[Code of Federal Regulations]

[Title 7, Volume 11]

[Revised as of January 1, 2006]

From the U.S. Government Printing Office via GPO Access

[CITE: 7CFR1755.200]



[Page 458-486]

 

                          TITLE 7--AGRICULTURE

 

    CHAPTER XVII--RURAL UTILITIES SERVICE, DEPARTMENT OF AGRICULTURE

 

PART 1755_TELECOMMUNICATIONS STANDARDS AND SPECIFICATIONS FOR MATERIALS, 

EQUIPMENT AND CONSTRUCTION--Table of Contents

 

Sec. 1755.200  RUS standard for splicing copper and fiber optic cables.



    (a) Scope. (1) This section describes approved methods for splicing 

plastic insulated copper and fiber optic cables. Typical applications of 

these methods include aerial, buried, and underground splices.

    (2) American National Standard Institute/National Fire Protection 

Association (ANSI/NFPA) 70, 1993 National Electrical Code (NEC) 

referenced in this section is incorporated by reference by RUS. This 

incorporation by reference was approved by the Director of the Federal 

Register in accordance with 5 U.S.C. 552(a) and 1 CFR part 51. A copy of 

the ANSI/NFPA 1993 NEC standard is available for inspection during 

normal business hours at RUS, room 2845, U.S. Department of Agriculture, 

Washington, DC 20250-1500, or at the National Archives and Records 

Administration (NARA). For information on the availability of this 

material at NARA, call 202-741-6030, or go to: http://www.archives.gov/

federal--register/code--of--federal--regulations/ibr--locations.html. 

Copies are available from NFPA, Batterymarch Park, Quincy, Massachusetts 

02269, telephone number 1 (800) 344-3555.

    (3) American National Standard Institute/Institute of Electrical and 

Electronics Engineers, Inc. (ANSI/IEEE), 1993 National Electrical Safety 

Code (NESC) referenced in this section is incorporated by reference by 

RUS. This incorporation by reference was approved by the Director of the 

Federal Register in accordance with 5 U.S.C. 552(a) and 1 CFR part 51. A 

copy of the ANSI/IEEE 1993 NESC standard is available for inspection 

during normal business hours at RUS, room 2845, U.S. Department of 

Agriculture, Washington, DC 20250-1500, or at the National Archives and 

Records Administration (NARA). For information on the availability of 

this material at NARA, call 202-741-6030, or go to: http://

www.archives.gov/federal--register/code--of--federal--regulations/ibr--

locations.html. Copies are available from IEEE Service Center, 455 Hoes 

Lane, Piscataway, New Jersey 08854, telephone number 1 (800) 678-4333.

    (b) General. (1) Only Rural Utilities Service (RUS) accepted filled 

cable and splicing materials shall be used on outside plant projects 

financed by RUS.



[[Page 459]]



    (2) The installation instructions provided by the manufacturer of 

splicing materials shall be followed except where those instructions 

conflict with the procedures specified in this section.

    (3) Precautions shall be taken to prevent the ingress of moisture 

and other contaminants during all phases of the splicing installation. 

When an uncompleted splice must be left unattended, it shall be sealed 

to prevent the ingress of moisture and other contaminants.

    (4) Minor sheath damage during construction may be repaired if the 

repair is completed immediately and approved by the borrower's resident 

project representative. Minor damage is typically repaired by:

    (i) Scuffing the cable sheath associated with the damaged area;

    (ii) Applying several layers of DR tape over the scuffed and damaged 

area;

    (iii) Applying several layers of plastic tape over the DR tape; and

    (iv) If damage is severe enough to rupture the cable shield, a 

splice closure shall be installed.

    (5) All splice cases installed on RUS toll trunk and feeder cables 

shall be filled, whether aerial, buried, or underground.

    (c) Splicing considerations for copper cables--(1) Preconstruction 

testing. It is desirable that each reel of cable be tested for grounds, 

opens, shorts, crosses, and shield continuity before the cable is 

installed. However, manufacturer supplied test results are acceptable. 

All cable pairs shall be free from electrical defects.

    (2) Handling precautions. The cable manufacturer's instructions 

concerning pulling tension and bending radius shall be observed. Unless 

the cable manufacturer's recommendation is more stringent, the minimum 

bending radius shall be 10 times the cable diameter for copper cables 

and 20 times the cable diameter for fiber optic cables.

    (3) Cable sheath removal. (i) The length of cable sheath to be 

removed shall be governed by the type of splicing hardware used. Follow 

the splice case manufacturer's recommendations. For pedestals or large 

pair count splice housings, consider removing enough cable sheath to 

allow the conductors to extend to the top of the pedestal and then to 

hang downward to approximately 15 centimeters (cm) (6 inches (in.)) 

above the baseplate.

    (ii) Caution shall be exercised to avoid damaging the conductor 

insulation when cutting through the cable shield and removing the 

shield. Sharp edges and burrs shall be removed from the cut end of the 

shield.

    (4) Shield bonding and grounding. For personnel safety, the shields 

of the cables to be spliced shall be bonded together and grounded before 

splicing activities are started. (See paragraphs (g)(2), and (g)(5)(i) 

through (g)(5)(iii) of this section for final bonding and grounding 

provisions.)

