressure (see Sec.   180.209(f))

                                180.209(g)).

3E..........................  Test not required...

3HT.........................  5/3 times service     3 (see Sec. Sec.

                               pressure.             180.209(k) and

                                                     180.213(c))

3T..........................  5/3 times service     5

                               pressure.

4AA480......................  2 times service       5 or 10 (see Sec.

                               pressure (see Sec.   180.209(h))

                                180.209(g)).



[[Page 1091]]





4B, 4BA, 4BW, 4B-240ET......  2 times service       5, 10, or 12 (see

                               pressure, except      Sec.  180.209(e),

                               non-corrosive         (f), and (j))

                               service (see Sec.

                               180.209(g)).

4D, 4DA, 4DS................  2 times service.....  5

DOT 4E......................  2 times service       5

                               pressure, except

                               non-corrosive (see

                               Sec.  180.209(g)).

4L..........................  Test not required...

8, 8AL......................  ....................  10 or 20 (see Sec.

                                                     180.209(i))

Exemption cylinder..........  See current           See current

                               exemption.            exemption

Foreign cylinder (see Sec.   As marked on          5 (see Sec. Sec.

 173.301(j) of this            cylinder, but not     180.209(l) and

 subchapter for restrictions   less than 5/3 of      180.213(d)(2))

 on use).                      any service or

                               working pressure

                               marking.

------------------------------------------------------------------------

\1\ Any cylinder not exceeding 2 inches outside diameter and less than 2

  feet in length is excepted from volumetric expansion test.

\2\ For cylinders not marked with a service pressure, see Sec.

  173.301a(b) of this subchapter.



    (b) DOT 3A or 3AA cylinders. (1) A cylinder conforming to 

specification DOT 3A or 3AA with a water capacity of 56.7 kg (125 lb) or 

less that is removed from any cluster, bank, group, rack, or vehicle 

each time it is filled, may be requalified every ten years instead of 

every five years, provided the cylinder conforms to all of the following 

conditions:

    (i) The cylinder was manufactured after December 31, 1945.

    (ii) The cylinder is used exclusively for air; argon; cyclopropane; 

ethylene; helium; hydrogen; krypton; neon; nitrogen; nitrous oxide; 

oxygen; sulfur hexafluoride; xenon; chlorinated hydrocarbons, 

fluorinated hydrocarbons, liquefied hydrocarbons, and mixtures thereof 

that are commercially free from corroding components; permitted mixtures 

of these gases (see Sec. 173.301(d) of this subchapter); and permitted 

mixtures of these gases with up to 30 percent by volume of carbon 

dioxide, provided the gas has a dew point at or below minus (52 [deg]F) 

at 1 atmosphere.

    (iii) Before each refill, the cylinder is removed from any cluster, 

bank, group, rack or vehicle and passes the hammer test specified in CGA 

Pamphlet C-6 (IBR, see Sec. 171.7 of this subchapter).

    (iv) The cylinder is dried immediately after hydrostatic testing to 

remove all traces of water.

    (v) The cylinder is not used for underwater breathing.

    (vi) Each cylinder is stamped with a five-pointed star at least one-

fourth of an inch high immediately following the test date.

    (2) If, since the last required requalification, a cylinder has not 

been used exclusively for the gases specifically identified in paragraph 

(b)(1)(ii) of this section, but currently conforms with all other 

provisions of paragraph (b)(1) of this section, it may be requalified 

every 10 years instead of every five years, provided it is first 

requalified and examined as prescribed by Sec. 173.302a(b) (2), (3) and 

(4) of this subchapter.

    (3) Except as specified in paragraph (b)(2) of this section, if a 

cylinder, marked with a star, is filled with a compressed gas other than 

as specified in paragraph (b)(1)(ii) of this section, the star following 

the most recent test date must be obliterated. The cylinder must be 

requalified five years from the marked test date, or prior to the first 

filling with a compressed gas, if the required five-year requalification 

period has passed.

