[Code of Federal Regulations]
[Title 24, Volume 4]
[Revised as of April 1, 2008]
From the U.S. Government Printing Office via GPO Access
[CITE: 24CFR982.401]

[Page 604-607]
 
                 TITLE 24--HOUSING AND URBAN DEVELOPMENT
 
CHAPTER IX--OFFICE OF ASSISTANT SECRETARY FOR PUBLIC AND INDIAN HOUSING, 
               DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT
 
PART 982_SECTION 8 TENANT BASED ASSISTANCE: HOUSING CHOICE VOUCHER PROGRAM--Table of Contents
 
 Subpart I_Dwelling Unit: Housing Quality Standards, Subsidy Standards, 
                       Inspection and Maintenance
 
Sec. 982.401  Housing quality standards (HQS).

    Source: 60 FR 34695, July 3, 1995, unless otherwise noted.


    (a) Performance and acceptability requirements. (1) This section 
states the housing quality standards (HQS) for housing assisted in the 
programs.
    (2)(i) The HQS consist of:
    (A) Performance requirements; and
    (B) Acceptability criteria or HUD approved variations in the 
acceptability criteria.
    (ii) This section states performance and acceptability criteria for 
these key aspects of housing quality:
    (A) Sanitary facilities;
    (B) Food preparation and refuse disposal;
    (C) Space and security;
    (D) Thermal environment;
    (E) Illumination and electricity;
    (F) Structure and materials;
    (G) Interior air quality;
    (H) Water supply;
    (I) Lead-based paint;
    (J) Access;
    (K) Site and neighborhood;
    (L) Sanitary condition; and
    (M) Smoke detectors.
    (3) All program housing must meet the HQS performance requirements 
both at commencement of assisted occupancy, and throughout the assisted 
tenancy.
    (4)(i) In addition to meeting HQS performance requirements, the 
housing must meet the acceptability criteria stated in this section, 
unless variations are approved by HUD.
    (ii) HUD may approve acceptability criteria variations for the 
following purposes:
    (A) Variations which apply standards in local housing codes or other 
codes adopted by the PHA; or
    (B) Variations because of local climatic or geographic conditions.
    (iii) Acceptability criteria variations may only be approved by HUD 
pursuant to paragraph (a)(4)(ii) of this section if such variations 
either:
    (A) Meet or exceed the performance requirements; or
    (B) Significantly expand affordable housing opportunities for 
families assisted under the program.
    (iv) HUD will not approve any acceptability criteria variation if 
HUD believes that such variation is likely to adversely affect the 
health or safety of participant families, or severely restrict housing 
choice.
    (b) Sanitary facilities--(1) Performance requirements. The dwelling 
unit must include sanitary facilities located in the unit. The sanitary 
facilities must be in proper operating condition, and adequate for 
personal cleanliness and the disposal of human waste. The sanitary 
facilities must be usable in privacy.
    (2) Acceptability criteria. (i) The bathroom must be located in a 
separate private room and have a flush toilet in proper operating 
condition.
    (ii) The dwelling unit must have a fixed basin in proper operating 
condition, with a sink trap and hot and cold running water.
    (iii) The dwelling unit must have a shower or a tub in proper 
operating condition with hot and cold running water.
    (iv) The facilities must utilize an approvable public or private 
disposal system (including a locally approvable septic system).
    (c) Food preparation and refuse disposal--(1) Performance 
requirement. (i) The dwelling unit must have suitable space and 
equipment to store, prepare, and serve foods in a sanitary manner.
    (ii) There must be adequate facilities and services for the sanitary 
disposal of food wastes and refuse, including facilities for temporary 
storage where necessary (e.g, garbage cans).
    (2) Acceptability criteria. (i) The dwelling unit must have an oven, 
and a stove or range, and a refrigerator of appropriate size for the 
family. All of the

[[Page 605]]

equipment must be in proper operating condition. The equipment may be 
supplied by either the owner or the family. A microwave oven may be 
substituted for a tenant-supplied oven and stove or range. A microwave 
oven may be substituted for an owner-supplied oven and stove or range if 
the tenant agrees and microwave ovens are furnished instead of an oven 
and stove or range to both subsidized and unsubsidized tenants in the 
building or premises.
    (ii) The dwelling unit must have a kitchen sink in proper operating 
condition, with a sink trap and hot and cold running water. The sink 
must drain into an approvable public or private system.
    (iii) The dwelling unit must have space for the storage, 
preparation, and serving of food.
    (iv) There must be facilities and services for the sanitary disposal 
of food waste and refuse, including temporary storage facilities where 
necessary (e.g., garbage cans).
    (d) Space and security--(1) Performance requirement. The dwelling 
unit must provide adequate space and security for the family.
    (2) Acceptability criteria. (i) At a minimum, the dwelling unit must 
have a living room, a kitchen area, and a bathroom.
    (ii) The dwelling unit must have at least one bedroom or living/
sleeping room for each two persons. Children of opposite sex, other than 
very young children, may not be required to occupy the same bedroom or 
living/sleeping room.
    (iii) Dwelling unit windows that are accessible from the outside, 
such as basement, first floor, and fire escape windows, must be lockable 
(such as window units with sash pins or sash locks, and combination 
windows with latches). Windows that are nailed shut are acceptable only 
if these windows are not needed for ventilation or as an alternate exit 
in case of fire.
    (iv) The exterior doors of the dwelling unit must be lockable. 
Exterior doors are doors by which someone can enter or exit the dwelling 
unit.
    (e) Thermal environment--(1) Performance requirement. The dwelling 
unit must have and be capable of maintaining a thermal environment 
healthy for the human body.
    (2) Acceptability criteria. (i) There must be a safe system for 
heating the dwelling unit (and a safe cooling system, where present). 
The system must be in proper operating condition. The system must be 
able to provide adequate heat (and cooling, if applicable), either 
directly or indirectly, to each room, in order to assure a healthy 
living environment appropriate to the climate.
    (ii) The dwelling unit must not contain unvented room heaters that 
burn gas, oil, or kerosene. Electric heaters are acceptable.
    (f) Illumination and electricity--(1) Performance requirement. Each 
room must have adequate natural or artificial illumination to permit 
normal indoor activities and to support the health and safety of 
occupants. The dwelling unit must have sufficient electrical sources so 
occupants can use essential electrical appliances. The electrical 
fixtures and wiring must ensure safety from fire.
    (2) Acceptability criteria. (i) There must be at least one window in 
the living room and in each sleeping room.
    (ii) The kitchen area and the bathroom must have a permanent ceiling 
or wall light fixture in proper operating condition. The kitchen area 
must also have at least one electrical outlet in proper operating 
condition.
    (iii) The living room and each bedroom must have at least two 
electrical outlets in proper operating condition. Permanent overhead or 
wall-mounted light fixtures may count as one of the required electrical 
outlets.
    (g) Structure and materials--(1) Performance requirement. The 
dwelling unit must be structurally sound. The structure must not present 
any threat to the health and safety of the occupants and must protect 
the occupants from the environment.
    (2) Acceptability criteria. (i) Ceilings, walls, and floors must not 
have any serious defects such as severe bulging or leaning, large holes, 
loose surface materials, severe buckling, missing parts, or other 
serious damage.
    (ii) The roof must be structurally sound and weathertight.