    (5) Binder group identification. (i) Color coded plastic tie wraps 

shall be placed loosely around each binder group of cables before 

splicing operations are attempted. The tie wraps shall be installed as 

near the cable sheath as practicable and shall conform to the same color 

designations as the binder ribbons. Twisted wire pigtails shall not be 

used to identify binder groups due to potential transmission 

degradation.

    (ii) The standard insulation color code used to identify individual 

cable pairs within 25-pair binder groups shall be as shown in Table 1:



         Table 1--Cable Pair Identification Within Binder Groups

------------------------------------------------------------------------

                                                    Color

             Pair No.              -------------------------------------

                                            Tip               Ring

------------------------------------------------------------------------

1.................................  White.............  Blue.

2.................................  White.............  Orange.

3.................................  White.............  Green.

4.................................  White.............  Brown.

5.................................  White.............  Slate.

6.................................  Red...............  Blue.

7.................................  Red...............  Orange.

8.................................  Red...............  Green.

9.................................  Red...............  Brown.

10................................  Red...............  Slate.

11................................  Black.............  Blue.

12................................  Black.............  Orange.

13................................  Black.............  Green.

14................................  Black.............  Brown.

15................................  Black.............  Slate.

16................................  Yellow............  Blue.

17................................  Yellow............  Orange.

18................................  Yellow............  Green.

19................................  Yellow............  Brown.

20................................  Yellow............  Slate.

21................................  Violet............  Blue.

22................................  Violet............  Orange.

23................................  Violet............  Green.



[[Page 460]]





24................................  Violet............  Brown.

25................................  Violet............  Slate.

------------------------------------------------------------------------



    (iii) The standard binder ribbon color code used to designate 25-

pair binder groups within 600-pair super units shall be as shown in 

Table 2:



               Table 2--Cable Binder Group Identification

------------------------------------------------------------------------

                                                              Group pair

            Group No.                  Color of bindings         count

------------------------------------------------------------------------

1................................  White-Blue...............    1-25

2................................  White-Orange.............   26-50

3................................  White-Green..............   51-75

4................................  White-Brown..............  76-100

5................................  White-Slate..............  101-125

6................................  Red-Blue.................  126-150

7................................  Red-Orange...............  151-175

8................................  Red-Green................  176-200

9................................  Red-Brown................  201-225

10...............................  Red-Slate................  226-250

11...............................  Black-Blue...............  251-275

12...............................  Black-Orange.............  276-300

13...............................  Black-Green..............  301-325

14...............................  Black-Brown..............  326-350

15...............................  Black-Slate..............  351-375

16...............................  Yellow-Blue..............  376-400

17...............................  Yellow-Orange............  401-425

18...............................  Yellow-Green.............  426-450

19...............................  Yellow-Brown.............  451-475

20...............................  Yellow-Slate.............  476-500

21...............................  Violet-Blue..............  501-525

22...............................  Violet-Orange............  526-550

23...............................  Violet-Green.............  551-575

24...............................  Violet-Brown.............  576-600

------------------------------------------------------------------------



    (iv) Super-unit binder groups shall be identified in accordance with 

Table 3:



                    Table 3--Super-Unit Binder Colors

------------------------------------------------------------------------

                Pair numbers                         Binder color

------------------------------------------------------------------------

1-600......................................  White.

601-1200...................................  Red.

1201-1800..................................  Black.

1801-2400..................................  Yellow.

2401-3000..................................  Violet.

3001-3600..................................  Blue.

3601-4200..................................  Orange.

4201-4800..................................  Green.

4801-5400..................................  Brown.

5401-6000..................................  Slate.

------------------------------------------------------------------------



    (v) Service pairs in screened cables shall be identified in 

accordance with Table 4:



           Table 4--Screened Cable Service Pair Identification

------------------------------------------------------------------------

                                                    Color

         Service pair No.          -------------------------------------

                                            Tip               Ring

------------------------------------------------------------------------

1.................................  White.............  Red.

2.................................  White.............  Black.

3.................................  White.............  Yellow.

4.................................  White.............  Violet.

                                    Red...............  Black.

6.................................  Red...............  Yellow.

7.................................  Red...............  Violet.

8.................................  Black.............  Yellow.

9.................................  Black.............  Violet.

------------------------------------------------------------------------



    (6) Cleaning conductors. It is not necessary to remove the filling 

compound from cable conductors before splicing. However, it is 

permissible to wipe individual conductors with clean paper towels or 

clean cloth rags. No cleaning chemicals, etc., shall be used. Caution 

shall be exercised to maintain individual cable pair and binder group 

identity. Binder group identity shall be maintained by using color coded 

plastic tie wraps. Individual pair identification shall be maintained by 

carefully twisting together the two conductors of each pair.

    (7) Expanded plastic insulated conductor (PIC) precautions. Solid 

PIC and expanded (foam or foam skin) PIC are spliced in the same manner, 

using the same tools and materials and, in general, should be treated 

the same. However, the insulation on expanded PIC is much more fragile 

than solid PIC. Twisting or forming expanded PIC into extremely compact 

splice bundles and applying excessive amounts of tension when tightening 

tie wraps causes shiners and, thus shall be avoided.

