[Code of Federal Regulations]

[Title 24, Volume 5]

[Revised as of April 1, 2006]

From the U.S. Government Printing Office via GPO Access

[CITE: 24CFR3280.305]



[Page 127-136]

 

                 TITLE 24--HOUSING AND URBAN DEVELOPMENT

 

 CHAPTER XX--OFFICE OF ASSISTANT SECRETARY FOR HOUSING--FEDERAL HOUSING 

        COMMISSIONER, DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT

 

PART 3280_MANUFACTURED HOME CONSTRUCTION AND SAFETY STANDARDS--Table 

of Contents

 

           Subpart D_Body and Frame Construction Requirements

 

Sec.  3280.305  Structural design requirements.



    (a) General. Each manufactured home shall be designed and 

constructed as a completely integrated structure capable of sustaining 

the design load requirements of this standard, and shall be capable of 

transmitting these loads to stabilizing devices without exceeding the 

allowable stresses or deflections. Roof framing shall be securely 

fastened to wall framing, walls to floor structure, and floor structure 

to chassis to secure and maintain continuity between the floor and 

chassis, so as to resist wind overturning, uplift, and sliding as 

imposed by design loads in this part. Uncompressed finished flooring 

greater than 1/8 inch in thickness shall not extend beneath load-bearing 

walls that are fastened to the floor structure.

    (b) Design loads--(1) Design dead loads. Design dead loads shall be 

the actual dead load supported by the structural assembly under 

consideration.

    (2) Design live loads. The design live loads and wind and snow loads 

shall be as specified in this section and shall be considered to be 

uniformly distributed. The roof live load or snow load shall not be 

considered as acting simultaneously with the wind load and the roof live 

or snow load and floor live loads shall not be considered as resisting 

the overturning moment due to wind.

    (3) When engineering calculations are performed, allowable unit 

stresses may be increased as provided in the documents referenced in 

Sec.  3280.304 except as otherwise indicated in Sec. Sec.  

3280.304(b)(1) and 3280.306(a).

    (4) Whenever the roof slope does not exceed 20 degrees, the design 

horizontal wind loads required by Sec.  3280.305(c)(1) may be determined 

without including the vertical roof projection of the manufactured home. 

However, regardless of the roof slope of the manufactured home, the 

vertical roof projection shall be included when determining the wind 

loading for split level or clerestory-type roof systems.

    (c) Wind, snow, and roof loads--(1) Wind loads--design requirements. 

(i) Standard wind loads (Zone I). When a manufactured home is not 

designed to resist the wind loads for high wind areas (Zone II or Zone 

III) specified in paragraph (c)(1)(ii) of this section, the manufactured 

home and each of its wind resisting parts and portions shall be designed 

for horizontal wind loads of not less than 15 psf and net uplift load of 

not less than 9 psf.

    (ii) Wind loads for high wind areas (Zone II and Zone III). When 

designed for high wind areas (Zone II and Zone III), the manufactured 

home, each of its wind resisting parts (including, but not limited to, 

shear walls, diaphragms, ridge beams, and their fastening and anchoring 

systems), and its components and cladding materials (including, but not 

limited to, roof trusses, wall studs, exterior sheathing, roofing and 

siding materials, exterior glazing, and their connections and fasteners) 

shall be designed by a Professional Engineer or Architect to resist:

    (A) The design wind loads for Exposure C specified in ANSI/ASCE 7-

88, ``Minimum Design Loads for Buildings and Other Structures,'' for a 

fifty-year recurrence interval, and a design wind speed of 100 mph, as 

specified for Wind



[[Page 128]]



Zone II, or 110 mph, as specified for Wind Zone III (Basic Wind Zone 

Map); or

    (B) The wind pressures specified in the following table:



                     Table of Design Wind Pressures

------------------------------------------------------------------------

                                           Wind zone II    Wind zone III

                 Element                    design wind     design wind

                                           speed 100 MPH   speed 110 MPH

------------------------------------------------------------------------

Anchorage for lateral and vertical

 stability (See Sec.   3280.306(a)):

    Net Horizontal Drag \1,2\:..........      \3\ 39 PSF   thn-eq>47 PSF

     \1,2\..............................

