Sec. 431.106  Uniform test method for the measurement of energy 
efficiency of commercial water heaters and hot water supply boilers 
(other than commercial heat pump water heaters).

    (a) Scope. This section covers the test procedures you must follow 
if, pursuant to EPCA, you are measuring the thermal efficiency or 
standby loss, or both, of a storage or instantaneous water heater or hot 
water supply boiler (other than a commercial heat pump water heater).
    (b) Testing and Calculations. Determine the energy efficiency of 
each covered product by conducting the test procedure(s), set forth in 
the two rightmost columns of the following table, that apply to the 
energy efficiency descriptor(s) for that product:

[[Page 429]]



----------------------------------------------------------------------------------------------------------------
                                                                 Use test setup,
                                                                  equipment and
              Product                   Energy efficiency         procedures in         With these additional
                                           descriptor          subsection labeled            stipulations
                                                              ``Method of Test'' of
----------------------------------------------------------------------------------------------------------------
Gas-fired Storage and Instantaneous  Thermal Efficiency....  ANSI Z21.10.3-1998,     A. For all products, the
 Water Heaters and Hot Water Supply                           Sec. 2.9**.           duration of the standby
 Boilers*.                                                                            loss test shall be until
                                                                                      whichever of the following
                                                                                      occurs first after you
                                                                                      begin to measure the fuel
                                                                                      and/or electric
                                                                                      consumption: (1) The first
                                                                                      cutout after 24 hours or
                                                                                      (2) 48 hours, if the water
                                                                                      heater is not in the
                                                                                      heating mode at that time.
                                     Standby Loss..........  ANSI Z21.10.3-1998,     B. For oil and gas
                                                              Sec. 2.10**.          products, the standby loss
                                                                                      in Btu per hour must be
                                                                                      calculated as follows: SL
                                                                                      (Btu per hour) = S (% per
                                                                                      hour) x 8.25 (Btu/gal-F) x
                                                                                      Measured Volume (gal) x 70
                                                                                      (degrees F).
                                                                                     C. For oil-fired products,
                                                                                      apply the following in
                                                                                      conducting the thermal
                                                                                      efficiency and standby
                                                                                      loss tests:
                                                                                     (1) Venting Requirements--
                                                                                      Connect a vertical length
                                                                                      of flue pipe to the flue
                                                                                      gas outlet of sufficient
                                                                                      height so as to meet the
                                                                                      minimum draft specified by
                                                                                      the manufacturer.
Oil-fired Storage and Instantaneous  Thermal Efficiency....  ANSI Z21.10.3-1998,     (2) Oil Supply--Adjust the
 Water Heaters and Hot Water Supply                           Sec. 2.9**.           burner rate so that: (a)
 Boilers*.                                                                            The hourly Btu input rate
                                                                                      lies within 2 percent of the
                                                                                      manufacturer's specified
                                                                                      input rate, (b) the CO2
                                                                                      reading shows the value
                                                                                      specified by the
                                                                                      manufacturer, (c) smoke in
                                                                                      the flue does not exceed
                                                                                      No. 1 smoke as measured by
                                                                                      the procedure in ASTM-D-
                                                                                      2156-80, and (d) fuel pump
                                                                                      pressure lies within 10 percent of
                                                                                      manufacturer's
                                                                                      specifications.
                                     Standby Loss..........  ANSI Z21.10.3-1998,     D. For electric products,
                                                              Sec. 2.10**.          apply the following in
                                                                                      conducting the standby
                                                                                      loss test:
                                                                                     (1) Assume that the thermal
                                                                                      efficiency (Et) of
                                                                                      electric water heaters
                                                                                      with immersed heating
                                                                                      elements is 98 percent.
                                                                                     (2) Maintain the electrical
                                                                                      supply voltage to within
                                                                                      5
                                                                                      percent of the center of
                                                                                      the voltage range
                                                                                      specified on the water
                                                                                      heater nameplate.
Electric Storage and Instantaneous   Standby Loss..........  ANSI Z21.10.3-1998,     (3) If the set up includes
 Water Heaters.                                               Sec. 2.10**.          multiple adjustable
                                                                                      thermostats, set the
                                                                                      highest one first to yield
                                                                                      a maximum water
                                                                                      temperature in the
                                                                                      specified range as
                                                                                      measured by the topmost
                                                                                      tank thermocouple. Then
                                                                                      set the lower
                                                                                      thermostat(s) to yield a
                                                                                      maximum mean tank
                                                                                      temperature within the
                                                                                      specified range.
----------------------------------------------------------------------------------------------------------------
*As to hot water supply boilers with a capacity of less than 10 gallons, these test methods become mandatory on
  October 21, 2005. Prior to that time, you may use for these products either (1) these test methods if you rate
  the product for thermal efficiency, or (2) the test methods in Subpart E if you rate the product for
  combustion efficiency as a commercial packaged boiler.
**Incorporated by reference, see Sec. 431.105.