[Code of Federal Regulations]
[Title 46, Volume 1]
[Revised as of January 1, 2007]
From the U.S. Government Printing Office via GPO Access
[CITE: 46CFR34.10-5]

[Page 453-454]
 
                           TITLE 46--SHIPPING
 
         CHAPTER I--COAST GUARD, DEPARTMENT OF HOMELAND SECURITY
 
PART 34_FIREFIGHTING EQUIPMENT--Table of Contents
 
                 Subpart 34.10_Fire Main System, Details
 
Sec. 34.10-5  Fire pumps--T/ALL.

    (a) Tankships shall be equipped with independently driven fire pumps 
in accordance with table 34.10-5(a).

[[Page 454]]



                      Table 34.10-5(a)--Fire Pumps
------------------------------------------------------------------------
Size vessel,  L.O.A.                                Minimum hydrant and
       (feet)            Minimum      Powerful      hose size (inches)
---------------------   number of    streams of  -----------------------
           Not over--     pumps       water per    Exterior    Interior
  Over--                                pump       stations    stations
------------------------------------------------------------------------
               100          (\1\)   ............  ..........  ..........
    100        250          \2\ 1         \3\ 2      1\1/2\      1\1/2\
    250        400              2         \3\ 2      1\1/2\      1\1/2\
    400        650              2         \3\ 2   \4\ 2\1/2\     1\1/2\
    650    .........            2         \3\ 3   \4\ 2\1/2\     1\1/2\
------------------------------------------------------------------------
\1\ Vessels of 65 feet and not over 100 feet shall be equipped with 2 B-
  V extinguishers. (Refer to Table 34.50-5(c).) Vessels under 65 feet
  shall be equipped with 1 B-V extinguisher. (Refer to Table 34.50-
  5(c).)
\2\ Vessels of 1,000 gross tons and over on an international voyage
  shall have at least 2 fire pumps.
\3\ From hydrants having greatest pressure drop between fire-pump(s) and
  nozzles.
\4\ Where 2\1/2\-inch hydrant size is required, two 1\1/2\-inch outlets
  may be substituted therefor with two 1\1/2\-inch hoses.

    (b) Each pump shall be capable of delivering simultaneously the 
number of streams of water required by table 34.10-5(a) from the outlets 
having the greatest pressure drop between fire pump(s) and nozzles at a 
Pitot tube pressure of approximately 75 p.s.i. Where 1\1/2\-inch hose is 
permitted in lieu of 2\1/2\-inch hose by footnote 3 of Table 34.10-5(a), 
the pump capacity shall be determined on the basis that both hoses are 
used.
    (c) On tankships of 1,000 gross tons and over on an international 
voyage, each required fire pump, while delivering water through the fire 
main system at a pressure corresponding to that required by Sec. 34.10-
15(e), shall have a minimum capacity of at least two-thirds of that 
required for an independent bilge pump if no length correction is taken 
for the cargo tank space. However, in no case shall the capacity of each 
fire pump be less than that otherwise required by this section.
    (d) Fire pumps shall be fitted on the discharge side with relief 
valves set to relieve at 25 p.s.i. in excess of the pressure necessary 
to maintain the requirements of paragraph (b) of this section.
    (e) Fire pumps shall be fitted with a pressure gage on the discharge 
side of the pumps.
    (f) Fire pumps may be used for other purposes provided at least one 
of the required pumps is kept available for use on the fire system at 
all times. In no case shall a pump having connection to an oil line be 
used as a fire pump. Branch lines connected to the fire main for 
purposes other than fire and deck wash shall be arranged so that the 
requirements of paragraph (b) of this section and any other services 
installed on the fire main can be met simultaneously.
    (g) On all vessels where two fire pumps are required, they shall be 
located in separate spaces, and the arrangement of pumps, sea 
connections, and sources of power shall be such as to insure that a fire 
in any one space will not put all of the fire pumps out of operation. 
However, where it is shown to the satisfaction of the Commandant that it 
is unreasonable or impracticable to meet this requirement due to the 
size, or arrangement of the vessel, or for other reasons, the 
installation of a total flooding carbon dioxide system may be accepted 
as an alternate method of extinguishing any fire which would affect the 
powering and operation of at least one of the required fire pumps.

[CGFR 65-50, 30 FR 16694, Dec. 30, 1965, as amended by CGD 95-028, 62 FR 
51199, Sept. 30, 1997]