    Ridge beams and other Main Roof              -30 PSF         -36 PSF

     Support Beams (Beams supporting

     expanding room sections, etc.).....

Components and cladding:

    Roof trusses \4\ in all areas;           \5\ -39 PSF     \5\ -47 PSF

     trusses shall be doubled within

     3[foot]-0[foot] from each end of

     the roof...........................

    Exterior roof coverings, sheathing       \5\ -39 PSF     \5\ -47 PSF

     and fastenings \4\,\6\,\7\ in all

     areas except the following.........

        Within 3[foot]-0[foot] from each     \5\ -73 PSF     \5\ -89 PSF

         gable end (overhang at end

         wall) of the roof or endwall if

         no overhang is provided

         \4\,\6\,\7\....................

        Within 3[foot]-0[foot] from the      \5\ -51 PSF     \5\ -62 PSF

         ridge and eave (overhang at

         sidewall) or sidewall if no

         eave is provided \4\,\6\,\7\...

    Eaves (Overhangs at Sidewalls)           \5\ -51 PSF     \5\ -62 PSF

     \4\,\6\,\7\........................

    Gables (Overhangs at Endwalls)           \5\ -73 PSF     \5\ -89 PSF

     \4\,\6\,\7\........................

Wall studs in sidewalls and endwalls,

 exterior windows and sliding glass

 doors (glazing and framing), exterior

 coverings, sheathing and fastenings

 \8\:

        Within 3[foot]-0[foot] from each  48 PSF   thn-eq>58 PSF

         endwall........................

        All other areas.................  38 PSF  thn-eq>46 PSF

------------------------------------------------------------------------

NOTES:



\1\ The net horizontal drag of 39 PSF to be used

  in calculating Anchorage for Lateral and Vertical Stability and for

  the design of Main Wind Force Resisting Systems is based on a

  distribution of wind pressures of +0.8 or +24 PSF to the windward wall

  and -0.5 or -15 PSF to the leeward wall.

\2\ Horizontal drag pressures need not be applied to roof projections

  when the roof slope does not exceed 20 degrees.

\3\ + sign would mean pressures are acting towards or on the structure;

   sign means pressures are acting away from the structure; sign means forces can act in either direction, towards

  or away from the structure.

\4\ Design values in this ``Table'' are only applicable to roof slopes

  between 10 degrees (nominal 2/12 slope) and 30 degrees.

\5\ The design uplift pressures are the same whether they are applied

  normal to the surface of the roof or to the horizontal projection of

  the roof.

\6\ Shingle roof coverings that are secured with 6 fasteners per shingle

  through an underlayment which is cemented to a 3/8'' structural rated

  roof sheathing need not be evaluated for these design wind pressures.

\7\ Structural rated roof sheathing that is at least 3/8'' in thickness,

  installed with the long dimension perpendicular to roof framing

  supports, and secured with fasteners at 4'' on center within 3[foot]-

  0[foot] of each gable end or endwall if no overhang is provided and

  6'' on center in all other areas, need not be evaluated for these

  design wind pressures.

\8\ Exterior coverings that are secured at 6 o.c. to a 3/8 structural rated sheathing that is fastened to wall framing

  members at 6 on center need not be evaluated for these

  design wind pressures.



    (2) Wind loads--zone designations. The Wind Zone and specific wind 

design load requirements are determined by the fastest basic wind speed 

(mph) within each Zone and the intended location, based on the Basic 

Wind Zone Map, as follows:

    (i) Wind Zone I. Wind Zone I consists of those areas on the Basic 

Wind Zone Map that are not identified in paragraphs (c)(2)(ii) or (iii) 

of this section as being within Wind Zone II or III, respectively.

