                           TITLE 46--SHIPPING
 
         CHAPTER I--COAST GUARD, DEPARTMENT OF HOMELAND SECURITY
 
PART 34_FIREFIGHTING EQUIPMENT--Table of Contents
 
       Subpart 34.15_Carbon Dioxide Extinguishing Systems, Details
 
Sec. 34.15-30  Alarms--T/ALL.

    (a) Spaces required to have a delayed discharge by Sec. 34.15-10(f) 
which are protected by a carbon dioxide extinguishing system and are 
normally accessible to persons on board while the vessel is being 
navigated, other than paint and lamp lockers and similar small spaces, 
shall be fitted with an approved audible alarm in such spaces which will 
be automatically sounded before the carbon dioxide is admitted to the 
space. The alarm shall be conspicuously and centrally located and shall 
be marked as required by Sec. 35.40-7 of this subchapter. Such alarms 
shall be so arranged as to sound during the 20-second delay period prior 
to the discharge of carbon dioxide into the space, and the alarm shall 
depend on no source of power other than the carbon dioxide.