[Code of Federal Regulations]
[Title 46, Volume 1]
[Revised as of January 1, 2007]
From the U.S. Government Printing Office via GPO Access
[CITE: 46CFR34.20-20]

[Page 466]
 
                           TITLE 46--SHIPPING
 
         CHAPTER I--COAST GUARD, DEPARTMENT OF HOMELAND SECURITY
 
PART 34_FIREFIGHTING EQUIPMENT--Table of Contents
 
                 Subpart 34.20_Deck Foam System, Details
 
Sec. 34.20-20  Discharge outlets--T/ALL.

    (a) Discharge outlets shall be of an approved type.
    (b) At least one mounted foam appliance shall be provided for each 
station that is required in Sec. 34.20-15(c).
    (c) The number of hand-held appliances provided shall be at least 
equal to the number of hose outlets at the two foam stations having the 
most hose outlets. Hand-held appliances shall be stowed in a well 
marked, readily accessible position that cannot be isolated by a fire 
involving the cargo tanks.

[CGFR 65-50, 30 FR 16694, Dec. 30, 1965, as amended by CGD 72-138, 39 FR 
7790, Feb. 28, 1974]