    (ii) Wind Zone II.....100 mph. The following areas are deemed to be 

within Wind Zone II of the Basic Wind Zone Map:

    Local governments: The following local governments listed by State 

(counties, unless specified otherwise):

    Alabama: Baldwin and Mobile.

    Florida: All counties except those identified in paragraph 

(c)(1)(i)(C) of this section as within Wind Zone III.

    Georgia: Bryan, Camden, Chatham, Glynn, Liberty, McIntosh.

    Louisiana: Parishes of Acadia, Allen, Ascension, Assumption, 

Calcasieu, Cameron, East Baton Rouge, East Feliciana, Evangeline, 

Iberia, Iberville, Jefferson Davis, LaFayette, Livingston, Pointe 

Coupee, St. Helena, St. James, St. John the Baptist, St. Landry, St. 

Martin, St. Tammany, Tangipahoa, Vermillion, Washington, West Baton 

Rouge, and West Feliciana.



[[Page 129]]



    Maine: Hancock and Washington.

    Massachusetts: Barnstable, Bristol, Dukes, Nantucket, and Plymouth.

    Mississippi: George, Hancock, Harrison, Jackson, Pearl River, and 

Stone.

    North Carolina: Beaufort, Brunswick, Camden, Chowan, Columbus, 

Craven, Currituck, Jones, New Hanover, Onslow, Pamlico, Pasquotank, 

Pender, Perquimans, Tyrrell, and Washington.

    South Carolina: Beaufort, Berkeley, Charleston, Colleton, 

Dorchester, Georgetown, Horry, Jasper, and Williamsburg.

    Texas: Aransas, Brazoria, Calhoun, Cameron, Chambers, Galveston, 

Jefferson, Kenedy, Kleberg, Matagorda, Nueces, Orange, Refugio, San 

Patricio, and Willacy.

    Virginia: Cities of Chesapeake, Norfolk, Portsmouth, Princess Anne, 

and Virginia Beach.

    (iii) Wind Zone III.....110 mph. The following areas are considered 

to be within Wind Zone III of the Basic Wind Zone Map:

    (A) States and Territories: The entire State of Hawaii, the coastal 

regions of Alaska (as determined by the 90 mph isotach on the ANSI/ASCE 

7-88 map), and all of the U.S. Territories of American Samoa, Guam, 

Northern Mariana Islands, Puerto Rico, Trust Territory of the Pacific 

Islands, and the United States Virgin Islands.

    (B) Local governments: The following local governments listed by 

State (counties, unless specified otherwise):

    Florida: Broward, Charlotte, Collier, Dade, Franklin, Gulf, Hendry, 

Lee, Martin, Manatee, Monroe, Palm Beach, Pinellas, and Sarasota.

    Louisiana: Parishes of Jefferson, La Fourche, Orleans, Plaquemines, 

St. Bernard, St. Charles, St. Mary, and Terrabonne.

    North Carolina: Carteret, Dare, and Hyde.

    (iv) Consideration of local requirements. For areas where local 

building code requirements exceed the design wind speed requirements of 

these standards, the Department will consider the adoption through 

rulemaking of the more stringent requirements of the State or local 

building authority.

    (3) Snow and roof loads. (i) Flat, curved and pitched roofs shall be 

designed to resist the following live loads, applied downward on the 

horizontal projection as appropriate for the design zone marked on the 

manufactured home:



------------------------------------------------------------------------

                                                                 Pounds

                                                                   per

            Zone (see Map in Sec.   3280.305(c)(4))              square

                                                                  foot

------------------------------------------------------------------------

North Zone....................................................        40

Middle Zone...................................................        30

South Zone....................................................        20

------------------------------------------------------------------------



    (ii) For exposures in areas (mountainous or other) where snow or 

wind records or experience indicate significant differences from the 

loads stated above, the Department may establish more stringent 

requirements for homes known to be destined for such areas. For snow 

loads, such requirements are to be based on a roof snow load of 0.6 of 

the ground snow load for areas exposed to wind and a roof snow load of 

0.8 of the ground snow load for sheltered areas.