[[Page 606]]

    (iii) The exterior wall structure and surface must not have any 
serious defects such as serious leaning, buckling, sagging, large holes, 
or defects that may result in air infiltration or vermin infestation.
    (iv) The condition and equipment of interior and exterior stairs, 
halls, porches, walkways, etc., must not present a danger of tripping 
and falling. For example, broken or missing steps or loose boards are 
unacceptable.
    (v) Elevators must be working and safe.
    (h) Interior air quality--(1) Performance requirement. The dwelling 
unit must be free of pollutants in the air at levels that threaten the 
health of the occupants.
    (2) Acceptability criteria. (i) The dwelling unit must be free from 
dangerous levels of air pollution from carbon monoxide, sewer gas, fuel 
gas, dust, and other harmful pollutants.
    (ii) There must be adequate air circulation in the dwelling unit.
    (iii) Bathroom areas must have one openable window or other adequate 
exhaust ventilation.
    (iv) Any room used for sleeping must have at least one window. If 
the window is designed to be openable, the window must work.
    (i) Water supply--(1) Performance requirement. The water supply must 
be free from contamination.
    (2) Acceptability criteria. The dwelling unit must be served by an 
approvable public or private water supply that is sanitary and free from 
contamination.
    (j) Lead-based paint performance requirement. The Lead-Based Paint 
Poisoning Prevention Act (42 U.S.C. 4821-4846), the Residential Lead-
Based Paint Hazard Reduction Act of 1992 (42 U.S.C. 4851-4856), and 
implementing regulations at part 35, subparts A, B, M, and R of this 
title apply to units assisted under this part.
    (k) Access performance requirement. The dwelling unit must be able 
to be used and maintained without unauthorized use of other private 
properties. The building must provide an alternate means of exit in case 
of fire (such as fire stairs or egress through windows).
    (l) Site and Neighborhood--(1) Performance requirement. The site and 
neighborhood must be reasonably free from disturbing noises and 
reverberations and other dangers to the health, safety, and general 
welfare of the occupants.
    (2) Acceptability criteria. The site and neighborhood may not be 
subject to serious adverse environmental conditions, natural or manmade, 
such as dangerous walks or steps; instability; flooding, poor drainage, 
septic tank back-ups or sewage hazards; mudslides; abnormal air 
pollution, smoke or dust; excessive noise, vibration or vehicular 
traffic; excessive accumulations of trash; vermin or rodent infestation; 
or fire hazards.
    (m) Sanitary condition--(1) Performance requirement. The dwelling 
unit and its equipment must be in sanitary condition.
    (2) Acceptability criteria. The dwelling unit and its equipment must 
be free of vermin and rodent infestation.
    (n) Smoke detectors performance requirement--(1) Except as provided 
in paragraph (n)(2) of this section, each dwelling unit must have at 
least one battery-operated or hard-wired smoke detector, in proper 
operating condition, on each level of the dwelling unit, including 
basements but excepting crawl spaces and unfinished attics. Smoke 
detectors must be installed in accordance with and meet the requirements 
of the National Fire Protection Association Standard (NFPA) 74 (or its 
successor standards). If the dwelling unit is occupied by any hearing-
impaired person, - smoke detectors must have an alarm system, designed 
for hearing-impaired persons as specified in NFPA 74 (or successor 
standards).
    (2) For units assisted prior to April 24, 1993, owners who installed 
battery-operated or hard-wired smoke detectors prior to April 24, 1993 
in compliance with HUD's smoke detector requirements, including the 
regulations published on July 30, 1992, (57 FR 33846), will not be 
required subsequently to comply with any additional requirements 
mandated by NFPA 74 (i.e., the owner would not be required to install a 
smoke detector in a basement not used for living purposes, nor would the 
owner be required to change the location of the smoke detectors that 
have

[[Page 607]]

already been installed on the other floors of the unit).

[60 FR 34695, July 3, 1995, as amended at 61 FR 27163, May 30, 1996; 63 
FR 23861, Apr. 30, 1998; 64 FR 26646, May 14, 1999; 64 FR 49658, Sept. 
14, 1999; 64 FR 50230, Sept. 15, 1999]