    (8) Splice connectors. (i) Only RUS accepted filled splice 

connectors shall be used on outside plant projects financed by RUS.

    (ii) Specialized connectors are available for splicing operations 

such as butt splices, in line splices, bridge taps, clearing and 

capping, and multiple pair splicing operations. The splice connector 

manufacturer's recommendations shall be followed concerning connector 

selection and use.

    (iii) Caution shall be exercised to maintain conductor and pair 

association both during and after splicing operations.

    (iv) Splicing operations that involve pairs containing working 

services shall



[[Page 461]]



utilize splice connectors that permit splicing without the interruption 

of service.

    (9) Piecing out conductors. Conductors may be pieced-out to provide 

additional slack or to repair damaged conductors. However, the 

conductors shall be pieced-out with conductors having the same gauge and 

type and color of insulation. The conductors used for piecing-out shall 

be from cables having RUS acceptance.

    (10) Splice organization. Spliced pair bundles shall be arranged in 

firm lay-ups with minimum conductor tension in accordance with the 

manufacturer's instructions.

    (11) Binder tape. Perforated nonhygroscopic and nonwicking binder 

tape should be applied to splices housed in filled splice cases. The 

binder tape allows the flow of filling compound while holding the splice 

bundles near the center of the splice case to allow adequate coverage of 

filling compound.

    (12) Cable tags. Cables shall be identified by a tag indicating the 

cable manufacturer's name, cable size, date of placement, and generic 

route information. Information susceptible to changes caused by future 

cable throws and rearrangements should not be included. Tags on load 

coil stubs shall include the serial number of the coil case, the 

manufacturer's name, and the inductance value.

    (13) Screened cable. Screened PIC cable is spliced in the same 

manner as nonscreened PIC cable. However, special considerations are 

necessary due to differences in the cable design. The transmit and 

receive bundles of the cable shall be separated and one of the bundles 

shall be wrapped with shielding material in accordance with the cable 

manufacturer's recommendations. When acceptable to the cable 

manufacturer, it is permissible to use either the scrap screening tape 

removed from the cable during the sheath opening process provided the 

screening tape is edge coated or new pressure sensitive aluminum foil 

tape over polyethylene tape.

    (14) Service wire connections. (i) Buried service wires may be 

spliced directly to cable conductors inside pedestals using the same 

techniques required for branch cables. Buried service wires may also be 

terminated on terminal blocks inside pedestals in areas where high 

service order activity or fixed count cable administration policies 

require terminal blocks. However, only RUS accepted terminal blocks 

equipped with grease or gel filled terminations to provide moisture and 

corrosion resistance shall be used.

    (ii) Only filled terminal blocks having RUS acceptance shall be used 

on aerial service wire connections.

    (15) Copper cable testing. Copper cable testing shall be performed 

in accordance with RUS Bulletin 345-63, ``RUS Standard for Acceptance 

Tests and Measurements of Telephone Plant,'' PC-4, (Incorporated by 

reference at Sec. 1755.97).

    (16) Cable acceptance. Installed cable shall be tested and pass the 

inventory and acceptance testing specified in the Telephone System 

Construction Contract (Labor and Materials), RUS Form 515. The tests and 

inspections shall be witnessed by the borrower's resident project 

representative. All conductors shall be free from grounds, shorts, 

crosses, splits, and opens.

    (d) Splice arrangements for copper cables--(1) Service distribution 

closures. (i) Ready access closures permit cable splicing activities and 

the installation of filled terminal blocks for service wire connections 

in the same closure. Ready access designs shall allow service 

technicians direct access to the cable core as well as the terminal 

block.

    (ii) Fixed count terminals shall restrict service technician access 

to the cable core. Predetermined cable pairs shall be spliced to the 

terminal leads or stub cable in advance of service assignments.

    (2) Aerial splices. Aerial splice cases accommodate straight 

splices, branch splices, load coils, and service distribution terminals. 

Aerial splicing arrangements having more than 4 cables spliced in the 

same splice case are not recommended. Stub cabling to a second splice 

case to avoid a congested splice is acceptable.

    (3) Buried splices. (i) Direct buried splice cases accommodate 

straight splices, branch splices, and load coils. Direct buried splices 

shall be filled and



[[Page 462]]



shall be used only when above ground splicing in pedestals is not 

practicable.

    (ii) A treated plank or equivalent shall be placed 15 cm (6 in.) 

above the buried splice case to prevent damage to the splice case from 

future digging. Where a firm base for burying a splice cannot be 

obtained, a treated plank or equivalent shall be placed beneath the 

splice case.

    (iii) Each buried splice shall be identified for future locating. 

One method of marking the splice point is the use of a warning sign. 

Another method is the burying of an electronic locating device.

    (4) BD-type pedestals. (i) BD-type pedestals are housings primarily 

intended to house, organize, and protect cable terminations 

incorporating splice connectors, ground lugs, and load coils. Activities 

typically performed in pedestals are cable splicing, shield bonding and 

grounding, loading, and connection of subscriber service drops.

