[Code of Federal Regulations]
[Title 24, Volume 5]
[Revised as of April 1, 2008]
From the U.S. Government Printing Office via GPO Access
[CITE: 24CFR3280.208]

[Page 120-121]
 
                 TITLE 24--HOUSING AND URBAN DEVELOPMENT
 
 CHAPTER XX--OFFICE OF ASSISTANT SECRETARY FOR HOUSING--FEDERAL HOUSING 
        COMMISSIONER, DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT
 
PART 3280_MANUFACTURED HOME CONSTRUCTION AND SAFETY STANDARDS--Table of Contents
 
                          Subpart C_Fire Safety
 
Sec. 3280.208  Smoke alarm requirements.

    (a) Labeling. Each smoke alarm required under paragraph (b) of this 
section must conform with the requirements of UL 217, Single and 
Multiple Station Smoke Alarms, dated January 4, 1999 (incorporated by 
reference, see Sec. 3280.4), or UL 268, Smoke Detectors for Fire 
Protective Signaling Systems, dated January 4, 1999 (incorporated by 
reference, see Sec. 3280.4), and must bear a label to evidence 
conformance.
    (b) Required smoke alarm locations. (1) At least one smoke alarm 
must be installed in each of the following locations:
    (i) To protect both the living area and kitchen space. Manufacturers 
are encouraged to locate the alarm in the living area remote from the 
kitchen and cooking appliances. A smoke alarm located within 20 feet 
horizontally of a cooking appliance must incorporate a temporary 
silencing feature or be of a photoelectric type.
    (ii) In each room designed for sleeping.
    (iii) On the ceiling of the upper level near the top or above each 
stairway, other than a basement stairway, in any multistory home 
completed in accordance with this part or part 3282 of this chapter. The 
alarm must be located so that smoke rising in the stairway cannot be 
prevented from reaching the alarm by an intervening door or obstruction.
    (2) For each home designed to be placed over a basement, the 
manufacturer must provide a smoke alarm for the basement and must 
install at the factory an electrical junction box for the installation 
of this smoke alarm and for its interconnection to other smoke alarms 
required by this section. The instructions for installers and 
information for homeowners required in paragraph (f) of this section 
must clearly indicate that a smoke alarm should be installed and is to 
be located on the basement ceiling near the stairway.
    (3) A smoke alarm required under this section must not be placed in 
a location that impairs its effectiveness or in any of the following 
locations:
    (i) Within 3 feet horizontally from any discharge grille when a home 
is equipped or designed for future installation of a roof-mounted 
evaporative cooler or other equipment discharging conditioned air 
through a ceiling grille into the living space; and
    (ii) In any location or environment that is prohibited by the terms 
of its listing, except as permitted by this section.
    (c) Mounting requirements. (1) Except in rooms with peaked sloping 
or shed sloping ceilings with a slope of more than 1.5/12 or as 
permitted pursuant to paragraph (e) of this section, smoke alarms must 
be mounted either:
    (i) On the ceiling at least 4 inches from each wall; or
    (ii) On a wall with the top of the alarm not less than 4 inches 
below the ceiling, and not farther from the ceiling than 12 inches or 
the distance from the ceiling specified in the smoke alarm 
manufacturer's listing and instructions, whichever is less.
    (2) Except as permitted pursuant to paragraph (e) of this section, 
in rooms with peaked sloping ceilings with a slope of more than 1.5/12, 
smoke alarms must be mounted on the ceiling within 3 feet, measured 
horizontally, from the peak of the ceiling; at least 4 inches, measured 
vertically, below the peak of the ceiling; and at least 4 inches from 
any projecting structural element.
    (3) Except as permitted pursuant to paragraph (e) of this section, 
in rooms with shed sloping ceilings with a slope of more than 1.5/12, 
smoke alarms must be mounted on the ceiling within 3 feet, measured 
horizontally, of the high side of the ceiling, and not closer than 4 
inches from any adjoining wall surface and from any projecting 
structural element.
    (d) Connection to power source. (1) Each smoke alarm must be powered 
from:
    (i) The electrical system of the home as the primary power source 
and a battery as a secondary power source; or
    (ii) A battery rated for a 10-year life, provided the smoke alarm is 
listed for use with a 10-year battery.

[[Page 121]]

    (2) Each smoke alarm whose primary power source is the home 
electrical system must be mounted on an electrical outlet box and 
connected by a permanent wiring method to a general electrical circuit. 
More than one smoke alarm is permitted to be placed on the same 
electrical circuit. The wiring circuit for the alarm must not include 
any switches between the over-current protective device and the alarm, 
and must not be protected by a ground fault circuit interrupter.
    (3) Smoke alarms required under this section must be interconnected 
such that the activation of any one smoke alarm causes the alarm to be 
triggered in all required smoke alarms in the home.
    (e) Visible and tactile notification appliances. (1) In addition to 
the smoke alarms required pursuant to this section, the manufacturer 
must provide visible and listed tactile notification appliances if these 
appliances are ordered by the purchaser or retailer before the home 
enters the first stage of production. These appliances are required to 
operate from the primary power source, but are not required to operate 
from a secondary power source.
    (2) A visible notification appliance in a room designed for sleeping 
must have a minimum rating of 177 candela, except that when the visible 
notification appliance is wall-mounted or suspended more than 24 inches 
below the ceiling, a minimum rating of 110 candela is permitted.
    (3) A visible notification appliance in an area other than a room 
designed for sleeping must have a minimum rating of 15 candela.
    (f) Testing and maintenance. (1) Each required smoke alarm installed 
at the factory must be operationally tested, after conducting the 
dielectric test specified in Sec. 3280.810(a), in accordance with the 
alarm manufacturer's instructions. A smoke alarm that does not function 
as designed during the test and is not fixed so that it functions 
properly in the next retest must be replaced. Any replacement smoke 
alarm must be successfully tested in accordance with this paragraph.
    (2) Home manufacturers must provide specific written instructions 
for installers on how to inspect and test the operation of smoke alarms 
during installation of the home. These instructions must indicate that 
any smoke alarm that does not meet the inspection or testing 
requirements needs to be replaced and retested.
    (3) Home manufacturers must provide the homeowner with the alarm 
manufacturer's information describing the operation, method and 
frequency of testing, and proper maintenance of the smoke alarm. This 
information must be provided in same manner and location as the consumer 
manual required by Sec. 3282.207 of this chapter, but does not have to 
be incorporated into the consumer manual. No dealer, distributor, 
construction contractor, or other person shall interfere with the 
distribution of this information

[67 FR 12817, Mar. 19, 2002, as amended at 67 FR 49795, July 31, 2002]