    (c) DOT 4-series cylinders. A DOT 4-series cylinder, except a 4L 

cylinder, that at any time shows evidence of a leak or of internal or 

external corrosion, denting, bulging or rough usage to the extent that 

it is likely to be weakened appreciably, or that has lost five percent 

or more of its official tare weight must be requalified before being 

refilled and offered for transportation. (Refer to CGA Pamphlet C-6 or 

C-6.3, as applicable, regarding cylinder weakening.) After testing, the 

actual tare weight must be recorded as the new tare weight.



[[Page 1092]]



    (d) Cylinders 5.44 kg (12 lb) or less with service pressures of 300 

psig or less. A cylinder of 5.44 (12 lb) or less water capacity 

authorized for service pressure of 300 psig or less must be given a 

complete external visual inspection at the time periodic requalification 

becomes due. External visual inspection must be in accordance with CGA 

Pamphlet C-6 or C-6.1 (IBR, see Sec. 171.7 of this subchapter). The 

cylinder may be proof pressure tested. The test is successful if the 

cylinder, when examined under test pressure, does not display a defect 

described in Sec. 180.205(i)(1) (ii) or (iii). Upon successful 

completion of the test and inspection, the cylinder must be marked in 

accordance with Sec. 180.213.

    (e) Proof pressure test A cylinder made in conformance with 

specifications DOT 4B, 4BA, 4BW, or 4E used exclusively for: liquefied 

petroleum gas that meets the detail requirement limits in Table I of 

ASTM D 1835, ``Standard Specification for Liquefied Petroleum (LP) 

Gases'' (IBR see Sec. 171.7 of this subchapter) or an equivalent 

standard containing the same limits; anhydrous dimethylamine; anhydrous 

methylamine; anhydrous trimethylamine; methyl chloride; methylacetylene-

propadiene stabilized; or dichlorodifluoromethane, difluoroethane, 

difluorochloroethane, chlorodifluoromethane, chlorotetrafluoroethane, 

trifluorochloroethylene, or mixture thereof, or mixtures of one or more 

with trichlorofluoromethane; and commercially free from corroding 

components and protected externally by a suitable corrosion-resistant 

coating (such as galvanizing or painting) may be requalified by 

volumetric expansion testing every 12 years instead of every five years. 

As an alternative, the cylinder may be subjected to a proof pressure 

test at least two times the marked service pressure, but this latter 

type of test must be repeated every seven years after expiration of the 

first 12-year period. When subjected to a proof pressure test, the 

cylinder must be carefully examined under test pressure and removed from 

service if a leak or defect is found.

    (f) Poisonous materials. A cylinder conforming to specification DOT 

3A, 3AA, 3B, 4BA, or 4BW having a service pressure of 300 psig or less 

and used exclusively for methyl bromide, liquid; mixtures of methyl 

bromide and ethylene dibromide, liquid; mixtures of methyl bromide and 

chlorpicrin, liquid; mixtures of methyl bromide and petroleum solvents, 

liquid; or methyl bromide and nonflammable, nonliquefied compressed gas 

mixtures, liquid; commercially free of corroding components, and 

protected externally by a suitable corrosion resistant coating (such as 

galvanizing or painting) and internally by a suitable corrosion 

resistant lining (such as galvanizing) may be tested every 10 years 

instead of every five years, provided a visual internal and external 

examination of the cylinder is conducted every five years in accordance 

with CGA Pamphlet C-6. The cylinder must be examined at each filling, 

and rejected if a dent, corroded area, leak or other condition indicates 

possible weakness.

    (g) Visual inspections. A cylinder conforming to a specification 

listed in the table in this paragraph and used exclusively in the 

service indicated may, instead of a periodic hydrostatic test, be given 

a complete external visual inspection at the time periodic 

requalification becomes due. External visual inspection must be in 

accordance with CGA Pamphlet C-6 or C-6.3, as applicable (IBR, see Sec. 