    (iii) Eaves and cornices shall be designed for a net uplift pressure 

of 2.5 times the design uplift wind pressure cited in Sec.  

3280.305(c)(1)(i) for Wind Zone I, and for the design pressures cited in 

Sec.  3280.305(c)(1)(ii) for Wind Zones II and III.

    (4) Data plate requirements. The Data Plate posted in the 

manufactured home (see Sec.  3280.5) shall designate the wind and roof 

load zones or, if designed for higher loads, the actual design external 

snow and wind loads for which the home has been designed. The Data Plate 

shall include reproductions of the Load Zone Maps shown in this 

paragraph (c)(4), with any related information. The Load Zone Maps shall 

be not less than either 3\1/2\ in. by 2\1/4\ in., or one-half the size 

illustrated in the Code of Federal Regulations.



[[Page 130]]



[GRAPHIC] [TIFF OMITTED] TR14JA94.000





[[Page 131]]





[GRAPHIC] [TIFF OMITTED] TR20OC97.004



    (d) Design load deflection. (1) When a structural assembly is 

subjected to total design live loads, the deflection for structural 

framing members shall not exceed the following (where L equals the clear 

span between supports or two times the length of a cantilever):





[[Page 132]]





Floor--L/240

Roof and ceiling--L/180

Headers, beams, and girders (vertical load)--L/180

Walls and partitions--L/180



    (2) The allowable eave or cornice deflection for uplift is to be 

measured at the design uplift load of 9 psf for Wind Zone I, and at the 

design uplift pressure cited in paragraph (c)(1)(ii) of this section for 

Wind Zones II and III. The allowable deflection shall be (2xLc)/180, 

where Lc is the measured horizontal eave projection from the wall.

    (e) Fastening of structural systems. (1) Roof framing shall be 

securely fastened to wall framing, walls to floor structure, and floor 

structure to chassis to secure and maintain continuity between the floor 

and chassis, so as to resist wind overturning, uplift, and sliding as 

specified in this part.

    (2) For Wind Zones II and III, roof trusses shall be secured to 

exterior wall framing members (studs), and exterior wall framing members 

(studs) shall be secured to floor framing members, with 26 gage minimum 

steel strapping or brackets or by a combination of 26 gage minimum steel 

strapping or brackets and structural rated wall sheathing that overlaps 

the roof and floor. Steel strapping or brackets shall be installed at a 

maximum spacing of 24 on center in Wind Zone II and at a 

maximum of 16 on center in Wind Zone III. The number and type 

of fasteners used to secure the steel straps or brackets or structural 

sheathing shall be capable of transferring all uplift forces between 

elements being joined.

    (f) Walls. The walls shall be of sufficient strength to withstand 

the load requirements as defined in Sec.  3280.305(c) of this part, 

without exceeding the deflections as specified in Sec.  3280.305(d). The 

connections between the bearing walls, floor, and roof framework members 

shall be fabricated in such a manner as to provide support for the 

material used to enclose the manufactured home and to provide for 

transfer of all lateral and vertical loads to the floor and chassis.

    (1) Except where substantiated by engineering analysis or tests, 

studs shall not be notched or drilled in the middle one-third of their 

length.

    (2) Interior walls and partitions shall be constructed with 

structural capacity adequate for the intended purpose and shall be 

capable of resisting a horizontal load of not less than five pounds per 

square foot. An allowable stress increase of 1.33 times the permitted 

published design values may be used in the design of wood framed 

interior partitions. Finish of walls and partitions shall be securely 

fastened to wall framing.

    (g) Floors. (1) Floor assemblies shall be designed in accordance 

with accepted engineering practice standards to support a minimum 

uniform live load of 40 lb/ft \2\ plus the dead load of the materials. 