    (ii) The recommended splice capacities for BD-type pedestals are 

shown in Table 5. However, larger size pedestals are permissible if 

service requirements dictate their usefulness. Table 5 is as follows:



            Table 5--Splice Capacities for BD-Type Pedestals

------------------------------------------------------------------------

                                                          Maximum load

                                    Maximum straight       splice pair

                                  splice pair capacity   capacity using

                                    using single pair      single pair

          Pedestal type               connectors or       connectors or

                                  multiple pair splice    multiple pair

                                         modules         splice modules

                                                          (see note 1)

------------------------------------------------------------------------

BD3, BD3A.......................  100 Pair............  50 Pair.

BD4, BD4A.......................  200 Pair............  100 Pair.

BD5, BD5A.......................  600 Pair............  300 Pair.

BD7.............................  1200 Pair...........  600 Pair.

BD14, BD14A.....................  100 Pair............  50 Pair.

BD15, BD15A.....................  400 Pair............  200 Pair.

BD16, BD16A.....................  600 Pair............  300 Pair.

------------------------------------------------------------------------

Note 1: This table refers to load coil cases that are to be direct

  buried with stub cables extending into the pedestal for splicing.

  Requirements involving individual coil arrangements inside the

  pedestal should be engineered on a case-by-case basis.



    (iii) Special distribution pedestals having a divider plate for 

mounting filled terminal blocks are available. Distribution pedestals 

are also equipped with service wire channels for installation of buried 

service wires without disturbing the cabling and gravel inside the base 

of the pedestal. Distribution pedestals are recommended in locations 

where the connection of service wires is required.

    (5) Large pair count splice housings. Large pair count splice 

housings are recommended for areas not suitable for man- holes. The 

recommended capacities are shown in Table 6:



           Table 6--Splice Capacities for Large Count Housings

------------------------------------------------------------------------

                                                          Maximum load

                                   Maximum straight       splice pair

                                 splice pair capacity    capacity using

                                  using single pair       single pair

         Housing type               connectors or        connectors or

                                 multiple pair splice    multiple pair

                                       modules           splice modules

                                                          (see note 1)

------------------------------------------------------------------------

BD 6000.......................  6,000 Pair...........  3,000 Pair.

BD 8000.......................  8,000 Pair...........  4,000 Pair.

BD 10000......................  10,000 Pair..........  5,000 Pair.

------------------------------------------------------------------------



    (6) Pedestal restricted access inserts. Restricted access inserts 

may be used to protect splices susceptible to unnecessary handling where 

subsequent work activities are required or expected to occur after 

splices have been completed. Restricted access inserts also provide 

moisture protection in areas susceptible to temporary flooding. A 

typical restricted access insert is shown in Figure 1:



[[Page 463]]



[GRAPHIC] [TIFF OMITTED] TR26JA95.002



    (7) Serving Area Interface (SAI) Systems. SAI systems provide the 

cross-connect point between feeder and distribution cables. Connection 

of feeder to distribution pairs is accomplished by placing jumpers 

between connecting blocks. Only RUS accepted connecting blocks having 

grease or gel filled terminations to provide moisture and corrosion 

resistance shall be used.

    (8) Buried cable splicing arrangements. Typical buried cable 

splicing arrangements are illustrated in Figures 2 through 5:



[[Page 464]]



[GRAPHIC] [TIFF OMITTED] TR26JA95.003





[[Page 465]]





[GRAPHIC] [TIFF OMITTED] TR26JA95.004





[[Page 466]]





[GRAPHIC] [TIFF OMITTED] TR26JA95.005





[[Page 467]]





[GRAPHIC] [TIFF OMITTED] TR26JA95.006



    (9) Underground splices (manholes). Underground splice cases 

accommodate straight splices, branch splices, and load coils. 

Underground splices shall be filled.

    (10) Central office tip cable splices. (i) Filled cable or filled 

splices are not recommended for use inside central offices, except in 

cable vault locations. Outside plant cable sheath and cable filling 

compound are susceptible to fire and will support combustion. Fire, 

smoke, and gases generated by these materials during burning are 

detrimental to telephone switching equipment.

    (ii) Tip cables should be spliced in a cable vault. However, as a 

last resort, tip cables may be spliced inside a central office if flame 

retardant splice cases or a noncombustible central office splice housing 

is used to contain the splice.

    (iii) Splices inside the central office shall be made as close as 

practical to



[[Page 468]]



the point where the outside plant cables enter the building. Except in 

cable vault locations, outside plant cables within the central office 

shall be wrapped with fireproof tape or enclosed in noncombustible 

conduit.

    (e) Splicing considerations for fiber optic cables--(1) Connection 

characteristics. Splicing efficiency between optical fibers is a 

function of light loss across the fiber junctions measured in decibels 

(dB). A loss of 0.2 dB in a splice corresponds to a light transmission 

efficiency of approximately 95.5 percent.

