[Code of Federal Regulations]

[Title 40, Volume 12]

[Revised as of July 1, 2006]

From the U.S. Government Printing Office via GPO Access

[CITE: 40CFR63.1547]



[Page 98-101]

 

                   TITLE 40--PROTECTION OF ENVIRONMENT

 

         CHAPTER I--ENVIRONMENTAL PROTECTION AGENCY (CONTINUED)

 

PART 63_NATIONAL EMISSION STANDARDS FOR HAZARDOUS AIR POLLUTANTS FOR 

SOURCE CATEGORIES--Table of Contents

 

Subpart TTT_National Emission Standards for Hazardous Air Pollutants for 

                          Primary Lead Smelting

 

Sec.  63.1547  Monitoring requirements.



    (a) Owners and operators of primary lead smelters shall prepare, and 

at all times operate according to, a standard operating procedures 

manual that describes in detail the procedures for inspection, 

maintenance, and bag leak detection and corrective action for all 

baghouses that are used to control process, process fugitive, or 

fugitive dust emissions from any source subject to the lead emission 

standards in Sec. Sec.  63.1543 and 63.1544, including those used to 

control emissions from general ventilation systems.

    (b) The standard operating procedures manual for baghouses required 

by paragraph (a) of this section shall be submitted to the Administrator 

or delegated authority for review and approval.

    (c) The procedures specified in the standard operating procedures 

manual for inspections and routine maintenance shall, at a minimum, 

include the requirements of paragraphs (c)(1) through (c)(9) of this 

section.

    (1) Daily monitoring of pressure drop across each baghouse cell to 

ensure pressure drop is within the normal operating range identified in 

the standard operating procedures manual.

    (2) Weekly confirmation that dust is being removed from hoppers 

through visual inspection or equivalent means of ensuring the proper 

functioning of removal mechanisms.

    (3) Daily check of compressed air supply for pulse-jet baghouses.

    (4) An appropriate methodology for monitoring cleaning cycles to 

ensure proper operation.

    (5) Monthly check of bag cleaning mechanisms for proper functioning 

through visual inspection or equivalent means.

    (6) Quarterly visual check of bag tension on reverse air and shaker-

type baghouses to ensure that bags are not kinked (kneed or bent) or 

laying on their sides. Such checks are not required for shaker-type 

baghouses using self-tensioning (spring loaded) devices.

    (7) Quarterly confirmation of the physical integrity of the baghouse



[[Page 99]]



through visual inspection of the baghouse interior for air leaks.

    (8) Quarterly inspection of fans for wear, material buildup, and 

corrosion through visual inspection, vibration detectors, or equivalent 

means.

    (9) Except as provided in paragraph (h) of this section, continuous 

operation of a bag leak detection system.

    (d) The procedures specified in the standard operating procedures 

manual for maintenance shall, at a minimum, include a preventative 

maintenance schedule that is consistent with the baghouse manufacturer's 

instructions for routine and long-term maintenance.

    (e) The bag leak detection system required by paragraph (c)(9) of 

this section shall meet the specifications and requirements of (e)(1) 

through (e)(8) of this section.

    (1) The bag leak detection system must be certified by the 

manufacturer to be capable of detecting particulate matter emissions at 

concentrations of 10 milligram per actual cubic meter (0.0044 grains per 

actual cubic foot) or less.

    (2) The bag leak detection system sensor must provide output of 

relative particulate matter loadings, and the owner or operator shall 

continuously record the output from the bag leak detection system.

    (3) The bag leak detection system must be equipped with an alarm 

system that will sound when an increase in relative particulate loading 

is detected over a preset level, and the alarm must be located such that 

it can be heard by the appropriate plant personnel.

    (4) Each bag leak detection system that works based on the 

triboelectric effect shall be installed, calibrated, and maintained in a 

manner consistent with guidance provided in the U.S. Environmental 

Protection Agency guidance document ``Fabric Filter Bag Leak Detection 

Guidance'' (EPA-454/R-98-015). Other bag leak detection systems shall be 

installed, calibrated, and maintained in a manner consistent with the 

manufacturer's written specifications and recommendations.

    (5) The initial adjustment of the system shall, at a minimum, 

consist of establishing the baseline output by adjusting the sensitivity 

(range) and the averaging period of the device, and establishing the 

alarm set points and the alarm delay time.

    (6) Following initial adjustment, the owner or operator shall not 

adjust the sensitivity or range, averaging period, alarm set points, or 

alarm delay time, except as detailed in the approved SOP required under 

paragraph (a) of this section. In no event shall the sensitivity be 

increased by more than 100 percent or decreased more than 50 percent 

over a 365-day period unless a responsible official certifies that the 

baghouse has been inspected and found to be in good operating condition.

    (7) For negative pressure, induced air baghouses, and positive 

pressure baghouses that are discharged to the atmosphere through a 

stack, the bag leak detector must be installed downstream of the 

baghouse and upstream of any wet acid gas scrubber.

    (8) Where multiple detectors are required, the system's 

instrumentation and alarm may be shared among detectors.

