[Code of Federal Regulations]

[Title 24, Volume 5]

[Revised as of April 1, 2006]

From the U.S. Government Printing Office via GPO Access

[CITE: 24CFR3280.715]



[Page 195-198]

 

                 TITLE 24--HOUSING AND URBAN DEVELOPMENT

 

 CHAPTER XX--OFFICE OF ASSISTANT SECRETARY FOR HOUSING--FEDERAL HOUSING 

        COMMISSIONER, DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT

 

PART 3280_MANUFACTURED HOME CONSTRUCTION AND SAFETY STANDARDS--Table 

of Contents

 

           Subpart H_Heating, Cooling and Fuel Burning Systems

 

Sec.  3280.715  Circulating air systems.



    (a) Supply system. (1) Supply ducts and any dampers contained 

therein shall be made from galvanized steel, tin-plated steel, or 

aluminum, or shall be listed Class 0, Class 1, or Class 2 air ducts. 

Class 2 air ducts shall be located at least 3 feet from the furnace 

bonnet or plenum. A duct system integral with the structure shall be of 

durable construction that can be demonstrated to be equally resistant to 

fire and deterioration. Ducts constructed from sheet metal shall be in 

accordance with the following table:



                  Minimum Metal Thickness for Ducts \1\

------------------------------------------------------------------------

                                                     Diameter    Width

                     Duct type                      14 in. or   over 14

                                                       less       in.

------------------------------------------------------------------------

Round.............................................      0.013      0.016

Enclosed rectangular..............................       .013       .016

Exposed rectangular...............................       .016       .019

------------------------------------------------------------------------

\1\ When ``nominal'' thicknesses are specified, 0.003 in. shall be added

  to these ``minimum'' metal thicknesses.



    (2) Sizing of ducts for heating. (i) Ducts shall be so designed that 

when a labeled forced-air furnace is installed and operated continuously 

at its normal heating air circulating rate in the manufactured home, 

with all registers in the full open position, the static pressure 

measured in the casing shall not exceed 90% of that shown on the label 

of the appliance. For upflow furnaces the static pressure shall be taken



[[Page 196]]



in the duct plenum. For external heating or combination heating/cooling 

appliances the static pressure shall be taken at the point used by the 

agency listing or certifying the appliance.

    (ii) When an evaporator-coil specifically designed for the 

particular furnace is installed between the furnace and the duct plenum, 

the total static pressure shall be measured downstream of the coil in 

accordance with the appliance label and shall not exceed 90 percent of 

that shown on the label of the appliance.

    (iii) When any other listed air-cooler coil is installed between the 

furnace and the duct plenum, the total static pressure shall be measured 

between the furnace and the coil and it shall not exceed 90 percent of 

that shown on the label of the furnace.

    (iv) The minimum dimension of any branch duct shall be at least 1\1/

2\ inches, and of any main duct, 2\1/2\ inches.

    (3) Sizing of ducts. (i) The manufactured home manufacturer shall 

certify the capacity of the air cooling supply duct system for the 

maximum allowable output of ARI certified central air conditioning 

systems. The certification shall be at operating static pressure of 0.3 

inches of water or greater. (See Sec.  3280.511).

    (ii) The refrigerated air cooling supply duct system including 

registers must be capable of handling at least 300 cfm per 10,000 btuh 

with a static pressure no greater than 0.3 inches of water when measured 

at room temperature. In the case of application of external self 

contained comfort cooling appliances or the cooling mode of combination 

heating/cooling appliances, either the external ducts between the 

appliance and the manufactured home supply system shall be considered 

part of, and shall comply with the requirements for the refrigerated air 

cooling supply duct system, or the connecting duct between the external 

appliance and the mobile supply duct system shall be a part of the 

listed appliance. The minimum dimension of any branch duct shall be at 

least 1\1/2\ inches, and of any main duct, 2\1/2\ inches.