    (2) Fiber core alignment. Fiber splicing techniques shall be 

conducted in such a manner that the cores of the fibers will be aligned 

as perfectly as possible to allow maximum light transmission from one 

fiber to the next. Without proper alignment, light will leave the fiber 

core and travel through the fiber cladding. Light outside the fiber core 

is not a usable light signal. Core misalignment is illustrated in Figure 

6:

[GRAPHIC] [TIFF OMITTED] TR26JA95.007



    (3) Splice loss. (i) Splice loss can also be caused by fiber defects 

such as nonidentical core diameters, cores not in center of the fiber, 

and noncircular cores. Such defects are depicted in Figure 7:



[[Page 469]]



[GRAPHIC] [TIFF OMITTED] TR26JA95.008



    (ii) Undesirable splice losses are caused by poor splicing 

techniques including splicing irregularities such as improper cleaves 

and dirty splices. Typical cleave problems are illustrated in Figure 8:



[[Page 470]]



[GRAPHIC] [TIFF OMITTED] TR26JA95.009



    (4) Handling precautions. The following precautions shall be 

observed:

    (i) Avoid damaging the cable during handling operations prior to 

splicing. Minor damage may change the transmission characteristics of 

the fibers to the extent that the cable section will have to be 

replaced;

    (ii) The cable manufacturer's recommendations concerning pulling 

tension shall be observed. The maximum pulling tension for most fiber 

optic cable is 2669 newtons (600 pound-force);

    (iii) The cable manufacturer's recommendations concerning bending 

radius shall be observed. Unless the cable manufacturer's recommendation 

is more stringent, the minimum bending radius for fiber optic cable 

shall be 20 times the cable diameter;

    (iv) The cable manufacturer's recommendations concerning buffer tube 

bending radius shall be observed. Unless the cable manufacturer's 

recommendation is more stringent, the minimum bending radius for buffer 

tubes is usually between 38 millimeters (mm) (1.5 in.) and 76 mm (3.0 

in.). The bending limitations on buffer tubes are intended to prevent 

kinking. Buffer tube kinking may cause excessive optical loss or fiber 

breakage; and

    (v) Handle unprotected glass fibers carefully to avoid introducing 

flaws such as scratched or broken fibers.

    (5) Personnel safety. The following safety precautions shall be 

observed:

    (i) Safety glasses shall be worn when handling glass fibers;



[[Page 471]]



    (ii) Never view open-ended fibers with the naked eye or a magnifying 

device. Improper viewing of a fiber end that is transmitting light may 

cause irreparable eye damage; and

    (iii) Dispose of bare scrap fibers by using the sticky side of a 

piece of tape to pick up and discard loose fiber ends. Fiber scraps 

easily penetrate the skin and are difficult to remove.

    (6) Equipment requirements. (i) Fiber optic splices shall be made in 

areas where temperature, humidity, and cleanliness can be controlled. 

Both fusion and mechanical splicing techniques may require a splicing 

vehicle equipped with a work station that will allow environmental 

control.

    (ii) Both fusion and mechanical splicing techniques are permitted on 

RUS financed projects. When using the mechanical splicing technique, 

only RUS accepted mechanical fiber optic splice connectors can be used.

    (iii) Fusion splicing machines shall be kept in proper working 

condition. Regular maintenance in accordance with the machine 

manufacturer's recommendations shall be observed.

    (iv) Mechanical splicing tools shall be in conformance with the tool 

manufacturer's recommendations.

    (v) An optical time domain reflectometer (OTDR) shall be used for 

testing splices. The OTDR shall be stationed at the central office or 

launch point for testing individual splices as they are made and for 

end-to-end signature tests for the fiber optic link.

    (vi) An optical power meter shall be used for end-to-end cable 

acceptance tests.

    (vii) A prerequisite for the successful completion of a fiber optic 

splicing endeavor is the presence of a talk circuit between the splicing 

technician in the splicing vehicle and the operator of the OTDR in the 

central office. The splicing technician and the OTDR operator shall have 

access to communications with each other in order to inform each other 

as to:

    (A) Which splices meet the loss objectives;

    (B) The sequence in which buffer tubes and fibers are to be selected 

for subsequent splicing operations; and

    (C) The timing required for the performance of OTDR testing to 

prevent making an OTDR test at the same time a splice is being fused.

    (7) Cable preparation. (i) Engineering work prints shall prescribe 

the cable slack needed at splice points to reach the work station inside 

the splicing vehicle. Consideration should be given to the slack 

required for future maintenance activity as well as initial construction 

activities. The required slack may be different for each splice point, 

depending on the site logistics. However, the required slack is seldom 

less than 15 meters (50 feet). The amount of slack actually used shall 

be recorded for each splice point to assist future maintenance and 

restoration efforts.

    (ii) The splice case manufacturer's recommendations concerning the 

amount of cable sheath to be removed shall be followed to facilitate 

splicing operations. The length of the sheath opening shall be 

identified with a wrap of plastic tape.

    (iii) If the cable contains a rip cord, the cable jacket shall be 

ring cut approximately 15 cm (6 in.) from the end and the 15 cm (6 in.) 

of cable jacket shall be removed to expose the rip cord. The rip cord 

shall be used to slit the jacket to the tape mark.

