                            TITLE 10--ENERGY
 
                    CHAPTER II--DEPARTMENT OF ENERGY
 
PART 431_ENERGY EFFICIENCY PROGRAM FOR CERTAIN COMMERCIAL AND INDUSTRIAL 
EQUIPMENT--Table of Contents
 
          Subpart F_Commercial Air Conditioners and Heat Pumps
 
Sec. 431.96  Uniform test method for the measurement of energy efficiency 
of small and large commercial package air conditioning and heating 
equipment, packaged terminal air conditioners, and packaged terminal heat 
pumps.

    (a) Scope. This section contains test procedures you must follow if, 
pursuant to EPCA, you are measuring the energy efficiency of any small 
or large commercial package air-conditioning

[[Page 423]]

and heating equipment, packaged terminal air conditioner or packaged 
terminal heat pump.
    (b) Testing and Calculations. Determine the energy efficiency of 
each covered product by conducting the test procedure(s) listed in the 
rightmost column of Table 1 of this section or the two rightmost columns 
of Table 2 of this section, that apply to the energy efficiency 
descriptor for that product, category, and cooling capacity.

   Table 1 to Sec. 431.96--Test Procedures for Certain Small Commercial Package Air Conditioning and Heating
 Equipment (All Water-Source Equipment and Other Equipment Less Than 65,000 Btu/h), for Large Commercial Package
  Air Conditioning and Heating Equipment and for Packaged Terminal Air Conditioners and Packaged Terminal Heat
                                                      Pumps
----------------------------------------------------------------------------------------------------------------
                                                                                                  Use tests,
             Product                   Category        Cooling capacity    Energy efficiency    conditions and
                                                                              descriptor       procedures \1\ in
----------------------------------------------------------------------------------------------------------------
Small Commercial Packaged Air     Air Cooled, 3       <65,000 Btu/h.....  SEER..............  ARI Standard 210/
 Conditioning and Heating          Phase, AC and HP                                            240-2003
 Equipment
                                                                         ---------------------------------------
                                                                          HSPF..............  ARI Standard 210/
                                                                                               240-2003
                                 -------------------------------------------------------------------------------
                                  Water Cooled and    <65,000 Btu/h.....  EER...............  ARI Standard 210/
                                   Evaporatively                                               240-2003
                                   Cooled AC
                                 -------------------------------------------------------------------------------
                                  Water-Source HP...  <135,000 Btu/h....  EER...............  ISO Standard 13256-
                                                                                               1 (1998)
                                                                         ---------------------------------------
                                                                          COP...............  ISO Standard 13256-
                                                                                               1 (1998)
----------------------------------------------------------------------------------------------------------------
Large Commercial Packaged Air     Air Cooled AC and   =135,00  EER...............  ARI Standard 340/
 Conditioning and Heating          HP.                 0 Btu/h and                             360-2000
 Equipment                                             <240,000 Btu/h.
                                                                         ---------------------------------------
                                                                          COP...............  ARI Standard 340/
                                                                                               360-2000
                                 -------------------------------------------------------------------------------
                                  Water Cooled AC...  =135,00  EER...............  ARI Standard 340/
                                                       0 Btu/h and                             360-2000
                                                       <240,000 Btu/h.
                                 -------------------------------------------------------------------------------
                                  Evaporatively       =135,00  EER...............  ARI Standard 340/
                                   Cooled AC.          0 Btu/h and                             360-2000
                                                       <240,000 Btu/h.
----------------------------------------------------------------------------------------------------------------
Packaged Terminal Air             AC and HP.........  All...............  EER...............  ARI Standard 310/
 Conditioners and Heat Pumps                                                                   380-2004
                                 -------------------------------------------------------------------------------
                                  HP................  All...............  COP...............  ARI Standard 310/
                                                                                               380-2004
----------------------------------------------------------------------------------------------------------------
\1\ Incorporated by reference, see Sec. 431.95.