    (4) Airtightness of supply duct systems. A supply duct system shall 

be considered substantially airtight when the static pressure in the 

duct system, with all registers sealed and with the furnace air 

circulator at high speed, is at least 80 percent of the static pressure 

measured in the furnace casing, with its outlets sealed and the furnace 

air circulator operating at high speed. For the purpose of this 

paragraph and Sec.  3280.715(b) pressures shall be measured with a water 

manometer or equivalent device calibrated to read in increments not 

greater than \1/10\ inch water column.

    (5) Expandable or multiple manufactured home connections. (i) An 

expandable or multiple manufactured home may have ducts of the heating 

system installed in the various units. The points of connection must be 

so designed and constructed that when the manufactured home is fully 

expanded or coupled, the resulting duct joint will conform to the 

requirements of this part.

    (ii) Installation instructions for supporting the crossover duct 

from the manufactured home shall be provided for onsite installation. 

The duct shall not be in contact with the ground.

    (6) Air supply ducts shall be insulated with material having an 

effective thermal resistance (R) of not less than 4.0 unless they are 

within manufactured home insulation having a minimum effective value of 

R-4.0 for floors or R-6.0 for ceilings.

    (7) Supply and return ducts exposed directly to outside air, such as 

under chassis crossover ducts or ducts connecting external heating, 

cooling or combination heating/cooling appliances shall be insulated 

with material having a minimum thermal resistance of R=4.0, with a 

continuous vapor barrier having a perm rating of not more than 1 perm. 

Where exposed underneath the manufactured home, all such ducts shall 

comply with Sec.  3280.715(a)(5)(ii).

    (b) Return air systems--(1) Return air openings. Provisions shall be 

made to permit the return of circulating air from all rooms and living 

spaces, except toilet room(s), to the circulating air supply inlet of 

the furnace.

    (2) Duct material. Return ducts and any diverting dampers contained 

therein shall be in accordance with the following:

    (i) Portions of return ducts directly above the heating surfaces, or 

closer



[[Page 197]]



than 2 feet from the outer jacket or casing of the furnace shall be 

constructed of metal in accordance with Sec.  3280.715(a)(1) or shall be 

listed Class 0 or Class 1 air ducts.

    (ii) Return ducts, except as required by paragraph (a) of this 

section, shall be constructed of one-inch (nominal) wood boards (flame 

spread classification of not more than 200), other suitable material no 

more flammable than one-inch board or in accordance with Sec.  

3280.715(a)(1).

    (iii) The interior of combustible ducts shall be lined with 

noncombustible material at points where there might be danger from 

incandescent particles dropped through the register or furnace such as 

directly under floor registers and the bottom return.

    (iv) Factory made air ducts used for connecting external heating, 

cooling or combination heating/cooling appliances to the supply system 

and return air system of a manufactured home shall be listed by a 

nationally recognized testing agency. Ducts applied to external heating 

appliances or combination heating/cooling appliances supply system 

outlets shall be constructed of metal in accordance with Sec.  

3280.715(a)(1) or shall be listed Class 0 or Class 1 air ducts for those 

portions of the duct closer than 2 feet from the outer casing of the 

appliance.

    (v) Ducts applied to external appliances shall be resistant to 

deteriorating environmental effects, including but not limited to 

ultraviolet rays, cold weather, or moisture and shall be resistant to 

insects and rodents.

    (3) Sizing. The cross-sectional areas of the return air duct shall 

not be less than 2 square inches for each 1,000 Btu per hour input 

rating of the appliance. Dampers shall not be placed in a combination 

fresh air intake and return air duct so arranged that the required 

cross-sectional area will not be reduced at all possible positions of 

the damper.

    (4) Permanent uncloseable openings. Living areas not served by 

return air ducts or closed off from the return opening of the furnace by 

doors, sliding partitions, or other means shall be provided with 

permanent uncloseable openings in the doors or separating partitions to 

allow circulated air to return to the furnace. Such openings may be 

grilled or louvered. The net free area of each opening shall be not less 

than 1 square inch for every 5 square feet of total living area closed 

off from the furnace by the door or partition serviced by that opening. 