    (iv) If the cable does not contain a rip cord, the cable jacket 

shall be slit using a sheath splitter. No cuts shall be made into the 

cable core nor shall the buffer tubes be damaged.

    (v) If the cable contains an armor sheath, the outer jacket shall be 

opened along the slit and the jacket shall be removed exposing the armor 

sheath. The armor shall be separated at the seam and pulled from the 

cable exposing the inner jacket. The armor shall be removed making 

allowances for a shield bond connector. The inner sheath shall be slit 

using a sheath splitter or rip cord. The cable core shall not be damaged 

nor shall there be any damage to the buffer tubes. The jacket shall be 

peeled back and cut at the end of the slit. The exposed buffer tubes 

shall not be cut, kinked, or bent.

    (vi) After the cable sheath has been removed, the binder tape shall 

be removed from the cable. The cable shall not be crushed or deformed.

    (vii) The buffer tubes shall be unstranded one at a time. The buffer 

tubes shall not be kinked.



[[Page 472]]



    (viii) If the cable is equipped with a strength member, the strength 

member shall be cut to the length recommended by the splice case 

manufacturer.

    (ix) Each buffer tube shall be inspected for kinks, cuts, and flat 

spots. If damage is detected, an additional length of cable jacket shall 

be removed and all of the buffer tubes shall be cut off at the point of 

damage.

    (x) The cable preparation sequence shall be repeated for the other 

cable end.

    (8) Shield bonding and grounding. For personnel safety, the shields 

and metallic strength members of the cables to be spliced shall be 

bonded together and grounded before splicing activities are started. 

(See paragraphs (g)(4), and (g)(5)(i) through (g)(5)(iii) of this 

section for final bonding and grounding provisions).

    (9) Fiber optic color code. The standard fiber optic color code for 

buffer tubes and individual fibers shall be as shown in Table 7:



              Table 7--Fiber and Buffer Tube Identification

------------------------------------------------------------------------

     Buffer tube and fiber No.                      Color

------------------------------------------------------------------------

 1.................................  Blue.

 2.................................  Orange.

 3.................................  Green.

 4.................................  Brown.

 5.................................  Slate.

 6.................................  White.

 7.................................  Red.

 8.................................  Black.

 9.................................  Yellow.

10.................................  Violet.

11.................................  Rose.

12.................................  Aqua.

13.................................  Blue/Black Tracer.

14.................................  Orange/Black Tracer.

15.................................  Green/Black Tracer.

16.................................  Brown/Black Tracer.

17.................................  Slate/Black Tracer.

18.................................  White/Black Tracer.

19.................................  Red/Black Tracer.

20.................................  Black/Yellow Tracer.

21.................................  Yellow/Black Tracer.

22.................................  Violet/Black Tracer.

23.................................  Rose/Black Tracer.

24.................................  Aqua/Black Tracer.

------------------------------------------------------------------------



    (10) Buffer tube removal. (i) The splice case manufacturer's 

recommendation shall be followed concerning the total length of buffer 

tube to be removed. Identify the length to be removed with plastic tape.

    (ii) Experiment with a scrap buffer tube to determine the cutting 

tool adjustment required to ring cut a buffer tube without damaging the 

fibers.

    (iii) Buffer tubes shall be removed by carefully ring cutting and 

removing approximately 15 to 46 cm (6 to 18 in.) of buffer tube at a 

time. The process shall be repeated until the required length of buffer 

tube has been removed, including the tape identification marker.

    (11) Coated fiber cleaning. (i) Each coated fiber shall be cleaned. 

The cable manufacturer's recommendations shall be followed concerning 

the solvent required to clean the coated fibers. Reagent grade isopropyl 

alcohol is a commonly used cleaning solvent.

    (ii) A tissue or cotton ball shall be soaked in the recommended 

cleaning solvent and the coated fibers shall be carefully wiped one at a 

time using a clean tissue or cotton ball for each coated fiber. Caution 

shall be exercised to avoid removing the coloring agent from the fiber 

coating.

    (12) Fiber coating removal. (i) Fiber coatings shall be removed. In 

accordance with the splicing method used, the splice case manufacturer's 

recommendation shall be followed concerning the length of fiber coating 

to be removed.

    (ii) The recommended length of fiber coating shall be removed only 

on the two fibers to be spliced. Fiber coating removal shall be 

performed on a one-fiber-at-a-time basis as each splice is prepared.

    (13) Bare fiber cleaning. After the fiber coating has been removed, 

the bare fibers shall be cleaned prior to splicing. Each fiber shall be 

wiped with a clean tissue or cotton ball soaked with the cleaning 

solvent recommended by the cable manufacturer. The bare fiber shall be 

wiped one time to minimize fiber damage. Aggressive wiping of bare fiber 

shall be avoided as it lowers the fiber tensile strength.

    (14) Fiber cleaving. Cleaving tools shall be clean and have sharp 

cutting edges to minimize fiber scratches and improper cleave angles. 

Cleaving tools that are recommended by the manufacturer of the splicing 

system shall be used.

    (15) Cleaved fiber handling. The cleaved and cleaned fiber shall not 

be allowed to touch other objects and



[[Page 473]]



shall be inserted into the splicing device.