171.7 of this subchapter). When this inspection is used instead of 

hydrostatic pressure testing, subsequent inspections are required at 

five-year intervals after the first inspection. After May 31, 2004, 

inspections must be made only by persons holding a current RIN and the 

results recorded and maintained in accordance with Sec. 180.215. 

Records must include: date of inspection (month and year); DOT 

specification number; cylinder identification (registered symbol and 

serial number, date of manufacture, and owner); type of cylinder 

protective coating (including statement as to need of refinishing or 

recoating); conditions checked (e.g., leakage, corrosion, gouges, dents 

or digs in shell or heads, broken or damaged footring or protective ring 

or fire damage); disposition of cylinder (returned to service, returned 

to cylinder manufacturer for repairs or condemned). A cylinder passing 

requalification by the external visual inspection must be marked in 

accordance



[[Page 1093]]



with Sec. 180.213. Specification cylinders must be in exclusive service 

as shown in the following table:



------------------------------------------------------------------------

       Cylinders conforming to--              Used exclusively for--

------------------------------------------------------------------------

DOT 3A, DOT 3AA, DOT 3A480X, DOT 4AA480  Anhydrous ammonia of at least

                                          99.95% purity.

DOT 3A, DOT 3AA, DOT 3A480X, DOT 3B,     Butadiene, inhibited, that is

 DOT 4B, DOT 4BA, DOT 4BW.                commercially free from

                                          corroding components.

DOT 3A, DOT 3A480X, DOT 3AA, DOT 3B,     Cyclopropane that is

 DOT 4AA480, DOT 4B, DOT 4BA, DOT 4BW.    commercially free from

                                          corroding components.

DOT 3A, DOT 3AA, DOT 3A480X, DOT 4B,     Chlorinated hydrocarbons and

 DOT 4BA, DOT 4BW, DOT 4E.                mixtures thereof that are

                                          commercially free from

                                          corroding components.

DOT 3A, DOT 3AA, DOT 3A480X, DOT 4B,     Fluorinated hydrocarbons and

 DOT 4BA, DOT 4BW, DOT 4E.                mixtures thereof that are

                                          commercially free from

                                          corroding components.

DOT 3A, DOT 3AA, DOT 3A480X, DOT 3B,     Liquefied hydrocarbon gas that

 DOT 4B, DOT 4BA, DOT 4BW, DOT 4E.        is commercially free from

                                          corroding components.

DOT 3A, DOT 3AA, DOT 3A480X, DOT 3B,     Liquefied petroleum gas that

 DOT 4B, DOT 4BA, DOT 4BW, DOT 4E.        meets the detail requirements

                                          limits in Table 1 of ASTM

                                          1835, Standard Specification

                                          for Liquefied Petroleum (LP)

                                          Gases (incorporated by

                                          reference; see Sec.  171.7 of

                                          this subchapter) or an

                                          equivalent standard containing

                                          the same limits.

DOT 3A, DOT 3AA, DOT 3B, DOT 4B, DOT     Methylacetylene-propadiene,

 4BA, DOT 4BW, DOT 4E.                    stabilized, that is

                                          commercially free from

                                          corroding components.

DOT 3A, DOT 3AA, DOT 3B, DOT 4B, DOT     Anhydrous mono,

 4BA, DOT 4BW.                            di,trimethylamines that are

                                          commercially free from

                                          corroding components.

DOT 4B240, DOT 4BW240..................  Ethyleneimine, stabilized.

------------------------------------------------------------------------



    (h) Cylinders containing anhydrous ammonia. A cylinder conforming to 

specification DOT 3A, 3A480X, or 4AA480 used exclusively for anhydrous 

ammonia, commercially free from corroding components, and protected 

externally by a suitable corrosion-resistant coating (such as paint) may 

be requalified every 10 years instead of every five years.