Undercutting doors connecting the closed-off space may be used as a 

means of providing return air area. However, in the event that doors are 

undercut, they shall be undercut a minimum of 2 inches and not more than 

2\1/2\ inches, as measured from the top surface of the floor decking to 

the bottom of the door and no more than one half of the free air area so 

provided shall be counted as return air area.

    (c) Joints and seams. Joints and seams of ducts shall be securely 

fastened and made substantially airtight. Slip joints shall have a lap 

of at least 1 inch and shall be individually fastened. Tape or caulking 

compound may be used for sealing mechanically secure joints. Where used, 

tape or caulking compound shall not be subject to deterioration under 

long exposures to temperatures up to 200[deg] F. and to conditions of 

high humidity, excessive moisture, or mildew.

    (d) Supports. Ducts shall be securely supported.

    (e) Registers or grilles. Fittings connecting the registers or 

grilles to the duct system shall be constructed of metal or material 

which complies with the requirements of Class 1 or 2 ducts under UL 

181--Sixth Edition--1984, Factory Made Air Ducts and Connectors. Air 

supply terminal devices (registers) when installed in kitchens, 

bedrooms, and bathrooms shall be equipped with adjustable closeable 

dampers. Registers or grilles shall be constructed of metal or conform 

with the following:

    (1) Be made of a material classified 94V-0 or 94V-1 when tested as 

described in Underwriters' Laboratories, Inc., Tests for Flammability of 

Plastic Materials for Parts in Devices and Appliances, UL 94-Fourth 

Edition-1991.

    (2) Floor registers or grilles shall resist without structural 

failure a 200 lb. concentrated load on a 2-inch diameter disc applied to 

the most critical area of the exposed face of the register or grille. 

For this test the register or grille is to be at a temperature of not



[[Page 198]]



less than 165[deg] F and is to be supported in accordance with the 

manufacturer's instructions.



[40 FR 58752, Dec. 18, 1975. Redesignated at 44 FR 20679, Apr. 6, 1979, 

as amended at 52 FR 4589, Feb. 12, 1987; 58 FR 55019, Oct. 25, 1993]



    Effective Date Note: At 70 FR 72051, Nov. 30, 2005, Sec.  3280.715 

was amended by revising paragraph (c), the introductory text of 

paragraph (e), and paragraph (e)(1), effective May 30, 2006. For the 

convenience of the user the revised text follows:



Sec.  3280.715  Circulating air systems.



                                * * * * *



    (c) Joints and seams. Joints and seams of sheet metal and factory-

made flexible ducts, including trunks, branches, risers, crossover 

ducts, and crossover duct plenums, shall be mechanically secured and 

made substantially airtight. Slip joints in sheet metal ducts shall have 

a lap of at least one inch and shall be mechanically fastened. Tapes or 

caulking compounds shall be permitted to be used for sealing 

mechanically secure joints. Sealants and tapes shall be applied only to 

surfaces that are dry and dust-, dirt-, oil-, and grease-free. Tapes and 

mastic closure systems for use with factory-made rigid fiberglass air 

ducts and air connectors shall be listed in accordance with UL Standard 

181A-1994, with 1998 revisions. Tapes and mastic closure systems used 

with factory-made flexible air ducts and air connectors shall be listed 

in accordance with UL Standard 181B-1995, with 1998 revisions.



                                * * * * *



    (e) Registers and grilles. Fittings connecting the registers and 

grilles to the duct system must be constructed of metal or material that 

complies with the requirements of Class 1 or 2 ducts under UL 181-1996 

with 1998 revisions, Factory Made Air Ducts and Connectors. Air supply 

terminal devices (registers) when installed in kitchen, bedrooms, and 

bathrooms must be equipped with adjustable closeable dampers. Registers 

or grilles must be constructed of metal or conform with the following:

    (1) Be made of a material classified 94V-0 or 94V-1, when tested as 

described in UL 94-1996, with 2001 revisions, Test for Flammability of 

Plastic Materials for Parts in Devices and Appliances, Fifth Edition; 

and



                                * * * * *