    (16) Completion of the splice. (i) In accordance with the method of 

splicing selected by the borrower, the splice shall be completed by 

either fusing the splice or by applying the mechanical connector.

    (ii) Each spliced fiber shall be routed through the organizer tray 

one at a time as splices are completed. The fibers shall be organized 

one at a time to prevent tangled spliced fibers. The splice case 

manufacturer's recommendation shall be followed concerning the splice 

tray selection.

    (17) Fiber optic testing. Fiber optic testing shall be performed in 

accordance with RUS Bulletin 345-63, ``RUS Standard for Acceptance Tests 

and Measurements of Telephone Plant,'' PC-4, (Incorporated by reference 

at Sec. 1755.97).

    (18) Cable acceptance. Installed cable shall be tested and pass the 

inventory and acceptance testing specified in the Telephone System 

Construction Contract (Labor and Materials), RUS Form 515. The tests and 

inspections shall be witnessed by the borrower's resident project 

representative.

    (f) Splice arrangements for fiber optic cables--(1) Aerial splices. 

Cable slack at aerial splices shall be stored either on the messenger 

strand, on the pole, or inside a pedestal at the base of the pole. A 

typical arrangement for the storage of slack cable at aerial splices is 

shown in Figure 9:



[[Page 474]]



[GRAPHIC] [TIFF OMITTED] TR26JA95.010



    (2) Buried splices. Buried splices shall be installed in handholes 

to accommodate the splice case and the required splicing slack. An 

alternative to the handhole is a pedestal specifically designed for 

fiber optic splice cases. Typical arrangements for buried cable splices 

are shown in Figures 10 and 11:



[[Page 475]]



[GRAPHIC] [TIFF OMITTED] TR26JA95.011





[[Page 476]]





[GRAPHIC] [TIFF OMITTED] TR26JA95.012



    (3) Underground manhole splices. Underground splices shall be stored 

in manholes on cable hooks and racks fastened to the manhole wall. The 

cable slack shall be stored on cable hooks and racks as shown in Figure 

12:



[[Page 477]]



[GRAPHIC] [TIFF OMITTED] TR26JA95.013



    (4) Central office cable entrance. (i) Filled cable or filled 

splices are not recommended for use inside central offices except in 

cable vault locations. Outside plant cable sheath and cable filling 

compound are susceptible to fire and will support combustion. Fire, 

smoke, and gases generated by these materials during burning are 

detrimental to telephone switching equipment.

    (ii) As a first choice, the outside plant fiber optic cable shall be 

spliced to an all-dielectric fire retardant cable in a cable vault with 

the all-dielectric cable extending into the central office and 

terminating inside a fiber patch panel.

    (iii) As a second choice, the outside plant cable may be spliced 

inside the central office if a flame retardant fiber optic splice case 

or a noncombustible central office splice housing equipped with 

organizer trays is used to contain the splice.

    (iv) In cases referenced in paragraphs (f)(4)(ii) and (f)(4)(iii) of 

this section, as a minimum the fire retardant all-dielectric cable used 

to provide the connection between the cable entrance splice and the 

fiber patch panel shall be listed as Communication Riser Cable (Type 

CMR) in accordance with Sections 800-50 and 800-51(b) of the 1993 

National Electrical Code.

    (v) Splices inside the central office shall be made as close as 

practicable to



[[Page 478]]



the point where the outside plant cables enter the building. Except in 

cable vault locations, outside plant cables within the central office 

shall be wrapped with fireproof tape or enclosed in noncombustible 

conduit.

    (g) Bonding and grounding fiber optic cable, copper cable, and 

copper service wire--(1) Bonding. Bonding is electrically connecting two 

or more metallic items of telephone hardware to maintain a common 

electrical potential. Bonding may involve connections to another 

utility.

    (2) Copper cable shield bond connections. (i) Cable shields shall be 

bonded at each splice location. Only RUS accepted cable shield bond 

connectors shall be used to provide bonding and grounding connections to 

metallic cable shields. The shield bond connector manufacturer's 

instructions shall be followed concerning installation and use.

    (ii)(A) Shield bonding conductors shall be either stranded or 

braided tinned copper wire equivalent to a minimum No. 6 American Wire 

Gauge (AWG) and shall be RUS accepted. The conductor connections shall 

be tinned or of a compatible bimetallic design to avoid corrosion 

problems associated with dissimilar metals. The number of shield bond 

connectors required per pair size and gauge shall be as shown in Table 

8:



         Table 8--Shield Bond Connectors per Pair Size and Gauge

------------------------------------------------------------------------

                            Pair size and gauge                 No. of

             ------------------------------------------------   shield

   19 AWG                                                        bond

                  22 AWG          24 AWG          26 AWG      connectors

------------------------------------------------------------------------

        0-25           0-100           0-150           0-200           1

      50-100         150-300         200-400         300-600           2

     150-200         400-600         600-900        900-1500           3

     300-600        900-1200       1200-2100       1800-3600           4

------------------------------------------------------------------------



    (B) It is permissible to strap across the shield bond connectors of 

several cables with a single length of braided wire. However, both ends 

of the braid shall be terminated on the pedestal ground bracket to 

provide a bonding loop. Shield bond connection methods for individual 

cables are shown in Figures 13 through 15, and the bonding of several 

cables inside a pedestal using the bonding loop is shown in Figure 16:



