Sec. 431.87  Energy conservation standards and their effective dates.

    Each manufacturer of a commercial packaged boiler manufactured on or 
after January 1, 1994, must meet the following energy efficiency 
standard levels:
    (a) For a gas-fired packaged boiler with a capacity (rated maximum 
input) of 300,000 Btu/hr or more, the combustion efficiency at the 
maximum rated capacity must be not less than 80 percent.
    (b) For an oil-fired packaged boiler with a capacity (rated maximum 
input) of 300,000 Btu/hr or more, the combustion efficiency at the 
maximum rated capacity must be not less than 83 percent.