                           TITLE 46--SHIPPING
 
         CHAPTER I--COAST GUARD, DEPARTMENT OF HOMELAND SECURITY
 
PART 34_FIREFIGHTING EQUIPMENT--Table of Contents
 
        Subpart 34.25_Water Spray Extinguishing Systems, Details
 
Sec. 34.25-10  Controls--T/ALL.

    (a) There shall be one control valve for the operation of the system 
located in an accessible position outside the space protected. The 
control shall be located as convenient as practicable to one of the main 
escapes from the space protected, and shall be marked as required by 
Sec. 35.40-18 of this subchapter. It shall not be necessary to start 
the pumps from the control space.
    (b) Complete, but simple instructions for the operation of the 
system shall be located in a conspicuous place at or near the controls.
    (c) The valve to the space protected shall be marked as required by 
Sec. 35.40-18 of this subchapter.