In addition (but not simultaneously), floors shall be able to support a 

200-pound concentrated load on a one-inch diameter disc at the most 

critical location with a maximum deflection not to exceed one-eighth 

inch relative to floor framing. Perimeter wood joists of more than six 

inches depth shall be stabilized against overturning from superimposed 

loads as follows: at ends by solid blocking not less than two-inch 

thickness by full depth of joist, or by connecting to a continuous 

header not less than two-inch thickness and not less than the depth of 

the joist with connecting devices; at eight-feet maximum intermediate 

spacing by solid blocking or by wood cross-bridging of not less than one 

inch by three inches, metal cross-bridging of equal strength, or by 

other approved methods.

    (2) Wood, wood fiber or plywood floors or subfloors in kitchens, 

bathrooms (including toilet compartments), laundry areas, water heater 

compartments, and any other areas subject to excessive moisture shall be 

moisture resistant or shall be made moisture resistant by sealing or by 

an overlay of nonabsorbent material applied with water-resistant 

adhesive. Use of one of the following methods would meet this 

requirement:

    (i) Sealing the floor with a water-resistant sealer; or

    (ii) Installing an overlay of a non-absorbent floor covering 

material applied with water-resistant adhesive; or

    (iii) Direct application of a water-resistant sealer to the exposed 

wood floor



[[Page 133]]



area when covered with a non-absorbent overlay; or

    (iv) The use of a non-absorbent floor covering which may be 

installed without a continuous application of a water-resistant adhesive 

or sealant when the floor covering meets the following criteria:

    (A) The covering is a continuous membrane with any seams or patches 

seam bonded or welded to preserve the continuity of the floor covering; 

and

    (B) The floor is protected at all penetrations in these areas by 

sealing with a compatible water-resistant adhesive or sealant to prevent 

moisture from migrating under the nonabsorbent floor covering; and

    (C) The covering is fastened around the perimeter of the subfloor in 

accordance with the floor covering manufacturer's instructions; and,

    (D) The covering is designed to be installed to prevent moisture 

penetration without the use of a water-resistant adhesive or sealer 

except as required in this paragraph (g). The vertical edges of 

penetrations for plumbing shall be covered with a moisture-resistant 

adhesive or sealant. The vertical penetrations located under the bottom 

plates of perimeter walls of rooms, areas, or compartments are not 

required to be sealed; this does not include walls or partitions within 

the rooms or areas.

    (3) Carpet or carpet pads shall not be installed under concealed 

spaces subject to excessive moisture, such as plumbing fixture spaces, 

floor areas under installed laundry equipment. Carpet may be installed 

in laundry space provided:

    (i) The appliances are not provided;

    (ii) The conditions of paragraph (g)(2) of this section are 

followed; and

    (iii) Instructions are provided to remove carpet when appliances are 

installed.

    (4) Except where substantiated by engineering analysis or tests:

    (i) Notches on the ends of joists shall not exceed one-fourth the 

joist depth.

    (ii) Holes bored in joists shall not be within 2 inches of the top 

or bottom of the joist, and the diameter of any such hole shall not 

exceed one-third the depth of the joist.

    (iii) Notches in the top or bottom of the joists shall not exceed 

one-sixth the depth and shall not be located in the middle third of the 

span.

    (5) Bottom board material (with or without patches) shall meet or 

exceed the level of 48 inch-pounds of puncture resistance as tested by 

the Beach Puncture Test in accordance with Standard Test Methods for 

Puncture and Stiffness of Paperboard, and Corrugated and Solid 

Fiberboard, ASTM D-781-1968 (73). The material shall be suitable for 

patches and the patch life shall be equivalent to the material life. 

Patch installation instruction shall be included in the manufactured 

home manufacturer's instructions.

    (h) Roofs. (1) Roofs shall be of sufficient strength to withstand 

the load requirements as defined in Sec.  3280.305 (b) and (c) without 

exceeding the deflections specified in Sec.  3280.305(d). The 

connections between roof framework members and bearing walls shall be 

fabricated in such a manner to provide for the transfer of design 

vertical and horizontal loads to the bearing walls and to resist uplift 

forces.