[[Page 479]]



[GRAPHIC] [TIFF OMITTED] TR26JA95.014





[[Page 480]]





[GRAPHIC] [TIFF OMITTED] TR26JA95.015





[[Page 481]]





[GRAPHIC] [TIFF OMITTED] TR26JA95.016





[[Page 482]]





[GRAPHIC] [TIFF OMITTED] TR26JA95.017



    (3) Buried service wire shield bond connections. Buried service wire 

shields shall be connected to the pedestal bonding and grounding system. 

Typical buried service wire installations are shown in Figures 17 and 

18. In addition to the methods referenced in Figures 17 and 18, the 

shields of buried service wires may also be connected to the pedestal 

bonding and grounding system using buried service wire bonding harnesses 

listed on Page 3.3.1, Item ``gs-b,'' of RUS Bulletin 1755I-100. RUS 

Bulletin 1755I-100 may be purchased from the



[[Page 483]]



Superintendent of Documents, U.S. Government Printing Office, 

Washington, DC 20402. When those harnesses are used they shall be 

installed in accordance with the manufacturer's instructions. Figures 17 

and 18 are as follows:

[GRAPHIC] [TIFF OMITTED] TR26JA95.018





[[Page 484]]





[GRAPHIC] [TIFF OMITTED] TR26JA95.019



    (4) Fiber optic cable bond connections. (i) The cable shield and 

metallic strength members shall be bonded at each splice location. Only 

RUS accepted fiber optic cable shield bond connectors shall be used to 

provide bonding connections to the metallic cable shields. The shield 

bond connector manufacturer's instructions shall be followed concerning 

installation and use.

    (ii) Shield bonding conductors shall be either stranded or braided 

tinned copper wire equivalent to a minimum No. 6 American Wire Gauge 

(AWG) and shall be RUS accepted. The conductor connections shall be 

tinned or of a compatible bimetallic design to avoid corrosion problems 

associated with dissimilar metals.

    (5) Grounding. (i) Grounding is electrically connecting metallic 

telephone hardware to a National Electrical Safety Code (NESC) 

acceptable grounding electrode. Acceptable grounding electrodes are 

defined in the Rule 99A of the NESC.



[[Page 485]]



    (ii) The conductor used for grounding metallic telephone hardware 

shall be a minimum No. 6 AWG solid, bare, copper conductor.

    (iii) For copper and fiber optic cable plant, all cable shields, all 

metallic strength members, and all metallic hardware shall be:

    (A) Grounded at each splice location to a driven grounding electrode 

(ground rod) of:

    (1) At least 1.5 meters (5 feet) in length where the local frost 

level is normally less than 0.30 meters (1 foot) deep; or

    (2) At least 2.44 meters (8 feet) in length where the local frost 

level is normally 0.30 meters (1 foot) or deeper; and

    (B) Bonded to a multi-grounded power system neutral when the splice 

is within 1.8 meters (6 feet) of access to the grounding system of the 

multi-grounded neutral system. Bonding to the multi-grounded neutral of 

a parallel power line may help to minimize telephone interference on 

long exposures with copper cable plant. Consideration, thus, should be 

given to completing such bonds, at least four (4) times each mile, when 

splices are greater than 1.8 meters (6 feet) but less than 4.6 meters 

(15 feet) from access to the multi-grounded neutral.

    (6) Bonding and grounding splice cases. (i) Splice cases are 

equipped with bonding and grounding devices to ensure that cable shields 

and metallic strength members maintain electrical continuity during and 

after cable splicing operations. The splice case manufacturer's 

recommendations shall be followed concerning the bonding and grounding 

procedures. Conductors used for bonding shall be either stranded or 

braided tinned copper wire equivalent to 6 AWG. Conductors used for 

grounding shall be a solid, bare, copper wire equivalent to minimum No. 

6 AWG.

    (ii) Buried splice cases installed in either handholes or pedestals 

shall be grounded such that the cable shield grounds are attached to a 

common ground connection that will allow the lifting of a ground on the 

cable shield in either direction to permit efficient cable locating 

procedures. As a first choice, buried grounding conductor(s) shall be 

bare. However, if two or more grounding conductors are buried in the s 

they shall be insulated to avoid shorts when a locating tone is applied.

    (iii) A typical bonding and grounding method for fiber optic splices 

is shown in Figure 19:



[[Page 486]]



[GRAPHIC] [TIFF OMITTED] TR26JA95.020



    (7) Bonding and grounding central office cable entrances. The RUS 

Telecommunications Engineering and Construction Manual (TE&CM) Section 

810 provides bonding and grounding guidance for central office cable 

entrances. Splicing operations shall not be attempted before all 

metallic cable shield and strength members are bonded and grounded.



[60 FR 5097, Jan. 26, 1995; 60 FR 9079, Feb. 16, 1995]



[[Page 487]]