    (i) Requalification of DOT-8 series cylinders. (1) Each owner of a 

DOT-8 series cylinder used to transport acetylene must have the cylinder 

shell and the porous filler requalified in accordance with CGA Pamphlet 

C-13 (IBR, see Sec. 171.7 of this subchapter). Requalification must be 

performed in accordance with the following schedule:



----------------------------------------------------------------------------------------------------------------

                                         Shell (visual inspection)             Porous filler requalification

                                              requalification            ---------------------------------------

  Date of cylinder manufacture   ----------------------------------------

                                        Initial           Subsequent            Initial           Subsequent

----------------------------------------------------------------------------------------------------------------

Before January 1, 1991..........  Before January 1,   10 years..........  Before January 1,   Not required.

                                   2001.                                   2011.

On or after January 1, 1991.....  10 years \1\......  10 years..........  3 to 20 years \2\.  Not required.

----------------------------------------------------------------------------------------------------------------

\1\ Years from date of cylinder manufacture.

\2\ For a cylinder manufactured on or after January 1, 1991, requalification of the porous filler must be

  performed no sooner than 5 years, and no later than 20 years, from the date of manufacture.



    (2) Unless requalified and marked in accordance with CGA Pamphlet C-

13 before October 1, 1994, an acetylene cylinder must be requalified by 

a person who holds a current RIN.

    (3) If a cylinder valve is replaced, a cylinder valve of the same 

weight must be used or the tare weight of the cylinder must be adjusted 

to compensate for valve weight differential.

    (4) The person performing a visual inspection or requalification 

must record the results as specified in Sec. 180.215.

    (5) The person performing a visual inspection or requalification 

must mark the cylinder as specified in Sec. 180.213.

    (j) Cylinder used as a fire extinguisher. Only a DOT specification 

cylinder used as a fire extinguisher and meeting Special Provision 18 in 

Sec. 172.102(c)(1) of this subchapter may be requalified in accordance 

with this paragraph (j).

    (1) A DOT 4B, 4BA, 4B240ET or 4BW cylinder may be tested as follows:

    (i) For a cylinder with a water capacity of 5.44 kg (12 lb) or less, 

by volumetric expansion test using the water



[[Page 1094]]



jacket method or by proof pressure test. A requalification must be 

performed by the end of 12 years after the original test date and at 12-

year intervals thereafter.

    (ii) For a cylinder having a water capacity over 5.44 kg (12 lb)--

    (A) By proof pressure test. A requalification must be performed by 

the end of 12 years after the original test date and at 7-year 

intervals; or

    (B) By volumetric expansion test using the water jacket method. A 

requalification must be performed 12 years after the original test date 

and at 12-year intervals thereafter.

    (2) A DOT 3A, 3AA, or 3AL cylinder must be requalified by volumetric 

expansion test using the water jacket method. A requalification must be 

performed 12 years after the original test date and at 12-year intervals 

thereafter.

    (k) 3HT cylinders. In addition to the other requirements of this 

section, a cylinder marked DOT-3HT must be requalified in accordance 

with CGA C-8 (IBR, see Sec. 171.7 of this subchapter).

    (l) Requalification of foreign cylinders filled for export. A 

cylinder manufactured outside the United States, other than as provided 

in Sec. 171.12a of this subchapter, that has not been manufactured, 

inspected, tested and marked in accordance with part 178 of this 

subchapter may be filled with compressed gas in the United States, and 

shipped solely for export if it meets the following requirements, in 

addition to other requirements of this subchapter:

    (1) It has been inspected, tested and marked (with only the month 

and year of test) in conformance with the procedures and requirements of 

this subpart or the Associate Administrator has authorized the filling 

company to fill foreign cylinders under an alternative method of 

qualification; and

    (2) It is offered for transportation in conformance with the 

requirements of Sec. 173.301(l) of this subchapter.