    (2) Roofing membranes shall be of sufficient rigidity to prevent 

deflection which would permit ponding of water or separation of seams 

due to wind, snow, ice, erection or transportation forces.

    (3) Cutting of roof framework members for passage of electrical, 

plumbing or mechanical systems shall not be allowed except where 

substantiated by engineering analysis.

    (4) All roof penetrations for electrical, plumbing or mechanical 

systems shall be properly flashed and sealed. In addition, where a metal 

roof membrane is penetrated, a wood backer shall be installed. The 

backer plate shall be not less than \5/16\ inch plywood, with exterior 

glues, secured to the roof framing system beneath the metal roof, and 

shall be of a size to assure that all screws securing the flashing are 

held by the backer plate.

    (i) Frame construction. The frame shall be capable of transmitting 

all design loads to stabilizing devices without exceeding the allowable 

load and deflections of this section. The frame shall also be capable of 

withstanding the effects of transportation shock and vibration without 

degradation as required by subpart J.



[[Page 134]]



    (1) Welded connections. (i) All welds shall be made in accordance 

with the applicable provisions of the Specification for Structural Steel 

Buildings, Allowable Stress Design and Plastic Design, AISC, June 1, 

1989. The Specification for the Design of Cold-Formed Steel Structural 

Members, AISI-1986 with 1989 addendum, and the Stainless Steel Cold-

Formed Structural Design Manual, AISI-1974.

    (ii) Regardless of the provisions of any reference standard 

contained in this subpart, deposits of weld slag or flux shall be 

required to be removed only from welded joints at the following 

locations:

    (A) Drawbar and coupling mechanisms;

    (B) Main member splices, and

    (C) Spring hanger to main member connections.

    (2) Protection of metal frames against corrosion. Metal frames shall 

be made corrosion resistant or protected against corrosion. Metal frames 

may be protected against corrosion by painting.



[40 FR 58752, Dec. 18, 1975. Redesignated at 44 FR 20679, Apr. 6, 1979, 

as amended at 44 FR 66195, Nov. 19, 1979; 52 FR 4582, Feb. 12, 1987; 58 

FR 55006, Oct. 25, 1993; 59 FR 2469, Jan. 14, 1994; 59 FR 15113, 15114, 

Mar. 31, 1994; 62 FR 54547, Oct. 20, 1997]



    Effective Date Note: At 70 FR 72043, Nov. 30, 2005, Sec.  3280.305 

was amended by adding paragraphs (c)(1)(iii), (c)(3)(i)(A) through (C) 

following the table in paragraph (c)(3)(i), and (c)(3)(iv); revising 

paragraph (e), redesignating paragraphs (g)(3) through (g)(5) as 

paragraphs (g)(4) through (g)(6), and adding new paragraph (g)(3); 

redesignating paragraphs (i)(1)(i), (i)(1)(ii), (i)(1)(ii)(A), 

(i)(1)(ii)(B) and (i)(1)(ii)(C) as paragraphs (j)(1), (j)(2), (j)(2)(i), 

(j)(2)(ii), and (j)(2)(iii), respectively; reserving vacated paragraph 

(i), and revising newly redesignated paragraph (j)(1), effective May 30, 

2006. For the convenience of the user the revised and added text 

follows:



Sec.  3280.305  Structural design requirements.



                                * * * * *



    (c) * * *

    (1) * * *

    (iii) One-piece metal roofing capable of resisting the design wind 

pressures for ``Components and Cladding: (Exterior roof coverings)'' in 

the Table for Design Wind Pressures in this section is allowed to be 

used without structural sheathing, provided the metal roofing is tested 

using procedures that have been approved by HUD and that meet all 

requirements of Sec. Sec.  3280.303(c) and (g) and 3280.401.