    (f) The standard operating procedures manual required by paragraph 

(a) of this section shall include a corrective action plan that 

specifies the procedures to be followed in the event of a bag leak 

detection system alarm. The corrective action plan shall include, at a 

minimum, procedures to be used to determine the cause of an alarm, as 

well as actions to be taken to minimize emissions, which may include, 

but are not limited to, the following.

    (1) Inspecting the baghouse for air leaks, torn or broken bags or 

filter media, or any other condition that may cause an increase in 

emissions.

    (2) Sealing off defective bags or filter media.

    (3) Replacing defective bags or filter media, or otherwise repairing 

the control device.

    (4) Sealing off a defective baghouse compartment.

    (5) Cleaning the bag leak detection system probe, or otherwise 

repairing the bag leak detection system.

    (6) Shutting down the process producing the particulate emissions.



[[Page 100]]



    (g) The percentage of total operating time the alarm on the bag leak 

detection system sounds in a 6-month reporting period shall be 

calculated in order to determine compliance with the five percent 

operating limit in Sec.  63.1543(f). The percentage of time the alarm on 

the bag leak detection system sounds shall be determined according to 

paragraphs (g)(1) through (g)(5) of this section.

    (1) Alarms that occur due solely to a malfunction of the bag leak 

detection system shall not be included in the calculation.

    (2) Alarms that occur during startup, shutdown, or malfunction shall 

not be included in the calculation if the condition is described in the 

startup, shutdown, and malfunction plan and the owner or operator 

operates the source during such periods in accordance with Sec.  

63.6(e)(1).

    (3) For each alarm where the owner or operator initiates procedures 

to determine the cause of an alarm within 1 hour of the alarm, 1 hour of 

alarm time shall be counted.

    (4) For each alarm where the owner or operator does not initiate 

procedures to determine the cause of the alarm within 1 hour of the 

alarm, alarm time will be counted as the actual amount of time taken by 

the owner or operator to initiate procedures to determine the cause of 

the alarm.

    (5) The percentage of time the alarm on the bag leak detection 

system sounds shall be calculated as the ratio of the sum of alarm times 

to the total operating time multiplied by 100.

    (h) Baghouses equipped with HEPA filters as a secondary filter used 

to control process or process fugitive sources subject to the lead 

emission standards in Sec.  63.1543 are exempt from the requirement in 

Sec.  63.1543(c)(9) to be equipped with a bag leak detector. The owner 

or operator of an affected source that uses a HEPA filter shall monitor 

and record the pressure drop across the HEPA filter system daily. If the 

pressure drop is outside the limit(s) specified by the filter 

manufacturer, the owner or operator must take appropriate corrective 

measures, which may include, but not be limited to, the following:

    (1) Inspecting the filter and filter housing for air leaks and torn 

or broken filters.

    (2) Replacing defective filter media, or otherwise repairing the 

control device.

    (3) Sealing off a defective control device by routing air to other 

control devices.

    (4) Shutting down the process producing the particulate emissions.

    (i) Owners and operators shall monitor sinter machine building in-

draft to demonstrate continued compliance with the operating standard 

specified in Sec.  63.1543(c) in accordance with either paragraph 

(i)(1), (i)(2), or (i)(3) of this section.

    (1) Owners and operators shall check and record on a daily basis 

doorway in-draft at each doorway in accordance with the methodology 

specified in Sec.  63.1546(b).

    (2) Owners and operators shall establish and maintain baseline 

ventilation parameters which result in a positive in-draft according to 

paragraphs (i)(2)(i) through (i)(2)(iv) of this section.

    (i) Owners and operators shall install, calibrate, maintain, and 

operate a monitoring device that continuously records the actual 

volumetric flow rate through each separately ducted hood; or install, 

calibrate, maintain, and operate a monitoring device that continuously 

records the volumetric flow rate at the control device inlet of each 

exhaust system ventilating the building. The flow rate monitoring 

device(s) can be installed in any location in the exhaust duct such that 

reproducible flow rate monitoring will result. The flow rate monitoring 

device(s) shall have an accuracy of plus or minus 10 percent over its 

normal operating range and shall be calibrated according to 

manufacturer's instructions.

    (ii) During the initial demonstration of sinter building in-draft, 

and at any time the owner or operator wishes to re-establish the 

baseline ventilation parameters, the owner or operator shall 

continuously record the volumetric flow rate through each separately 

ducted hood, or continuously record the volumetric flow rate at the 

control device inlet of each exhaust system ventilating the building and



[[Page 101]]



record exhaust system damper positions. The owner or operator shall 

determine the average volumetric flow rate(s) corresponding to the 

period of time the in-draft compliance determinations are being 

conducted.

    (iii) The owner or operator shall maintain the volumetric flow 

rate(s) at or above the value(s) established during the most recent in-

draft determination at all times the sinter machine is in operation. 

Volumetric flow rate(s) shall be calculated as a 15-minute average.

    (iv) If the volumetric flow rate is monitored at the control device 

inlet, the owner or operator shall check and record damper positions 

daily to ensure they are in the positions they were in during the most 

recent in-draft determination.

    (3) An owner or operator may request an alternative monitoring 

method by following the procedures and requirements in Sec.  63.8(f) of 

the General Provisions.



[64 FR 30204, June 4, 1999, as amended at 71 FR 20462, Apr. 20, 2006]