  Table 2 to Sec. 431.96--Test Procedures for Small Commercial Package Air Conditioning and Heating Equipment
                 =65,000 Btu/h and <135,000 Btu/h (Other Than Water-Source Equipment)
----------------------------------------------------------------------------------------------------------------
                                            Energy
                Category                  efficiency   Use tests, conditions and       With these additional
                                          descriptor       procedures \1\ in             stipulations \2\
----------------------------------------------------------------------------------------------------------------
Air Cooled AC and HP...................          EER   ARI Standard 340/360-2000  1. Models with a desuperheater/
                                                    COP                            water heating device:
                                                                                   Establish Standard Ratings of
                                                                                   units equipped with a
                                                                                   refrigerant-to-water heat
                                                                                   exchanger to heat domestic
                                                                                   water (i.e., a
                                                                                   desuperheater), with the
                                                                                   desuperheater not in
                                                                                   operation.

[[Page 424]]


                                         ............                             2. Models Manufactured Without
                                                                                   Indoor Air- Circulating Fans:
                                                                                   (a) Establish Standard
                                                                                   Ratings of units which do not
                                                                                   have indoor air circulating
                                                                                   fans furnished as part of the
                                                                                   model, i.e., split systems
                                                                                   with indoor coil alone, by
                                                                                   subtracting from the total
                                                                                   cooling capacity 1,250 Btu/h
                                                                                   per 1,000 cfm [775 W/m\3\/s],
                                                                                   and by adding the same amount
                                                                                   to the heating capacity.
                                                                                   Increase total power input
                                                                                   for both heating and cooling
                                                                                   by 365 W per 1,000 cfm [226 W/
                                                                                   m\3\/s] of indoor air
                                                                                   circulated.
                                         ............                             (b) Equipment which does not
                                                                                   incorporate an indoor fan,
                                                                                   but is rated in combination
                                                                                   with a device employing a
                                                                                   fan, shall be rated as
                                                                                   described in 6.1.3.2a of 340/
                                                                                   360-2000. For equipment of
                                                                                   this class which is rated for
                                                                                   general use to be applied to
                                                                                   a variety of heating units,
                                                                                   the indoor-coil airflow rate
                                                                                   shall be (1) specified by the
                                                                                   manufacturer in Standard
                                                                                   Ratings, not to exceed 37.5
                                                                                   SCFM/1,000 Btu/h [0.06 m\3\/s
                                                                                   per 1,000 W] of rated
                                                                                   capacity, or (2) the airflow
                                                                                   rate obtained through the
                                                                                   indoor coil assembly when the
                                                                                   pressure drop across the
                                                                                   indoor coil assembly and the
                                                                                   recommended enclosures and
                                                                                   attachment means is not
                                                                                   greater than 0.30 inch of
                                                                                   water [75 Pa], whichever is
                                                                                   less.
Water Cooled AC........................          EER   ARI Standard 340/360-2000  3. Models with Indoor Fans,
                                                                                   Not Made for Use With Field
                                                                                   Installed Duct Systems: (a)
                                                                                   Equipment with indoor fans
                                                                                   not made for use with field
                                                                                   installed duct systems (free
                                                                                   discharge) shall be rated at
                                                                                   the indoor-coil airflow rate
                                                                                   delivered when operating at 0
                                                                                   inches of water [0 Pa]
                                                                                   external pressure as
                                                                                   specified by the
                                                                                   manufacturer.
                                                                                   (b) Test indoor air-moving
                                                                                   equipment not intended for
                                                                                   use with field installed duct
                                                                                   systems (free discharge) at 0
                                                                                   inches of water [0 Pa]
                                                                                   external pressure.
Evaporately Cooled AC..................          EER   ARI Standard 340/360-2000  4. Water cooled models: For
                                                                                   Standard Ratings of water-
                                                                                   cooled units add a total
                                                                                   allowance for cooling tower
                                                                                   fan motor and circulating
                                                                                   water pump motor power inputs
                                                                                   in the amount of 10.0 W per
                                                                                   1,000 Btu/h [34.1 W per 1,000
                                                                                   W] cooling capacity.
----------------------------------------------------------------------------------------------------------------
\1\ Incorporated by reference, see Sec. 431.95.
\2\ The content of stipulations 1, 2(a), 2(b), 3(a), 3(b), and 4 is taken from Sections 2.2.5, 6.1, 6.1.3.3 (c),
  6.1.3.3 (b), 6.1.3.6, and 6.1, respectively, of ARI Standard 210/240-2003.

                       Energy Efficiency Standards