                                * * * * *



    (3) * * *

    (i) * * *

    (A) North Roof Load Zone. The following counties in each of the 

following states are deemed to be within the North Roof Load Zone:

    Maine--Aroostook, Piscataquis, Somerset, Penobscot, Waldo, Knox, 

Hancock, and Washington.



                          Alaska--All Counties



    (B) Middle Roof Load Zone. The following counties in each of the 

following states are deemed to be within the Middle Roof Load Zone:



----------------------------------------------------------------------------------------------------------------



----------------------------------------------------------------------------------------------------------------

             States                                                  Counties

----------------------------------------------------------------------------------------------------------------

South Dakota...................  Grant                Brookings           Hanson              Lincoln

                                 Codington            Miner               Minnehaha           Yankton

                                 Deuel                Lake                Hutchinson          Union

                                 Hamlin               Moody               Turner              Clay

                                 Kingsbury            McCook              ..................  ..................

Minnesota......................  Koochiching          Stearns             Renville            Sibley

                                 Itasca               Swift               McLeod              Nicollet

                                 Hubbard              Kandiyohi           Carver              Blue Earth

                                 Cass                 Meeker              Dakota              Martin

                                 Crow Wing            Wright              Goodhue             Watonwan

                                 Aitkin               Lac qui Parle       Wabasha             Brown

                                 St. Louis            Chippewa            Winona              Redwood

                                 Lake                 Yellow Medicine     Fillmore            Lyon

                                 Cook                 Mille Lacs          Mower               Lincoln

                                 Carlton              Kanabec             Olmsted             Pipestone

                                 Pine                 Benton              Dodge               Murray

                                 Wadena               Isanti              Rice                Cottonwood

                                 Todd                 Sherburne           Steele              Jackson

                                 Morrison             Anoka               Freeborn            Nobles

                                 Douglas              Chisapo             Faribault           Rock



[[Page 135]]





                                 Grant                Washington          Waseca              St. Croix

                                 Stevens              Hennepin            Le Sueur            ..................

                                 Pope                 Ramsey              Scott               ..................

Iowa...........................  Hanock               Mitchell            Hamilton            Buena Vista

                                 Lyon                 Howard              Webster             Cherokee

                                 Osceola              Chickasaw           Calhoun             Plymouth

                                 Dickinson            Butler              Sac                 Sioux

                                 Emmet                Floyd               Ida                 O'Brien

                                 Kossuth              Cerro Gordo         Humboldt            Clay

                                 Winnebago            Franklin            Pocahontas          Wright

                                 Worth                Hardin              Palo Alto           Crawford

Wisconsin......................  Douglas              Oconto              Pepin               Lincoln

                                 Bayfied              Menominee           Pierce              Oneida

                                 Ashland              Langlade            Dunn                Polk

                                 Iron                 Marathon            Eau Claire          Burnett

                                 Vilas                Clark               Chippewa            Washburn

                                 Forest               Jackson             Rusk                Sawyer

                                 Florence             Trempealeau         Barron              Price

                                 Marinette            Buffalo             Taylor              Doon

Michigan.......................  Houghton             Iron                Presque Isle        Wexford

                                 Baraga               Dickinson           Charlevoix          Benzie

                                 Marquette            Menominee           Montmorency         Grand Traverse

                                 Alger                Delta               Alpena              Kalkaska

                                 Luce                 Schoolcraft         Alcona              Oscoda

                                 Chippewa             Mackinaw            Ogemaw              Otsego

                                 Keweenaw             Cheyboygan          Roscommon           Leelanau

                                 Ontonagon            Emmet               Missaukee           Antrim

                                 Gogebic              ..................  ..................  ..................

New York.......................  St. Lawrence         Herkimer            Onondage            Genesee

                                 Franklin             Lewis               Madison             Orleans

                                 Clinton              Oswego              Cayuga              Niagara

                                 Essex                Jefferson           Seneca              Erie

                                 Hamilton             Oneida              Wayne               Wyoming

                                 Warren               Fulton              Ontario             Monroe

                                 Saratoga             Montgomery          Yates               ..................

                                 Washington           Schenectady         Livingston          ..................

Massachusetts..................  Essex                ..................  ..................  ..................

Maine..........................  Franklin             Kennebec            Lincoln             Cumberland

                                 Oxford               Androscoggin        Sagadahoc           York

Montana........................  All Counties         ..................  ..................  ..................

Idaho..........................  All Counties         ..................  ..................  ..................

Colorado.......................  All Counties         ..................  ..................  ..................

Wyoming........................  All Counties         ..................  ..................  ..................

Utah...........................  All Counties         ..................  ..................  ..................

Vermont........................  Franklin             Orleans             Caledonia           Addison

                                 Grand Isle           Essex               Washington          Rutland

                                 Lamoille             Chittendon          Orange              Windsor

New Hampshire..................  Coos                 Belknap             Sullivan            Hillsborough

                                 Grafton              Strafford           Rockingham          Cheshire

                                 Carroll              Merrimack           ..................  ..................

----------------------------------------------------------------------------------------------------------------



    (C) South Roof Load Zone. The states and counties that are not 

listed for the North Roof Load Zone in paragraph (c)(3)(i)(A) of this 

section, or the Middle Roof Load Zone in paragraph (c)(3)(i)(B) of this 

section, are deemed to be within the South Roof Load Zone.



                                * * * * *



    (iv) Skylights must be capable of withstanding roof loads as 

specified in paragraphs (c)(3)(i) or (c)(3)(ii) of this section. 

Skylights must be listed and tested in accordance with AAMA 1600/I.S.7-

00, 2003, Voluntary Specification for Skylights.



                                * * * * *



    (e) Fastening of structural systems. (1) Roof framing must be 

securely fastened to wall framing, walls to floor structure, and floor 

structure to chassis, to secure and maintain continuity between the 

floor and chassis in order to resist wind overturning, uplift, and 

sliding, and to provide continuous load paths for these forces to the 

foundation or anchorage system. The number and type of fasteners used 

must be capable of transferring all forces between elements being 

joined.



[[Page 136]]



    (2) For Wind Zone II and Wind Zone III, roof framing members must be 

securely fastened at the vertical bearing points to resist design 

overturning, uplift, and sliding forces. When engineered connectors are 

not installed, roof framing members must be secured at the vertical 

bearing points to wall framing members (studs), and wall framing members 

(studs) must be secured to floor framing members, with 0.016 inch base 

metal, minimum steel strapping or engineered connectors, or by a 

combination of 0.016 inch base metal, minimum steel strapping or 

engineered connectors, and structural-rated wall sheathing that overlaps 

the roof and floor system if substantiated by structural analysis or by 

suitable load tests. Steel strapping or engineered connectors are to be 

installed at a maximum spacing of 24 inches on center in Wind Zone II, 

and 16 inches on center in Wind Zone III. Exception: Where substantiated 

by structural analysis or suitable load tests, the 0.016 inch base metal 

minimum steel strapping or engineered connectors may be omitted at the 

roof to wall and/or wall to floor connections, when structural rated 

sheathing that overlaps the roof and wall and/or wall and floor is 

capable of resisting the applicable design wind loads.



                                * * * * *



    (g) * * *

    (3) Wood panel products used as floor or subfloor materials on the 

exterior of the home, such as in recessed entryways, must be rated for 

exterior exposure and protected from moisture by sealing or applying 

nonabsorbent overlay with water resistant adhesive.



                                * * * * *



    (j) Welded connections. (1) All welds must be made in accordance 

with the applicable provisions of the Specification for Structural Steel 

Buildings, Allowable Stress Design and Plastic Design, AISC-S335, 1989; 

the Specification for the Design of Cold-Formed Steel Structural 

Members, AISI, 1996; and the Specification for the Design of Cold-Formed 

Stainless Steel Structural Members, SEI/ASCE 8-02, 2002.



                                * * * * *